NEC Table 310.16 looks simple: rows of wire sizes, columns of amps. The confusion starts when the breaker is smaller than the wire rating, or when three temperature columns disagree. This article reads the table the way inspectors do.

Scope: copper and aluminium conductors, 0–2000 V, three temperature columns (60 °C, 75 °C, 90 °C). References are NEC Article 310 (2023/2026), Table 310.16, 110.14(C) termination limits, and 240.4(D) small-conductor limits.

1. What the table actually lists

Each row gives the allowable ampacity — the maximum continuous current a conductor can carry without exceeding its temperature rating, under the table conditions (not more than three current-carrying conductors in a raceway, 30 °C ambient). Change the conditions and you must adjust or correct.

2. The three temperature columns

Columns are insulation ratings, not free choices. TW/UF = 60 °C column. RHW/THHW/THW/THWN/XHHW/USE = 75 °C column. THHN/THWN-2/XHHW-2/USE-2 = 90 °C column. You may use the 90 °C ampacity only for derating math; the final circuit is still limited by the lowest-rated termination (110.14(C)) — usually 75 °C or 60 °C.

3. Core table: copper and aluminium (75 °C column)

AWG / kcmilmm²Copper 75 °C (A)Aluminium 75 °C (A)Max breaker (small conductors)
14 AWG2.0820—15 A (240.4(D))
12 AWG3.31252020 A (240.4(D))
10 AWG5.26353030 A (240.4(D))
8 AWG8.37504050 A
6 AWG13.36550—
4 AWG21.28565—
3 AWG26.710075—
2 AWG33.611590—
1 AWG42.4130100—
1/053.5150120—
2/067.4175135—

Source: NEC Table 310.16, 75 °C columns. The 90 °C column runs higher (e.g. 12 AWG copper 30 A, 10 AWG 40 A) but is usable only for derating start values per 110.14(C).

4. Why the breaker is often smaller than the wire

Three limiters sit above the table. First, 240.4(D): 14 AWG → 15 A, 12 AWG → 20 A, 10 AWG → 30 A regardless of the 75 °C numbers. Second, 110.14(C): terminations rated 60 °C or 75 °C cap the circuit at that column. Third, continuous loads (210.19(A)(1)): conductors sized at 125% of continuous current.

Worked check: 12 AWG copper shows 25 A in the table, but on a 20 A receptacle circuit with 60 °C terminations you are limited to the 60 °C value (20 A) and the 240.4(D) cap (20 A). Answer: 20 A breaker.

5. Adjustment and correction: worked example

Six current-carrying 12 AWG THHN conductors in one conduit, 40 °C ambient. Start from the 90 °C column (30 A, allowed as derating start). Adjustment for 4–6 conductors per 310.15(C)(1): ×0.80. Temperature correction (40 °C, 90 °C column, Table 310.15(B)(1)): ×0.91. Result: 30 × 0.80 × 0.91 = 21.8 A. Still above the 20 A breaker and the termination limit — circuit holds. With nine conductors (×0.70): 30 × 0.70 × 0.91 = 19.1 A — now it fails for a 20 A load; split conduits or upsize.

Second derating check, different shape: eight current-carrying 10 AWG THHN conductors in one conduit at 30 °C. Start 90 °C column: 40 A. Adjustment for 7–9 conductors: ×0.70 → 28 A. Temperature correction at 30 °C: ×1.0. Result 28 A — still above the 240.4(D) cap of 30 A? No: 28 < 30, so a 30 A breaker no longer fits this bundle; drop to a 25 A breaker or split the conduit into two groups of four (×0.80 → 32 A, fits 30 A). The pattern repeats everywhere: count conductors first, because the bundling factor moves faster than temperature.

Aluminium version of the same bundle: 10 AWG Al starts at 35 A (90 °C column). Six conductors at 40 °C: 35 × 0.80 × 0.91 = 25.5 A. On 75 °C terminations the Al column caps at 30 A anyway, so the bundle governs at 25.5 A — a 25 A breaker fits, a 30 A does not. Write both numbers on the schedule (bundle result and termination cap) and circle the lower one; that is the circuit rating. Keep this sheet with the panel schedule for the inspector.

6. Copper vs aluminium in the table

Aluminium rows run about 20% lower (12 AWG Al 20 A vs Cu 25 A at 75 °C). Check terminations: many older devices are Cu-only; use CO/ALR or Al-rated lugs. Torque to the marked value — loose Al terminations are a classic failure point.

Field tip: when a panel schedule cites only wire size without insulation type, assume the worst column that fits the age of the installation — 60 °C for old TW-era wiring, 75 °C for modern THW-era work — and verify one termination with a photo of its marking before loading the circuit above the lower value.

7. How this maps to mm² and IEC/BS

AWG 12 (3.31 mm²) sits between metric 2.5 and 4 mm². IEC 60364-5-52 Table B.52.2 (method C, copper, two loaded conductors): 2.5 mm² → 21 A, 4 mm² → 28 A, 6 mm² → 36 A. BS 7671 Appendix 4 (Table 4D5, 70 °C PVC, clipped direct): 2.5 mm² → 27 A, 4 mm² → 36 A, 6 mm² → 46 A (method C values differ slightly by standard — always cite the table you used).

8. Neutral and ground: what the table does not cover

Table 310.16 covers phase (current-carrying) conductors. Neutrals count as current-carrying in many multiwire and nonlinear-load cases (310.15(E)). Equipment grounding conductor size comes from Table 250.122 (based on the upstream breaker, e.g. 20 A → 12 AWG copper, 100 A → 8 AWG copper).

9. Common mistakes

  • Using the 90 °C column as the circuit rating. It is a derating start value, not the final answer — terminations cap it.
  • Ignoring 240.4(D). 14/12/10 AWG have hard breaker caps (15/20/30 A).
  • Counting conductors wrong. Neutrals and multiple circuits in one raceway change the adjustment factor.
  • Forgetting termination temperature. Old panel, 60 °C lugs — the whole circuit drops a column.
  • Reading aluminium at copper values. Always use the Al column.

10. Checklist

  • Insulation type identified → correct temperature column.
  • Termination rating checked (110.14(C)).
  • Small-conductor caps 240.4(D) applied.
  • Adjustment (bundling) and correction (temperature) applied from the right column.
  • Continuous load × 1.25 verified.
  • Ground sized from Table 250.122.

11. End-to-end sizing: 40 A garage feeder in conduit

Given: 9.2 kW single-phase load at 230 V (40 A), four current-carrying THHN conductors in one conduit (two circuits), ambient 35 °C, 75 °C terminations. Start from the 90 °C column for 8 AWG copper: 55 A. Adjustment for 4–6 conductors per NEC 310.15(C)(1): ×0.80 → 44 A. Temperature correction for 35 °C at 90 °C column per Table 310.15(B)(1): ×0.94 → 55 × 0.80 × 0.94 = 41.4 A. Check termination cap: 8 AWG at 75 °C = 50 A, so terminations allow 50 A; the derated 41.4 A governs. Continuous load check: 40 A × 1.25 = 50 A required — fails (41.4 < 50). Fix: split into two conduits (adjustment ×1.0): 55 × 0.94 = 51.7 A ≥ 50 — passes with a 50 A breaker, or upsize to 6 AWG. This is exactly how the table, the termination rule, and the continuous-load rule stack in real work.

12. Metric cable on the same job (IEC/BS view)

The same 40 A feeder in metric: 10 mm² copper, method C, two loaded conductors, Iz = 50 A per IEC 60364-5-52 Table B.52.2. Grouping two circuits (K2 ≈ 0.80) and 35 °C (K1 ≈ 0.94): 50 × 0.80 × 0.94 = 37.6 A — fails the 50 A continuous requirement the same way. Move to 16 mm² (Iz = 66 A): 66 × 0.80 × 0.94 = 49.6 A — borderline; separate the conduits (K2 = 1.0): 66 × 0.94 = 62 A — passes with margin. BS 7671 Appendix 4 Table 4D5 (70 °C PVC, clipped direct) gives 10 mm² → 63 A and 16 mm² → 85 A under method C reference — higher than IEC B.52.2 because the reference conditions differ, so always name the table on the calculation sheet. Either standard leads to the same engineering conclusion: grouping is what breaks this feeder, and splitting conduits fixes it.

See also

Check a full panel against these rules automatically: open the free demo and run the built-in checks on your own layout.

Try it on your own plan — open the free demo at https://gorkycad.com/cad/?demo=1, no registration needed.

Frequently asked questions

Why is my 12 AWG wire limited to 20 amps when the table says 25?

Because three limiters sit above the table: 240.4(D) caps 12 AWG protection at 20 A, terminations under 110.14(C) are often rated 60/75 °C, and continuous loads need 125% sizing. The table value is the start, not the final answer.

Can I use the 90 °C column for a higher rating?

Only as the starting point for derating math. The finished circuit is still limited by the lowest-rated termination (usually 75 °C or 60 °C) per 110.14(C).

How do I derate for many conductors in one conduit?

Multiply the 90 °C (or applicable) table value by the 310.15(C)(1) adjustment factor (4–6 conductors ×0.80, 7–9 ×0.70) and by the ambient-temperature correction from Table 310.15(B)(1). Example: 12 AWG THHN, six conductors at 40 °C → 30 × 0.80 × 0.91 = 21.8 A.

What size ground wire for a 20 A or 100 A circuit?

Per Table 250.122: a 20 A circuit needs 12 AWG copper ground, a 100 A circuit needs 8 AWG copper ground. Ground size follows the upstream breaker, not the load.

Does the neutral count as a current-carrying conductor?

Often yes — in multiwire circuits with unbalanced load and with nonlinear loads (310.15(E)). Count it when the code says so, because it changes the bundling adjustment factor.