Buy too small and the generator stalls every time the well pump kicks in. Buy too big and you burn extra fuel for a decade to power a machine running at quarter load. The right size comes from one honest list: every load, its running watts, and its starting surge.

This guide shows the math for fridges, air conditioners and well pumps — the three loads that decide generator size — then works three scenarios (5, 8 and 12 kW) so you can see which one fits a real house. References: NEC Article 702 (optional standby) and manufacturer locked-rotor data.

1. The two numbers every appliance has

Running watts is what the label shows. Starting watts is the 1–3 second surge when a motor starts — typically 3 to 7 times running for compressors and pumps. A fridge that runs at 150 W can demand 1,200 W to start. Size for running watts only and the first compressor start collapses the voltage.

Rule: generator surge rating must cover the largest single start plus everything already running. Generator continuous rating must cover all running watts that can coincide. Both conditions, not one.

2. Appliance table: running vs starting watts

Typical values for sizing (check your nameplates — well pumps vary most). Starting multiple from locked-rotor current per NEMA code letters.

ApplianceRunning WStart multipleStarting W
Fridge / freezer150–2006–8x1,000–1,400
Window AC 12k BTU1,2004–5x5,000–6,000
Central AC 3-ton3,5004–6x14,000–20,000
Well pump 1 HP7503–5x2,250–3,750
Well pump 1.5 HP1,1003–5x3,300–5,500
Sump pump 1/3 HP8003x2,400
Gas furnace blower8003x2,400
LED lighting + router + chargers3001x300

3. How to do the math in 4 steps

Step 1: list everything you want on backup with running watts. Step 2: mark motor loads with starting watts. Step 3: add all running watts that run together. Step 4: add the single largest starting surge on top (not all surges — motors rarely start in the same second, but assume the worst one starts last).

Example: fridge 200 + freezer 200 + lights 300 + furnace blower 800 + well pump 750 = 2,250 W running. Largest start: pump 3,000 W (4x). Required: surge 2,250 + 3,000 = 5,250 W, continuous 2,250 W. A 5–6 kW portable covers it with margin.

4. Scenario A: 5 kW portable (essentials only)

Loads: fridge, freezer, sump pump, furnace blower, LED lights, router, phone chargers. Running total about 2,300 W; worst single start about 2,400 W (sump or blower). A 5 kW continuous / 6.25 kW surge unit handles it at roughly 40% load — efficient and quiet.

Fits: town houses, gas heat, city water (no well pump), one small window AC at a time. Does not fit: central AC, electric range, electric water heater, 1.5 HP well pump plus anything else starting.

5. Scenario B: 8 kW (well pump house)

Add a 1 HP well pump (750 running, 3,000 starting) and a window AC (1,200 running, 5,000 starting) to Scenario A. Running: 2,300 + 750 + 1,200 = 4,250 W. Worst case — AC starts while the pump runs: 4,250 + 5,000 = 9,250 W surge. An 8 kW continuous / 10 kW surge unit just covers it; stagger starts (let the pump finish before the AC kicks) and it runs comfortably.

This is the most common rural size: water, septic controls, fridge and one cooling zone. Fuel at half load: about 0.9–1.2 gal/h gasoline, roughly 8–10 hours on a 8-gallon tank.

6. Scenario C: 12 kW (AC + pump + comfort)

Add a second fridge zone or a 2-ton mini-split (2,400 running, 8,000 starting). Running climbs to 5,500–6,500 W; worst surge to 12,000–14,000 W. A 12 kW continuous / 15 kW surge standby unit covers it and can take a 3-ton central AC with a soft starter.

Above this — electric ranges (8–12 kW), electric dryers (5 kW), tank water heaters (4.5 kW) — you are choosing between a 20 kW+ standby unit or managing loads (never run the dryer on generator). Most families choose management and stay at 8–12 kW.

7. ATS and grounding: the two code items people skip

Transfer: NEC 702.6 requires a transfer switch or interlocked breaker so the generator can never backfeed the grid — backfeed kills lineworkers. Automatic (ATS) for standby units, manual interlock kit for portables; both must switch the neutral correctly for the system type (NEC 702.7, separately vs non-separately derived).

Grounding: portable under 5 kW feeding cord-connected tools needs no ground rod (frame ground suffices, NEC 250.34). Once wired to the house through a transfer switch, the house grounding electrode system applies and the generator bonds to it — drive no separate rod that creates a second ground path unless the design calls for it (NEC Article 250).

8. Mini case: farmhouse, 1 HP pump, window AC

Given: pump 750/3,000 W, AC 1,200/5,000 W, fridge 200/1,200 W, lights and controls 500/500 W. Running together: 750 + 1,200 + 200 + 500 = 2,650 W. Worst surge (AC starts with all running): 2,650 + 5,000 = 7,650 W. Verdict: 5 kW unit fails (surge 6.25 kW max), 8 kW unit passes with 2.35 kW surge margin. The owner bought 8 kW, added a $15 pump delay relay so pump and AC never start together, and runtime at 40% load is 11 hours per tank.

9. Mistakes that cost money or stall the unit

  • Sizing from the breaker panel total (e.g. 200 A service = 48 kW) instead of actual coincident loads.
  • Forgetting the well pump — the single most common undersize cause in rural quotes.
  • Starting everything at once after an outage — stagger motor starts by 30 seconds each.
  • Running a 20 kW unit at 2 kW for years — wet-stacking on diesel, carbon fouling on gas.
  • No transfer switch (suicide cords) — illegal under NEC 702.6 and lethal to lineworkers.

10. Assumptions and when this does not apply

  • Assumes 120/240 V split-phase at 60 Hz (US-style); for 230 V 50 Hz regions divide power by local voltage the same way.
  • Start multiples are typical NEMA ranges — deep wells, old compressors and low voltage raise them; use nameplate LRA when available (starting VA = LRA x volts).
  • Does not cover fire pumps, elevators or medical life-support — separate NEC articles and engineering apply.
  • Fuel and altitude derate (about 3.5% per 1,000 ft above 500 ft) not included — high sites need the next size up.
  • Noise and placement rules (NEC 702.12, local setbacks) can force a standby location that changes cable and ATS cost.

11. Fuel, runtime and ATS sizing

Size is only half the purchase decision; fuel type and runtime decide whether the unit is usable. Gasoline portables are cheapest to buy but thirstiest: a 5 kW unit burns roughly 0.6 gallons per hour at half load, an 8 kW unit about 1.0, a 12 kW standby on natural gas about 1.5 therms per hour. Diesel costs more upfront but runs longest between refuels and stores safely for years, while propane never goes stale in the tank.

GeneratorFuelHalf-load burn8-hour outage cost
5 kW portableGasoline0.6 gal/h4.8 gal (one tank)
8 kW portableGasoline / dual-fuel1.0 gal/h8 gal (one refill)
12 kW standbyNatural gas / LPG1.5 therm/hautomatic, no refuel

Size the ATS with the generator, not the house: a 60 A ATS suits 12 kW at 240 V (12000 / 240 = 50 A, next standard size up). Whole-house ATS on a 200 A service with an 8 kW generator is a design error — use a critical-loads subpanel with 8 to 12 circuits instead, so the generator can never see the range and dryer together.

12. Checklist before you buy

  • List every load with running watts from nameplates, not guesses.
  • Mark motor loads and write starting watts from LRA or the 3–6x rule.
  • Add running watts that coincide, then add the single largest start on top.
  • Confirm surge rating covers that sum and continuous rating covers running total.
  • Confirm transfer method (interlock or ATS), cable length, fuel storage and noise setback before paying.

A dealer who sizes from your list in writing is worth more than a bigger unit from one who sizes from the panel total. Keep the list with the manual — it is also what the inspector wants to see.

See also: Home load calculation · Breaker size from load · Voltage drop by distance

Try it free in your browser — open the demo: https://gorkycad.com/cad/?demo=1

Frequently asked questions

What size generator runs a house with a well pump?

Usually 8 kW continuous. A 1 HP pump needs 3,000 W to start on top of 2-4 kW of house loads, so 5 kW units stall and 8 kW covers it with margin.

Can a 5 kW generator run central AC?

No. A 3-ton central AC alone surges 14-20 kW on start. 5 kW covers fridges, pumps and lights, not central air.

How do I calculate starting watts?

Use locked-rotor amps from the nameplate: starting VA = LRA x volts. Without LRA, multiply running watts by 3-5 for pumps and 4-6 for AC compressors.

Do I need a transfer switch for a portable generator?

Yes. NEC 702.6 requires it so the generator can never backfeed the grid. Interlock kits are the minimum; ATS for standby units.

Does a portable generator need a ground rod?

Cord-connected tools under 5 kW: no, frame ground suffices per NEC 250.34. Wired to the house: bond to the house electrode system.

Related reading