Loads: light, doors, chargers, office
Start with an inventory of everything that consumes power: high-bay lighting across the floor, dock doors and gates with motor drives, the forklift charging zone, the office and amenity block, plus ventilation, heating and fire systems. Each load differs in duty cycle and starting current, so the inventory records rated power, operating hours and simultaneity from day one.
This list sizes the incomer and sets the group structure. Chargers and door motors are continuous and motor loads; lighting is long and steady; the office is a standard small commercial load. Mixing them on shared groups is where warehouse projects start to fail.
- Lighting: high bays, aisles, docks, outdoor yard.
- Drives: dock doors, gates, shutters, dock levellers.
- Chargers: forklifts, pallet trucks, cleaning machines.
- Office and amenities: sockets, IT, heating, ventilation.
High-bay lighting
High-bay LED luminaires with medium or narrow optics serve ceilings of 6–12 metres: light must reach the floor between racks, not scatter under the roof. Spacing follows aisle width and rack height, and a lighting calculation verifies illuminance and uniformity at floor level before a single luminaire is bought. Group luminaires by aisle so one breaker never darkens the whole building.
Divide control into zones — storage aisles, dispatch area, docks — with motion sensors or schedules where traffic is intermittent. Emergency luminaires along escape routes sit on independent circuits. Drivers and control gear go where a lift can reach them without stopping operations below.
Sockets, doors, motors: dedicated groups
Every motor drive gets its own group: dock doors, gates and levellers draw starting currents several times their rated value and briefly drag down shared circuits. Size breakers for the starting regime, add motor protection where required, and keep drives off lighting groups entirely — a door opening at night must not blink the aisle light.
Chargers form a separate panel section near the parking bays, with capacity for simultaneous charging of the whole fleet and sub-metering of energy. Office and amenity sockets follow standard commercial practice on their own residual-current-protected groups. The result is a panel where each section has one owner and one failure domain.
Routes: tray versus conduit
Long runs under high ceilings belong on cable tray: cables stay accessible for inspection, heat dissipates freely, and a new circuit means one more cable on the tray rather than opened walls. Size trays with 20–30% spare capacity — warehouses add equipment constantly. Drops to individual sockets, dock controls and dusty packing zones go in conduit for mechanical protection.
| Run | Recommended | Why |
|---|---|---|
| Highway along the building | Tray | Accessible, ventilated, expandable |
| Drops to sockets and controls | Conduit | Mechanical protection |
| Office block | Conduit or trunking | Finish and fire rules |
Panel, metering and handover
The warehouse panel mirrors the building: incomer with metering, lighting section, drives section, chargers section, office section. Phase balancing keeps unbalance within 15%, and spare ways in every section absorb the next tenant improvement. Verify short-circuit disconnection at the farthest dock socket and voltage drop within the 5% total limit — long warehouse runs make drop the governing check.
Hand over the plan with routes, the single-line diagram, the panel schedule, the cable schedule and the estimate with its price date. GorkyCAD exports this as one PDF set, and stated Pro exports add DXF and IFC for coordination with the general contractor — verify the needed format in the editor first.
Mistakes that inflate the budget
Oversizing everywhere at once is the dearest mistake: luminaires bought without a calculation, cables with triple margin on hundred-metre runs, a panel twice the needed size. The second mistake is the opposite — no spare tray capacity or panel ways, so the first new tenant pays for reconstruction. The third is chargers mixed with lighting, which shows up as flicker and tripped breakers within months.
Run the automated checks before issue: 25 checks against IEC 60364 on the international tier catch missing protection and overloaded groups. Checks assist review; the engineer of record approves the design, and calculations stay preliminary until signed.
Design the warehouse in GorkyCAD
Draw the floor plan in the browser, lay tray highways and conduit drops on it, and let the single-line diagram generate from the model automatically. The estimate with 14-day price freshness shows materials, labour and VAT without spreadsheets, and the panel assembles with balanced phases. Full terms are on the pricing page — Pro €40/mo with 20,000 AI tokens included.
Start free in the editor, check the project against 25 IEC 60364 rules, and export the PDF set the contractor will build from.
FAQ
Which luminaires suit high bays?
High-bay LED luminaires with narrow or medium optics suit ceilings of 6–12 metres: they throw light down to the aisles instead of heating the roof. Choose the optics by aisle width and rack height, verify uniformity on the floor with a lighting calculation, and mount drivers where maintenance can reach them without a full facility shutdown.
Do doors need dedicated groups?
Yes, in most designs. Dock doors, sectional gates and shutters have motors with starting currents that dim shared lighting at the moment of opening, so each drive group gets a dedicated breaker. Separation also keeps a jammed door from taking out the aisle light.
Where should charger loads be fed from?
Feed chargers from their own group sized for simultaneous charging of the fleet, located near the parking bays to keep cable runs short. Forklift chargers are long continuous loads with harmonics, so do not mix them with lighting or office sockets — a dedicated panel section with its own metering is standard practice.
Tray or conduit in a warehouse?
Trays win on long straight runs under high ceilings: cables are accessible, heat dissipates, and adding a circuit means laying one more cable, not opening walls. Conduit suits drops to individual sockets, dusty zones and mechanical-protection sections. Most warehouses combine both — tray highways with conduit drops.
Related articles
- Lighting calculation guide
- Cable trays guide
- Cable tray vs conduit: choosing
- Three-phase supply for buildings