A panel schedule is the document somebody reads at 11 p.m. with a flashlight, one hand on the panel door, trying to work out which breaker kills the circuit they are standing next to. If four different circuits are all described as "lights", it has failed. If it says "Spare" where a breaker is actually installed, it has failed worse.

Below is a working template, the column set that survives real projects, a filled example with the arithmetic shown, and what changes when the schedule is generated from the drawing instead of typed into a spreadsheet. None of this replaces your local code edition: the requirements cited come from NEC Article 408 and the IEC 60364 / 61439 family. Check the current edition before you issue a document.

Author: Guide

What the code actually requires

NEC 408.4 requires every circuit and circuit modification to be legibly identified as to its clear, evident and specific purpose, with enough detail that each circuit can be distinguished from all others. Spare positions containing unused overcurrent devices must be described as spare. That is the whole requirement: identity and honesty. No layout is prescribed.

IEC practice is similar in intent, different in vocabulary. IEC 60364-5-53 covers selection of switchgear, IEC 61439-1/-2 covers the assembly, and IEC 60364-6 covers verification and handover. In IEC projects the schedule usually sits inside a distribution board schedule set with the single-line diagram and test results.

So a schedule has three jobs, in this order: identify every way out of the panel (including spares and future ways), quantify what each carries in VA, amps, breaker rating and conductor size, and prove the panel is neither overloaded nor badly balanced. A template that does not do all three is a label list, not a schedule.

The 12 columns that earn their space

Most templates carry 20+ columns because a form once had them. These twelve cover design, installation, and the person with the flashlight.

# Column Example entry Why it stays
1 Circuit / way 14 Anchor for every other document
2 Description Kitchen counter, south wall Specific purpose, per NEC 408.4
3 Phase / pole L2, 1-pole Balance and panel wiring
4 Breaker rating 20 A Must match conductor ampacity
5 Breaker type 1-pole, AFCI GFCI/AFCI/RCD requirement lives here
6 Conductor 12 AWG Cu, 2-wire + ground Size, material, count
7 Conduit / cable 3/4 in EMT Installation reference for the crew
8 Connected load, VA 1,500 Summable, unlike loosely used "watts"
9 Demand load, VA 1,500 After demand factors, for the total
10 Current, A 12.5 Connected VA divided by voltage
11 Voltage 120 Line-to-neutral vs line-to-line
12 Remarks Spare, future, existing State of the way, at a glance

Two optional columns earn their ink on commercial work: earth-fault loop / disconnection time (IEC projects, where automatic disconnection must be proven) and lockout or arc-flash reference. Everything else — install date, electrician initials — belongs on the panel directory sticker.

Copy-paste template

Plain text, tab-separated, pastes cleanly into Excel, Sheets or a markdown table:

text PANEL: LP-1 | 120/240 V, 1-ph, 3-wire | fed from MSB, 100 A | 125 A bus, 24 sp Ckt | Description | Ph | Breaker | Type | Conductor | VA | Amps | Remarks 1 | Kitchen counter, south | L1 | 20 A | 1p AFCI | 12 AWG Cu | 1500 | 12.5 | GFCI 2 | Kitchen counter, north | L2 | 20 A | 1p AFCI | 12 AWG Cu | 1500 | 12.5 | GFCI SPARES: 21-24 reserved, no breaker installed

The header block matters: a schedule without a rating, a source and a location is not traceable.

Worked example: a 12-circuit apartment panel

Single-phase 120/240 V. Line-to-neutral loads sit on one leg; line-to-line loads span both and split evenly.

Ckt Description VA Breaker / conductor Leg
1 Kitchen counter, south 1,500 20 A / 12 AWG L1
2 Kitchen counter, north 1,500 20 A / 12 AWG L2
3 Dishwasher 1,200 20 A / 12 AWG L1
4 Microwave 1,500 20 A / 12 AWG L2
5 Laundry receptacles 1,500 20 A / 12 AWG L1
6 Bath receptacles, GFCI 1,000 20 A / 12 AWG L2
7 Bedrooms 1,200 15 A / 14 AWG L1
8 Living room 1,000 15 A / 14 AWG L2
9 Lighting 900 15 A / 14 AWG L1
10 Dryer 5,500 30 A / 10 AWG L1-L2
11 Range 8,000 40 A / 8 AWG L1-L2
12 A/C condenser 4,800 25 A / 10 AWG L1-L2

Line-to-neutral: L1 = 1,500 + 1,200 + 1,500 + 1,200 + 900 = 6,300 VA; L2 = 1,500 + 1,500 + 1,000 + 1,000 = 5,000 VA.

Line-to-line: 5,500 + 8,000 + 4,800 = 18,300 VA, or 18,300 / 2 = 9,150 VA per leg.

Per-leg totals: L1 = 6,300 + 9,150 = 15,450 VA; L2 = 5,000 + 9,150 = 14,150 VA. Imbalance = 1,300 VA = 1,300 / 15,450 = 8.4% of the heavier leg. Under 10%, the usual comfort threshold — a practice target, not a code limit.

To improve it, move load from the heavier leg to the lighter one and move less than the gap. Circuit 9 (900 VA) from L1 to L2 gives 14,550 and 15,050 VA — 500 VA apart, 500 / 15,050 = 3.3%. Overshooting is easy: shift circuit 5 (1,500 VA) from L1 to L2 instead and the legs land at 13,950 and 15,650 VA, a 10.9% imbalance that has merely swapped sides. Keep the base of the percentage fixed (the heavier leg) or the numbers stop being comparable.

Connected total: 6,300 + 5,000 + 18,300 = 29,600 VA, which at 240 V is 29,600 / 240 = 123.3 A before any demand factor. After NEC 220 demand factors — the range drops to 8,000 VA under Table 220.55, general lighting takes the first 3,000 VA at 100% and the rest at 35% — the calculated load is materially lower. Do the demand calculation separately; never size a service from the connected column.

For the same circuit list checked against ampacity and volt drop, see the voltage drop calculator walkthrough.

Where templates break

  • Spares that are not spare. A breaker was added on site, the schedule was never updated, and position 21 is now a live 20 A circuit labelled "Spare". NEC 408.4 exists because of this.
  • Room names instead of circuit descriptions. "Living room" is useless when the room has four circuits. "Living room receptacles, north wall" is not.
  • Duplicate circuit numbers across revisions. Two people edit the sheet and both add "13".
  • Schedule and single-line diagram disagree. The single-line diagram shows 18 ways, the schedule lists 20. One is wrong and nobody knows which.

From template to automated schedule

A spreadsheet is fine for one panel. It stops being fine when the panel changes three times and the schedule must change with it, because every edit is manual and can break the link between drawing and document.

Automation means the schedule is a view of design data: the circuit list comes from the single-line diagram, so adding a way adds a row; breaker and conductor fields are checked against ampacity and derating; phase assignment is computed and imbalance reported as you go; spares are a state, so an unused position cannot silently become live; and the PDF carries the same revision as the drawing set. That is what panel schedule software is for — the difference between a template that documents a design and one that argues with it.

Want to see the generated version of the template above? Open the demo project — it loads with a plan, a small panel and a schedule you can edit.

Next step

The template is free to copy. If you would rather have the schedule generated from the plan and the single-line diagram — with breaker, cable and balance checks running as you edit — start with the demo, then compare plans on the pricing page. Product limits and export options are in the docs.

Sources

  • NFPA 70 (NEC) — code development and current edition: https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70
  • NFPA free access to codes and standards: https://www.nfpa.org/codes-and-standards/free-access
  • IEC 60364-5-52:2009 — wiring systems, current-carrying capacity: https://webstore.iec.ch/en/publication/1878
  • IEC 60364-5-53:2001 — selection and erection of switchgear: https://webstore.iec.ch/en/publication/1880
  • Southwire voltage drop calculator (reference implementation): https://www.southwire.com/calculator-vdrop

Standards are revised on a regular cycle and local amendments vary. Verify requirements against the current edition of the applicable code before issuing a design. This article is technical guidance, not a legal or code-compliance opinion.

Is there a required format for a panel schedule in the NEC?
No. NEC 408.4 requires legible identification of each circuit's specific purpose and identification of spares, but prescribes no layout. Local jurisdictions and client standards often do. Check the current edition and local amendments.
Should spare breakers be listed separately from empty spaces?
Yes. An installed but unused breaker is a spare; an empty position with no breaker is a space. Both should appear, labelled differently, because the next person needs to know whether to buy a breaker.
How much spare capacity should a panel have?
Common practice is 20–25% spare ways and 20–30% spare bus capacity — a design convention, not an NEC requirement. Some client standards mandate more.
What is an acceptable phase imbalance?
There is no universal code number. A widely used design target is within 10% between legs at the connected-load stage. Motors and large single-phase loads are what usually break it.
Can I just use an Excel template?
For one small panel, yes. The risk is divergence: schedule and drawing are separate files with separate revisions, and nobody reconciles them.
How does a three-phase schedule differ?
Add A/B/C phase columns, show line-to-line loads as spanning two phases, and total each phase separately. The arithmetic is identical; the imbalance check is between three numbers.