Electricians crossing between American and international jobs meet the same shock twice: the numbers look familiar but the rules differ. Wire sizes in AWG versus square millimetres, voltages 120/240 versus 230/400, GFCI versus RCD, conduit fill versus grouping factors. This one-page comparison puts the two systems side by side so you can read either drawing and know where the philosophies diverge.

IEC here means the IEC 60364 family with BS 7671 as its best-known national implementation. NEC means NFPA 70 as enforced in the United States. Neither is better in general; each optimises for its own grid history and enforcement culture.

1. Voltages and frequencies at a glance

North America uses split-phase 120/240 V at 60 Hz for homes: two 120 V legs with a neutral, large 240 V loads across both legs. The IEC world uses 230 V single-phase and 400 V three-phase at 50 Hz per IEC 60038. The practical consequence is current: the same 3 kW load draws about 13 A at 230 V but 25 A at 120 V, so American branch circuits run fatter wires for the same power.

Worked comparison. A 9 kW cooker at 230 V single-phase draws 39 A, needing 10 sq mm on a 40 A breaker. At 240 V split-phase in the US the same 9 kW draws 37.5 A across the two legs, typically served by 8 AWG copper on a 40 A two-pole breaker per NEC 310.16. Similar answer, different wire language.

ItemNEC, USIEC, international
Home voltage120/240 V split-phase, 60 Hz230 V / 400 V, 50 Hz
Common socket circuit15 or 20 A, 14 or 12 AWG16 or 20 A, 2.5 sq mm
Cooker circuit40 to 50 A, 8 to 6 AWG32 to 40 A, 6 to 10 sq mm
Reference standardNFPA 70, NEC Article 210, 250, 310IEC 60364 series, BS 7671

2. Wire sizes: AWG against square millimetres

American Wire Gauge runs backwards: bigger number means thinner wire. Fourteen AWG is about 2.08 sq mm, twelve AWG about 3.31, ten AWG about 5.26, eight AWG about 8.37. IEC sizes are direct areas: 1.5, 2.5, 4, 6, 10 sq mm. Memorise three pairs and you can read either schedule: 14 AWG is near 2 sq mm, 12 AWG is near 3.3 sq mm which behaves like 2.5 sq mm class, and 10 AWG is near 5.3 sq mm which behaves like 4 to 6 sq mm class.

Ampacity tables differ in structure but agree roughly on copper in conduit: 12 AWG at 20 A and 2.5 sq mm at 20 to 24 A depending on method, 10 AWG at 30 A and 4 sq mm at 28 to 32 A. Always use the installation method column, not the headline number: grouping and ambient temperature derate both systems.

3. Colour codes that prevent disasters

Colours are where cross-trained electricians make dangerous mistakes. US: black and red are hot, white is neutral, green or bare is ground. IEC: brown and black and grey are line conductors, blue is neutral, green-yellow is protective earth. The killer swap is white versus blue and green versus green-yellow: an American seeing blue may treat it as a hot, and a European seeing white may treat it as neutral when it is a hot leg in a US cable.

Rule for mixed crews: never trust colour memory across systems. Verify with a tester and label both ends whenever you touch a foreign installation. Photograph the existing connections before disconnecting anything, because the original installer may already have improvised across standards.

4. Protection philosophy: what each system obsesses over

NEC obsesses over arc and ground faults at the outlet: AFCI protection for bedrooms and living areas per NEC 210.12, GFCI at 5 mA for wet and outdoor locations per NEC 210.8. IEC obsesses over disconnection times and RCD coverage: 30 mA RCD on socket circuits and a maximum 0.4 s disconnection on final circuits up to 32 A per IEC 60364-4-41.

The result is visible in panels. An American board bristles with GFCI and AFCI breakers at 5 mA and arc detection. A European board carries 30 mA RCDs or RCBOs across groups with selectivity staging upstream. Both achieve safety; they chase different fault statistics shaped by different wiring traditions.

ProtectionNEC approachIEC approach
Socket shock protectionGFCI 5 mA, listed locations 210.8RCD 30 mA on socket circuits
Arc faultsAFCI required, 210.12Arc-fault devices recommended, not general
Disconnection timeVia breaker curves and OCPD rulesExplicit 0.4 s up to 32 A, 5 s above
SelectivityBreaker coordination practiceRCD type S staging plus MCB grading

5. Conduit fill versus grouping: two answers to heat

Both systems fight the same physics of hot wires in a pipe, but they count differently. NEC Chapter 9 limits conduit fill to 40 percent for three or more conductors and derates ampacity by conductor count per 310.15. IEC applies grouping factors from 60364-5-52 Table B.52.3: four circuits together keep 65 percent of solo ampacity, nine circuits keep 50 percent.

Worked example. Nine current-carrying 2.5 sq mm conductors in one conduit: NEC derates to 50 percent, so a 20 A base becomes 10 A and the circuit must be redesigned or split. IEC grouping for the equivalent bunched installation lands in the same area, roughly half. Different tables, same verdict: spread the circuits or upsize the wire.

6. Grounding versus bonding language

Terminology is the trap. In NEC language, grounding connects to earth and bonding connects metal parts together; both words are used precisely across Article 250. In IEC language, earthing is the connection to earth and protective bonding connects exposed and extraneous parts, with the protective conductor doing the work. An American ground rod and a European earth electrode are the same object with different paperwork.

System types differ more. The US uses solidly grounded neutrals almost everywhere. The IEC world names them: TN-S with separate neutral and earth throughout, TN-C-S with combined then split, TT with independent local earth, IT with isolated or impedance-grounded neutral. Read the system letter before judging any grounding detail.

7. Mini-case: one duplex, two code books

A contractor wired identical duplex units for a client with one foot in Texas and one in Dubai. The Texas unit used 12 AWG home runs on 20 A breakers with GFCI receptacles in kitchens and baths per NEC 210.8, AFCI breakers for bedrooms per 210.12, and a 200 A split-phase service. The Dubai unit used 2.5 sq mm radials on 20 A MCBs with 30 mA RCBO protection, 4 sq mm for the cooker on 32 A, and a 400/230 V three-phase service with TN-S earthing. Copper weight came out within ten percent; the panel schedules looked nothing alike, and the inspection checklists differed completely. The lesson the crew kept: translate the function first, then pick the local device, never translate device for device.

8. What this means for your project

If you bid from a foreign drawing, convert three things before pricing: wire sizes through the AWG to sq mm pairs, breaker philosophy through the protection table above, and earthing notes through the system letter. A drawing that says 100 A main means different service equipment in each world. A note that says RCD protected means different shopping lists: GFCI receptacles and breakers in one world, DIN-rail RCDs and RCBOs in the other.

For design work, follow the code of the installation country, not your home code. AHJ approval in the US follows the locally adopted NEC edition; European-style RCBO schedules need an engineer willing to sign them against local amendments. Check the edition year too: NEC 2020 versus 2023 differ on GFCI and surge requirements, and BS 7671 amendments move RCD rules.

9. Assumptions and limits of this page

This page compares mainstream residential and light commercial practice in 2026: NEC as adopted in most US states, IEC 60364 with BS 7671 flavour internationally. It does not cover utility medium voltage, hazardous locations, healthcare, marinas, or solar rapid-shutdown rules, where each code has specialist chapters. Prices are not compared because devices are not interchangeable across systems. Wire data here are copper at 30 C in conduit; aluminium, high ambient temperature, and long buried runs need the full tables. When in doubt, the local code book and the local inspector outrank any one-page summary.

10. Practical takeaways to keep

Keep four habits. One: convert function, not devices, when reading foreign drawings. Two: check disconnection philosophy explicitly, 0.4 s in IEC jobs and GFCI plus AFCI placement in NEC jobs. Three: derate grouped conductors under either table before complaining about wire size. Four: verify colours with a tester on any cross-system job. The electrician who respects both books gets hired for the interesting work: expat villas, franchise rollouts, and equipment imports that need a translator between two safety cultures.

Practice reading both drawing styles on one plan: open the free demo at https://gorkycad.com/cad/?demo=1, no signup needed, and compare the generated panel schedule with the protection tables above.

Compare both protection styles on one plan: free demo at https://gorkycad.com/cad/?demo=1, no signup needed.

Frequently asked questions

Is 12 AWG the same as 2.5 sq mm?

Close but not identical. Twelve AWG is 3.31 sq mm of copper, so it behaves like the 2.5 sq mm class: typically 20 A in conduit. Always check the installation-method column of NEC 310.16 or IEC 60364-5-52 rather than swapping by area alone.

Which is safer, GFCI or RCD?

Both protect against shock; they trip at different levels for different histories. US GFCI trips at 5 mA in listed locations per NEC 210.8, IEC sockets use 30 mA RCDs with disconnection-time rules. Follow the code of the installation country.

Do I need AFCI outside the US?

Generally no. AFCI per NEC 210.12 is a US requirement for bedrooms and living areas. IEC practice relies on 30 mA RCDs, good workmanship, and disconnection times, with arc-fault devices only in special cases.

Why do wire colours differ?

Historical development. US black-red-white-green versus IEC brown-black-grey-blue-green-yellow. On mixed crews never trust colour memory: test and label both ends, because white and blue swap roles across systems.

Can I design to IEC for a US installation?

No. The locally adopted NEC edition governs, and the inspector enforces it. Use this page to understand foreign drawings, then design and buy to the installation country code.