A cable can pass the ampacity table and still fail the job. The reason is voltage drop: resistance over distance eats volts, dims lights, and stalls motors. This guide sizes cable by length, not just by amps.

You get the formula, a worked 2.5 mm² / 20 m / 16 A example, the 3% and 5% limits (NEC 210.19(A) FPN, IEC 60364-5-52 Annex G / BS 7671 Appendix 4), and a rule for when to step up a size.

1. The formula (single-phase and three-phase)

Single-phase: ΔU = 2 × I × L × ρ / S, percentage ΔU% = ΔU / U × 100. Three-phase (balanced, ignoring reactance for small cables): ΔU = √3 × I × L × (ρ/S) × cosφ approx, or with reactance for large feeders per IEC 60364-5-52. I = amps, L = one-way metres, ρ = 0.0175 Ω·mm²/m copper at 20 °C (0.0282 aluminium), S = mm².

2. Worked example: 2.5 mm², 20 m, 16 A

Given: copper, 230 V, cosφ = 1.0, L = 20 m one-way (40 m loop), S = 2.5 mm². Loop resistance: R = ρ × 2L / S = 0.0175 × 40 / 2.5 = 0.28 Ω. Drop: ΔU = 16 × 0.28 = 4.48 V. Percentage: 4.48 / 230 × 100 = 1.95%. Verdict: passes the 3% lighting limit and the 5% general limit.

Same run at cosφ = 0.92 (mixed load): effective drop ≈ 1.95 × 0.92 ≈ 1.79% resistive share — still passes. At 70 °C operating temperature (ρ ≈ 0.0209): R = 0.334 Ω, ΔU = 5.35 V = 2.33% — still inside 3%.

3. The limits: 3% and 5%

NEC 210.19(A) informational note: 3% on branch circuits, 5% total feeder + branch for reasonable efficiency. IEC 60364-5-52 Annex G and BS 7671 Appendix 4 (Table 4Ab): lighting 3%, other uses 5% from the origin of the installation. These are design values, not trip thresholds — exceeding them wastes energy and shortens equipment life.

4. Distance table: how far can 230 V go?

Max one-way length for 3% drop (6.9 V at 230 V), copper, cosφ = 1. Computed as L = ΔU × S / (2 × I × ρ), ρ = 0.0175.

Cable10 A16 A25 A32 A
1.5 mm²29.6 m18.5 m11.8 m9.2 m
2.5 mm²49.3 m30.8 m19.7 m15.4 m
4 mm²78.9 m49.3 m31.5 m24.6 m
6 mm²118 m73.9 m47.3 m37.0 m
10 mm²197 m123 m78.9 m61.6 m

Read it: a 16 A socket circuit on 2.5 mm² stays inside 3% only to ~31 m. Past that, upsize or split the run.

5. Worked example 2: long garden feed

Given: 3.5 kW load (15.2 A at 230 V), 45 m run. On 2.5 mm²: ΔU = 2 × 15.2 × 45 × 0.0175 / 2.5 = 9.56 V = 4.16%. Passes 5% but fails 3% — fine for sockets, not for lighting. On 4 mm²: 9.56 × 2.5/4 = 5.97 V = 2.60% — passes both. Answer: 4 mm² if the run feeds lights.

6. Three-phase example

Given: 15 kW, 400 V, cosφ = 0.85, 40 m, 4 mm² copper. Current: I = 15000 / (1.732 × 400 × 0.85) = 25.5 A. Drop (resistive approx): ΔU = 1.732 × 25.5 × 40 × 0.0175/4 × 0.85 = 1.732 × 25.5 × 40 × 0.004375 × 0.85 = 6.57 V line-to-line ≈ 1.64% of 400 V. Passes. At 80 m it doubles to ~3.3% — still inside 5% for power, marginal for lighting sub-circuits.

Second distance check with power factor below unity: 4 kW motor load, 230 V, cosφ = 0.80, 35 m run on 4 mm² copper. Current: I = 4000 / (230 × 0.80) = 21.7 A. Loop resistance: R = 0.0175 × 70 / 4 = 0.306 Ω. Resistive drop: 21.7 × 0.306 = 6.65 V; with cosφ the in-phase component ≈ 6.65 × 0.80 = 5.32 V = 2.31% (reactance adds a small quadrature term on small cables — under 0.2% here per IEC 60364-5-52 guidance, safely ignored for 4 mm²). Verdict: passes 3%. The same run at 50 m: drop scales linearly to 5.32 × 50/35 = 7.60 V = 3.30% — fails lighting, passes sockets. Two metres of trench decide the section: measure the route, not the straight line on the plan, and add 10% spare length for terminations and vertical drops before computing.

Temperature note with numbers: the examples above use ρ = 0.0175 at 20 °C. A loaded PVC cable runs near 70 °C, where ρ ≈ 0.0209 — resistance 19% higher. The section-2 example at operating temperature gave 2.33% instead of 1.95%. For borderline runs (2.7–3.0% cold), recompute hot: multiply the cold percentage by 1.19. If the hot number crosses 3% on a lighting circuit, upsize now — the cable will live hot, not cold.

7. When to step up a size

Step up when: drop exceeds 3% on lighting or 5% overall; the run is aluminium (ρ = 0.0282, ~61% more drop); ambient heat pushes ρ up (~0.4% per °C for copper); or the load may grow (EV charger, heat pump). One size up roughly halves the problem only if you double the section — otherwise scale by S ratio.

Quick rule for the site cabin wall chart: on 230 V copper, one amp over one metre costs about 0.0152% per mm² of section — that is (2 × 0.0175 / 230 × 100) / S. So a 16 A load on 25 m of 2.5 mm² gives 16 × 25 × 0.0152 / 2.5 = 2.43% cold (≈2.9% hot), matching the detailed 1.95–2.33% band from section 2 within rounding and spare-length allowance. Use it for estimates on site; use the full formula with temperature correction for the final purchase order and test sheet.

8. Common mistakes

  • Sizing by amps only. 2.5 mm²/16 A is fine at 10 m and fails at 45 m.
  • Using one-way length as loop length. The factor 2 is the most dropped number in DIY math.
  • Forgetting temperature. Hot cable has higher ρ — add ~19% resistance at 70 °C vs 20 °C.
  • Aluminium at copper math. Same amps, same length needs ~1.6× the section for equal drop.
  • Checking only the branch. Feeder + branch add up — the 5% cap is total.

9. Checklist

  • Length measured one-way, factor 2 applied.
  • Correct ρ (copper 0.0175 / aluminium 0.0282 at 20 °C).
  • 3% checked for lighting, 5% for the whole path.
  • Feeder and branch drops summed.
  • Upsize decision recorded with the new percentage.

10. Worked example 3: aluminium run to an outbuilding

Given: 5 kW load, 230 V, cosφ = 1.0, 60 m run, aluminium cable. Current: I = 5000 / 230 = 21.7 A. Try 10 mm² Al (ρ = 0.0282): R = 0.0282 × 120 / 10 = 0.338 Ω. Drop: 21.7 × 0.338 = 7.34 V = 3.19% — fails 3%, passes 5%. Try 16 mm² Al: R = 0.0282 × 120 / 16 = 0.2115 Ω, ΔU = 4.59 V = 2.00% — passes both. Copper equivalent for comparison: 10 mm² Cu gives R = 0.21 Ω and 1.98%. Lesson: aluminium needs roughly 1.6× the copper section for equal drop — here 16 mm² Al matches 10 mm² Cu almost exactly (2.00% vs 1.98%).

11. Measuring drop on site (confirm the math)

Calculate first, then verify with a meter. With the load running, measure voltage at the panel (U1) and at the farthest outlet (U2); drop = U1 − U2, percentage = drop / U1 × 100. A reading of 231 V at the panel and 224 V at the garage outlet means 7 V, or 3.0% — right at the lighting limit. Measure under real load: a no-load reading hides the drop because current is near zero. If the meter shows more than the calculation, look for loose terminations (heat marks, buzzing) before blaming the cable — resistance at a bad joint adds volts no table predicts. Record U1, U2, load amps, ambient temperature, and full cable data on the test sheet; it is the cheapest commissioning record you will ever make.

12. Feeder plus branch: the total that actually matters

The 5% cap is end-to-end. A feeder dropping 2.5% plus a branch dropping 2.5% totals 5.0% — exactly at the limit, with zero margin for temperature or load growth. Worked stack: house feeder 25 m of 10 mm² at 40 A single-phase: ΔU = 2 × 40 × 25 × 0.0175 / 10 = 3.5 V = 1.52%. Branch 20 m of 2.5 mm² at 16 A: 4.48 V = 1.95% (section 2). Total: 1.52 + 1.95 = 3.47% — inside 5% but outside 3%, so lighting on that branch is marginal. Fix options: upsize the branch to 4 mm² (drop 2.80 V = 1.22%, total 2.74% — passes 3%), shorten the branch with a sub-panel, or accept 5%-only loads (sockets, heating) on that run. Always sum feeder and branch drops before buying cable, and keep the written calculation with the panel schedule.

See also

Size it by distance on your own floor plan: open the free demo and check voltage drop per circuit automatically.

Try it on your own plan — open the free demo at https://gorkycad.com/cad/?demo=1, no registration needed.

Frequently asked questions

What is the voltage drop for 2.5 mm² cable at 20 m with 16 A?

Loop resistance is 0.28 Ω (ρ = 0.0175, 40 m loop, 2.5 mm²), so ΔU = 16 × 0.28 = 4.48 V, which is 1.95% of 230 V — inside both the 3% lighting and 5% general limits.

What are the 3% and 5% voltage drop limits?

Design guidance from NEC 210.19(A) informational note and IEC 60364-5-52/BS 7671: max 3% on lighting circuits and 5% total (feeder + branch) from the origin. They protect efficiency and equipment life, not just safety.

How far can I run 2.5 mm² at 16 A on 230 V?

About 31 m one-way for 3% drop (6.9 V budget). Past that distance, step up to 4 mm² (≈49 m) or split the circuit.

Does three-phase drop use the same formula?

No — use ΔU ≈ √3 × I × L × (ρ/S) × cosφ for balanced three-phase (plus reactance for large feeders per IEC 60364-5-52). A 15 kW/400 V/40 m run on 4 mm² drops about 1.6%.

When should I go one size up?

When drop exceeds 3% on lights or 5% total, when the run is aluminium, when cable runs hot, or when the load may grow. Recompute the percentage after upsizing — do not assume.