Automatic disconnection sounds abstract until you translate it: when a live conductor touches an exposed metal part, the fault current must be large enough to trip the breaker within 0.4 seconds on a final circuit. Earth loop impedance, Zs, is the number that decides whether that happens. Too high, and the breaker sees a modest overload and waits while the metalwork sits at dangerous voltage.
This guide shows how to measure Zs, the maximum values for common breakers, the calculation behind them, and the honest fixes when a reading fails. It follows IEC 60364-4-41 for disconnection times and IEC 60364-6 for verification.
1. What Zs actually is
Zs is the total impedance of the fault loop: source winding plus line conductor out plus protective earth conductor back. At low voltage it is mostly resistance of copper and connections. Measure it in ohms at the farthest point of the circuit with the supply on, using a loop tester that applies a small test load and derives impedance from the voltage drop. The reading includes everything, which is exactly why it is trusted: joints, length, and cross section all appear in one number.
External loop Ze is measured at the origin with the installation earth disconnected. Zs at any point equals Ze plus the resistance of the circuit conductors R1 plus R2. If you know Ze is 0.35 ohm and the circuit adds 0.6 ohm, Zs should read about 0.95 ohm. A much higher reading points to a bad joint, not to theory.
2. Why 0.4 seconds decides everything
IEC 60364-4-41 requires final circuits up to 32 A in TN systems to disconnect within 0.4 seconds, because longer exposure at fault voltage risks ventricular fibrillation. Distribution circuits get 5 seconds. The breaker meets 0.4 s only if fault current reaches its instantaneous region. Fault current is simply line voltage divided by Zs. Lower Zs means higher current means faster trip. Every Zs limit in the tables below is this physics rearranged.
For a 230 V circuit the minimum current that guarantees magnetic tripping is the breaker instantaneous threshold. Divide 230 V by that current and you get the maximum Zs. Add the standard 0.8 correction for cold measurement versus hot fault conditions, which is why tabulated values look stricter than raw division.
3. Worked calculation for a B16 breaker
Breaker B16: magnetic range 3 to 5 times rated, so worst case threshold is 5 times 16 equals 80 A. Raw limit is 230 divided by 80 equals 2.875 ohm. Apply the 0.8 temperature and safety factor: 2.875 times 0.8 equals 2.30 ohm. That is the tabulated maximum Zs for B16. Measured 1.8 ohm passes with margin. Measured 2.6 ohm fails even though a multimeter shows continuity.
Same method for C16: threshold 10 times 16 equals 160 A, 230 divided by 160 equals 1.4375, times 0.8 equals 1.15 ohm. For D16: 20 times 16 equals 320 A, 230 divided by 320 equals 0.719, times 0.8 equals 0.57 ohm. Each step from B to C to D roughly halves the allowed impedance, which is the price of tolerating inrush.
4. Maximum Zs table for common breakers
| Breaker | Magnetic threshold | Max Zs at 230 V |
|---|---|---|
| B10 | 50 A | 3.68 ohm |
| B16 | 80 A | 2.30 ohm |
| B20 | 100 A | 1.84 ohm |
| B32 | 160 A | 1.15 ohm |
| C10 | 100 A | 1.84 ohm |
| C16 | 160 A | 1.15 ohm |
| C20 | 200 A | 0.92 ohm |
| C32 | 320 A | 0.57 ohm |
| D16 | 320 A | 0.57 ohm |
| D20 | 400 A | 0.46 ohm |
| D32 | 640 A | 0.29 ohm |
Values include the 0.8 factor and assume 230 V phase to earth. For 220 V supplies multiply by 220 divided by 230. Fuse protected circuits use the current for 0.4 s from the fuse curve instead of a magnetic multiple.
5. How to measure without fooling yourself
Measure at the farthest outlet with all bonding in place and loads disconnected, because connected loads parallel the test and flatter the reading. Use the high current test where the instrument offers it, unless an upstream 30 mA RCD would trip, in which case use the no trip low current mode and accept its wider tolerance. Take three readings and keep the highest. Record Ze separately at the origin so you can split external versus internal contributions when a reading fails.
Never measure with temporary jumpers or with the earth bar disconnected to make the number look better. The reading must represent the installation as the fault sees it.
6. Worked field example
Kitchen ring converted to two 20 A radials, cable 2.5 sq mm copper, run 28 m each way. Measured Zs at the farthest socket: 1.42 ohm. Breaker is C20 with a 0.92 ohm limit. Result: fail by 0.5 ohm. Ze at origin is 0.35 ohm, so the circuit contributes 1.07 ohm against an expected 0.42 ohm for 56 m of 2.5 sq mm at operating temperature. The excess points to a series joint, found as a twisted spur connection buried behind plaster. Remade as a maintenance free joint, Zs falls to 0.81 ohm. Pass with margin, and the fault current rises from 162 A to 284 A, comfortably into the magnetic region.
7. What to do when Zs fails
| Option | When it fits | Watch out |
|---|---|---|
| Find and remake the bad joint | Reading far above calculated R1 plus R2 | Do not just tighten live terminals |
| Shorten or enlarge the cable | Long runs on C or D curves | Recheck voltage drop and thermal limits |
| Drop one curve step B to C to B | Inrush allows it | Recheck inrush and selectivity |
| Add 30 mA RCD protection | Where disconnection cannot be met by overcurrent | RCD is supplementary, fix the loop too |
| Split into two shorter circuits | Overlong radials | Board space and cost |
An RCD with 30 mA rating permits much higher Zs for shock protection, but it does not repair a broken protective conductor. Use it as the compliant backstop while still fixing the underlying impedance.
8. Link to RCDs and bonding
Where overcurrent disconnection cannot be achieved, IEC 60364 allows an RCD as additional protection, with the product of loop impedance and rated residual current kept within safe voltage, 50 V in ordinary locations. A 30 mA device thus covers Zs up to about 1667 ohm for shock purposes. Main bonding of water, gas, and structural metal keeps exposed parts at similar potential during the fault, buying the milliseconds the breaker needs.
Record which circuits rely on RCDs for disconnection versus overcurrent alone. The next electrician must know that swapping the RCD for a plain switch would remove the only compliant path.
9. Assumptions and when this does not apply
This guide assumes TN systems at 220 to 240 V phase to earth, breakers to IEC 60898 with B, C, D curves, and TN disconnection times of 0.4 s for final circuits. It does not cover TT systems where the earth electrode dominates and RCDs do the work, IT systems with first fault monitoring, or circuits protected only by fuses, which need fuse curve currents for 0.4 s. Temperature factor 0.8 is the conventional allowance; measured hot values need no correction.
10. Mini case: the long garage feed
A 45 m garage feed in 2.5 sq mm on a C16 breaker read 1.68 ohm against a 1.15 limit. Voltage drop was also 4.1 percent, near its own limit. The fix upsized the run to 4 sq mm, which cut loop resistance by 37 percent and drop to 2.6 percent. New Zs 1.02 ohm, pass. One cable change fixed two compliance failures at once, which is typical: impedance and drop share the same copper.
11. Record sheet that proves compliance
For each circuit record breaker type and rating, tabulated maximum Zs, measured Zs at the farthest point, Ze, instrument number and calibration date, and a pass or fail verdict with the action taken. Numbers beat ticks. A sheet showing B16 limit 2.30 against measured 1.8 tells the story in one line; a tick column tells nothing.
12. TT systems in one paragraph
In TT systems the earth path runs through the soil electrode rather than a distributor earth, so loop values are tens of ohms instead of fractions, and overcurrent devices cannot meet 0.4 s on their own. Protection then rests on RCDs: the product of earth electrode resistance and rated residual current must stay within 50 V, so a 100 ohm electrode with a 30 mA device gives 3 V and passes easily. Measure the electrode with an earth tester using the three point method, record it separately from Zs, and never mix TT earth readings into TN loop tables. Where a site mixes systems, label each board clearly so nobody applies the wrong limit.
Calibrate on schedule and log the instrument number with every reading. A loop tester a year overdue turns every pass into an argument, while a current certificate ends the discussion before it starts.
Photograph each test position and staple the image to the sheet so next year comparison is straightforward.
File the sheet promptly.
Try it on your own plan: open the free demo at https://gorkycad.com/cad/?demo=1&lang=en — draw rooms, place the board, run checks and export a PDF parts list.
Frequently asked questions
Can I use the raw 230 V divided by threshold without 0.8?
For design discussion yes, for compliance no. Tabulated limits include the 0.8 factor for temperature rise and measurement tolerance. A raw pass can still be a tabulated fail.
Does an RCD fix a high Zs?
For shock protection yes within its own rule, but it does not repair the loop. Fix bad joints and sizing first, then rely on the RCD as the compliant backstop where overcurrent alone cannot meet 0.4 s.
Where exactly do I measure Zs?
At the farthest point of each circuit with bonding in place and loads disconnected. Board readings hide circuit faults.
What if Ze alone already exceeds the limit?
Then no circuit on that supply can pass by overcurrent. Escalate to the distributor: the external loop is their responsibility.
Do fuses use the same table?
No. Fuses need the current that melts them within 0.4 s from the fuse curve, not a magnetic multiple. Use manufacturer data for the specific fuse.