Picking a cable is a two-step job. First you find the current. Then you pick a cross-section that carries it safely. This guide does both: amps and kilowatts to mm² and AWG, for 1-phase 230 V and 3-phase 400 V systems.

You will get a calculator-style procedure, a 1–100 A lookup table, copper vs aluminium notes, and derating for temperature and installation method. All numbers below are either calculated (formula shown) or quoted from NEC Table 310.16, IEC 60364-5-52 Table B.52.2, or BS 7671 Appendix 4.

1. The two formulas you need

Single-phase (230 V): I = P / (U × cosφ). Three-phase (400 V): I = P / (√3 × U × cosφ). Here P is watts, U is volts, cosφ is power factor (0.95 for heating, 0.8–0.87 for motors, 1.0 for pure resistive).

Worked check: 7 kW single-phase heater, cosφ = 1.0. I = 7000 / (230 × 1.0) = 30.4 A. Same 7 kW three-phase motor, cosφ = 0.85: I = 7000 / (1.732 × 400 × 0.85) = 7000 / 588.9 = 11.9 A.

2. Amps and kW to mm²: master table (copper)

Base current-carrying capacity Iz for copper, PVC insulation, reference method C (clipped direct / in free air per IEC 60364-5-52 Table B.52.2, two loaded conductors). For enclosed conduit use lower values — see section 5.

Current (A)1-ph kW @230V, cosφ=13-ph kW @400V, cosφ=0.85Copper mm² (method C)AWG equiv.
102.35.91.516
163.79.42.514
204.611.82.5–412
255.814.7412–10
327.418.8610
409.223.56–108
5011.529.4108–6
6314.537.1166
8018.447.1254
10023.058.925–353–2

How to read it: compute your current, go to the next row up, read mm². A 30.4 A heater needs the 32 A row → 6 mm² copper. The 11.9 A motor needs the 16 A row → 2.5 mm² copper.

3. Copper vs aluminium

Aluminium carries about 78% of copper at the same cross-section (IEC 60364-5-52). Rule of thumb: go one to two standard sizes up. A 32 A circuit that needs 6 mm² copper needs 10 mm² aluminium. A 63 A feeder: 16 mm² copper → 25 mm² aluminium.

Aluminium needs care: use Al-rated lugs, antioxidant paste, and correct torque. Do not mix bare copper and aluminium in one terminal. For home branch circuits, copper is the default choice in the US, UK, and India.

4. Temperature derating (K1)

Tables assume 30 °C ambient. Hotter air or grouped hot surfaces cut capacity. Per IEC 60364-5-52 Table B.52.14 (PVC): 35 °C → ×0.94, 40 °C → ×0.87, 45 °C → ×0.79, 50 °C → ×0.71.

Worked check: 2.5 mm² base Iz = 21 A (method C). In a 40 °C attic: 21 × 0.87 = 18.3 A. A 16 A breaker still fits (16 ≤ 18.3). At 50 °C: 21 × 0.71 = 14.9 A — a 16 A breaker no longer fits; step up to 4 mm².

5. Installation method derating (K2)

Conduit, trunking, and bunched cables trap heat. Reference: IEC 60364-5-52 Table B.52.17 and NEC 310.15(C)(1) adjustment factors. Few practical multipliers: 2–3 circuits together ×0.80–0.70, 4–6 together ×0.65–0.60, single conduit in insulated wall (method A1) roughly −25% vs open clipped.

Worked check: 4 mm² base 28 A, four circuits bunched (×0.65): 28 × 0.65 = 18.2 A. The same cable that feeds 25 A alone feeds only 18 A bunched. Fix: split groups across conduits or upsize.

6. Full worked example: 12 kW workshop feeder

Given: 12 kW three-phase, 400 V, cosφ = 0.85, run in conduit with two other circuits, ambient 35 °C. Step 1 — current: I = 12000 / (1.732 × 400 × 0.85) = 12000 / 588.9 = 20.4 A. Breaker next size up: 25 A. Step 2 — base section for 25 A: 4 mm² (Iz = 28 A). Step 3 — derate: K1 (35 °C) 0.94 × K2 (3 circuits) 0.70 = 0.658. 28 × 0.658 = 18.4 A — fails (18.4 < 25). Step 4 — try 6 mm² (Iz = 36 A): 36 × 0.658 = 23.7 A — still short. Step 5 — try 10 mm² (Iz = 50 A): 50 × 0.658 = 32.9 A ≥ 25 — passes. Answer: 10 mm² copper, 25 A breaker for these conditions, or reroute to cut grouping.

7. AWG to mm² quick map

US wire sizes with metric equivalents: 14 AWG = 2.08 mm², 12 AWG = 3.31, 10 AWG = 5.26, 8 AWG = 8.37, 6 AWG = 13.3, 4 AWG = 21.2, 3 AWG = 26.7, 2 AWG = 33.6, 1 AWG = 42.4, 1/0 = 53.5, 2/0 = 67.4, 3/0 = 85.0, 4/0 = 107.2 mm². NEC ampacity (75 °C copper column, Table 310.16): 14 AWG 20 A (limited to 15 A by 240.4(D)), 12 AWG 25 A (limited to 20 A), 10 AWG 35 A (limited to 30 A), 8 AWG 50 A, 6 AWG 65 A, 4 AWG 85 A.

8. The breaker rule: Ib ≤ In ≤ Iz

The breaker rating In must sit between load current Ib and cable capacity Iz (IEC 60364-4-43, NEC 240.4). Standard next step: In ≥ 1.25 × Ib for continuous loads (NEC 210.19(A)(1) — size conductors at 125% of continuous load). A 20.4 A continuous load needs conductors rated ≥ 25.5 A.

9. Common mistakes

  • Sizing by breaker instead of load. A 32 A breaker does not mean the load is 32 A — compute Ib first.
  • Ignoring grouping. Three conduits tied together is not three independent cables — apply K2.
  • Mixing methods. Open-air ratings in a hot insulated wall — apply both K1 and method correction.
  • Aluminium at copper size. Same mm² does not mean same amps — upsize Al by one to two steps.
  • Forgetting voltage drop. A cable that passes thermally can still fail on long runs — check distance separately.

10. Checklist before you buy cable

  • Load current computed with correct voltage and cosφ.
  • Continuous load × 1.25 applied where required.
  • Base section from IEC or NEC table for your method.
  • K1 temperature and K2 grouping applied.
  • Breaker satisfies Ib ≤ In ≤ Iz.
  • Voltage drop checked for the actual length.

11. Worked example 2: aluminium sub-feeder with derating

Given: 18 kW three-phase load, 400 V, cosφ = 0.87, aluminium cable in trunking with one other circuit, ambient 30 °C. Step 1 — current: I = 18000 / (1.732 × 400 × 0.87) = 18000 / 602.9 = 29.9 A. Continuous load rule (NEC 210.19(A)(1)): size at 125% → 29.9 × 1.25 = 37.4 A minimum conductor rating. Step 2 — base aluminium section: 16 mm² Al is rated about 62 A by IEC method C equivalents (roughly 78% of the 16 mm² copper 66 A from IEC 60364-5-52 Table B.52.2), so it covers 37.4 A with margin. Step 3 — grouping: two circuits together, K2 ≈ 0.80. Check: 62 × 0.80 = 49.6 A ≥ 37.4 A — passes. Breaker: needs In between 29.9 A load and 49.6 A derated capacity → standard 32 or 40 A; the conservative pick for a continuous 30 A load is 40 A with 16 mm² aluminium. If terminations are 60 °C rated, verify against the 60 °C column per NEC 110.14(C) before finalizing.

A copper alternative for the same job: 10 mm² copper (Iz = 50 A) derated 50 × 0.80 = 40 A ≥ 37.4 A — passes with a 32–40 A breaker. The 40 A aluminium feeder uses cheaper metal but a thicker cable and larger lugs; the 10 mm² copper feeder is slimmer and easier to terminate. Price both before deciding.

12. Power factor traps that change the answer

Two 10 kW loads can need different cables. A 10 kW heater at cosφ = 1.0, single-phase 230 V: I = 10000 / 230 = 43.5 A → 10 mm² copper. A 10 kW motor at cosφ = 0.80: I = 10000 / (230 × 0.80) = 54.3 A → 16 mm² copper. Same kilowatts, two sizes apart — because current, not power, heats the cable. Always write down cosφ: 1.0 heating and lighting with electronic drivers near 0.9–0.95, small motors 0.75–0.85, welders and discharge lighting lower. When the nameplate gives amps directly, trust the amps and skip the conversion.

Three-phase saves copper fast. The 12 kW workshop feeder from section 6 drew 20.4 A three-phase but would draw 52.2 A single-phase (12000 / 230) at unity power factor — the single-phase version needs 10–16 mm² where the three-phase version, before derating, needed only 4 mm². If a property has a three-phase supply, move every load above 5 kW onto three phases.

See also

Run the numbers on your own layout: open the free demo, draw the rooms, and check cable, breaker, and voltage drop together.

Try it on your own plan — open the free demo at https://gorkycad.com/cad/?demo=1, no registration needed.

Frequently asked questions

What size cable do I need for 32 amps?

Compute the load current first, then pick the next standard section up. For 32 A continuous on copper in open air, 6 mm² (Iz ≈ 36 A per IEC 60364-5-52 Table B.52.2, method C) is the typical answer; in conduit or hot rooms, derate and you often land on 10 mm².

How do I convert kW to cable size?

Convert kW to amps (1-phase: P/(U·cosφ); 3-phase: P/(√3·U·cosφ)), multiply continuous loads by 1.25, then read the section from the ampacity table for your installation method and apply temperature and grouping corrections.

What is 10 AWG in mm² and how many amps?

10 AWG is 5.26 mm². Per NEC Table 310.16 it is rated 35 A at 75 °C copper, but 240.4(D) limits overcurrent protection to 30 A for 10 AWG.

Can I use aluminium instead of copper?

Yes, upsized one to two standard sizes (aluminium carries about 78% of copper at equal section). Use Al-rated lugs, paste, and correct torque, and never mix bare copper and aluminium in one terminal.

Do I need to derate cables in conduit?

Yes. Heat trapped in conduit or bunched groups cuts capacity — apply IEC Table B.52.17 or NEC 310.15(C)(1) factors. Four grouped circuits typically keep only about 65% of the single-circuit rating.