Pre-drilling estimates save the most expensive mistake in earthing: digging a full contour and discovering it misses the target. The classical formulas below predict the resistance of rods and strips from soil resistivity and geometry within roughly 10–20% — good enough to choose the number of electrodes. For the final word, always measure on site and have a licensed engineer sign off the design.
Key takeaways
- Single rod: R = ρ / (2πL) × ln(4L/d) — resistivity, length and diameter are the only inputs.
- Groups need a utilisation factor η (typical value): 1.0 for one rod, 0.85 up to three, 0.75 up to five, 0.65 above.
- Horizontal strip: R = ρ / (2πL) × ln(2L²/(b×h)) — long shallow strips are efficient in good soil.
- Full example: 3 rods × 3 m, Ø16 mm, ρ = 100 Ω·m, η = 0.85 → about 13.8 Ω.
- The model assumes one uniform soil layer and identical electrodes — frozen topsoil or rock beneath breaks it.
- Rod resistance is DC/low-frequency behaviour; lightning surges see impulse impedance, a different quantity.
What the formula assumes
All formulas in this article model one uniform layer of soil with resistivity ρ (ohm-metres, Ω·m) and electrodes fully in contact with it. Real ground is layered, dries and freezes — so treat every result as an estimate with roughly ±10–20% error, then verify by measurement. The GorkyCAD earthing calculator uses the same family of formulas with a burial-depth correction and a single-layer soil model.
Single rod formula
For one vertical rod of length L (m) and diameter d (m) in soil ρ:
R = ρ / (2πL) × ln(4L/d)
Length helps twice: it divides directly and sits inside the logarithm. Diameter matters weakly — doubling it shaves only about 10%. Depth of burial adds a small correction term (our calculator includes it); the simplified form above is enough for hand estimates. Longer rods beat thicker rods, always.
Strip and ring formula
For a horizontal steel strip of length L (m), width b (m), buried with its axis at depth h (m):
R = ρ / (2πL) × ln(2L² / (b×h))
The same expression covers a ring earth electrode (a closed loop around the building): use the total ring length as L. Rings combine electrode and interconnection in one trench, which is why they often beat separate rods in collaborators' cost comparisons.
Groups of rods: the utilisation factor
Rods placed close together shield each other — three rods give less than three times one rod. The group resistance is:
R = R1 / (n × η)
| Rods in a row, n | Utilisation factor η (typical value) |
|---|---|
| 1 | 1.00 |
| 2–3 | 0.85 |
| 4–5 | 0.75 |
| More than 5 | 0.65 |
Spacing matters: these factors assume rods at least one rod-length apart. Cramming rods shoulder to shoulder wastes steel — spread them. US readers: NEC 250.53(A)(3) requires rods at least 1.8 m (6 ft) apart.
Soil resistivity and seasonal correction
Resistivity is the dominant input — and the least certain. Reference values (typical values, confirm by Wenner 4-pin measurement per IEEE 81):
| Soil | ρ, Ω·m (typical) |
|---|---|
| Black soil | 30 |
| Clay, wet | 40 |
| Clay, dry | 80 |
| Loam | 100 |
| Sand, wet | 150 |
| Sand, dry | 500 |
| Gravel | 800 |
| Rock | 1,000 |
Frozen or dry seasons multiply the reference value: climate zone II ×1.7 for rods and ×3.5 for shallow strips; zone I ×1.9/×5.0; zone III ×1.5/×2.5; zone IV ×1.3/×1.5 (guidance values from design references). A measured resistivity always overrides the table. Our companion guide explains what the target value should be once you have the number.
Full worked example: three rods in loam
Given: n = 3 rods, L = 3 m, d = 16 mm = 0.016 m, loam ρ = 100 Ω·m, η = 0.85.
Step 1 — geometry term: 4L/d = 12 / 0.016 = 750; ln(750) = 6.620.
Step 2 — scale: ρ / (2πL) = 100 / 18.85 = 5.305 Ω.
Step 3 — single rod: R1 = 5.305 × 6.620 = 35.1 Ω.
Step 4 — group: R = 35.1 / (3 × 0.85) = 35.1 / 2.55 = 13.8 Ω.
Bonus — add a 20 m strip (40 mm wide, 0.7 m deep) in the same soil: Rstrip = 100 / 125.7 × ln(800/0.028) = 0.796 × 10.26 = 8.2 Ω. In parallel: (13.8 × 8.2) / (13.8 + 8.2) = 5.1 Ω — ignoring mutual shielding between rods and strip, so the real value reads roughly 10–20% higher. Try variations in the free earthing calculator.
What the result means — and where the model ends
Compare 13.8 Ω (rods only) or ~5 Ω (with strip) against your target from the target-value guide: comfortable for any TT system with an RCD, short of a 10 Ω lightning-protection specification in bad season, and above a 4–5 Ω contractual target — the strip closes that gap. Know the limits: one soil layer only; all electrodes assumed identical; strips assumed straight and orthogonal; steel grade (galvanised, copper-bonded, stainless) changes service life, not the computed resistance; and none of this predicts impulse impedance for lightning currents (IEC 62305-3) — that needs a different analysis. For protection devices downstream of the electrodes see RCD rules and load calculation.
Common mistakes
- Adding rods arithmetically. Three 35 Ω rods give 13.8 Ω, not 11.7 Ω — forgetting η overstates every design.
- Using diameter in centimetres inside the log. Mixed units silently corrupt ln(4L/d). Convert everything to metres first.
- Designing to spring soil. Size for the worst season: ×1.7 on resistivity in zone II turns 13.8 Ω into ~23 Ω.
- Counting the strip twice. The ring is both electrode and interconnection — model it once, in one formula.
- Thicker rods instead of longer ones. Doubling length nearly halves R; doubling diameter saves ~10%. Spend on depth.
- Confusing resistance with impulse impedance. A contour that measures 5 Ω at 50 Hz can look far worse to a lightning surge — do not promise surge performance from a DC reading.
Which formula should I use for a single earth rod?
R = ρ / (2πL) × ln(4L/d), with ρ in Ω·m and L, d in metres. It assumes uniform soil. For a quick check it is accurate within about 10–20%; the final value always comes from measurement.
How do I account for several rods close together?
Divide the single-rod value by n × η, where η is the utilisation factor: 1.0, 0.85, 0.75 or 0.65 for 1, up to 3, up to 5, or more rods. Keep spacing at least one rod length.
What soil resistivity should I assume without a measurement?
Use reference values (loam 100, dry sand 500, rock 1,000 Ω·m) only for preliminary sizing, then measure with the Wenner 4-pin method. A measurement always overrides the table.
Why is my calculated value lower than the measured one?
Usual causes: dry or frozen soil versus the table value, rods closer than assumed, contact resistance from poor backfill, or layered ground the single-layer model cannot see. Re-measure in the worst season.
Does rod material change the calculated resistance?
No — galvanised steel, copper-bonded or stainless give the same computed R. Material governs corrosion life and service conditions, and it is recorded in the specification, not in the formula.