Insulation resistance testing — the "megger test" — is the single fastest way to find out whether wiring is safe to energize. A multimeter cannot do this job: it applies 9 V, while a megger applies 500 V or 1,000 V and watches whether current leaks through damaged insulation. A cable that reads "open circuit" on a multimeter can still flash over at mains voltage.

This guide covers test voltages, minimum values from IEC 60364-6, the correct measuring method step by step, what a failure means, and the typical causes — moisture, ageing, and mechanical damage. Every number below is either calculated or tied to a standard clause.

1. What a Megger Actually Measures

An insulation resistance tester applies a high DC voltage between a conductor and earth (or between two conductors) and measures the leakage current. By Ohm's law, R = V / I. If the tester applies 500 V and measures 0.5 microamps, the resistance is 1,000 MΩ. Good insulation passes almost no current; wet or cracked insulation passes measurably more.

The result is read in megohms (MΩ) or gigohms (GΩ). New PVC cable typically reads hundreds or thousands of megohms. A reading below 1 MΩ on a 230/400 V installation is a fail by IEC 60364-6 and the circuit must not be energized until the fault is found. The test is non-destructive when done correctly — but only after electronic equipment is disconnected, because 500–1,000 V DC will damage surge protectors, LED drivers, and control boards.

2. Test Voltages: 250 V, 500 V or 1,000 V

The test voltage must match the rated voltage of the circuit, not the tester's maximum. IEC 60364-6 Table 6.1 gives three bands. Using too high a voltage risks damaging healthy insulation and connected devices; too low a voltage will not stress the insulation enough to reveal weak spots.

Nominal circuit voltageDC test voltageMinimum insulation resistance
SELV and PELV (up to 50 V)250 V DC0.5 MΩ
Up to 500 V, including 230/400 V500 V DC1.0 MΩ
Above 500 V (e.g. 690 V)1,000 V DC1.0 MΩ

For a home or small commercial building at 230/400 V, the answer is simple: 500 V DC, minimum 1.0 MΩ. The 1,000 V range is for 690 V industrial systems and for some motor windings. Never megger a circuit with electronics still connected at any voltage.

3. Minimum Values and What They Mean

The table above gives pass/fail limits, but experienced testers read more from the number. A new 20 m run of 2.5 mm² VVG/PVC cable should read well above 100 MΩ. A reading of 2 MΩ passes the standard but signals a problem developing — moisture in one box, a nicked sheath, or aged insulation. Trending readings over years is standard maintenance practice.

Rough interpretation for 230/400 V circuits at 500 V DC: above 100 MΩ — excellent, new or dry; 10–100 MΩ — good, normal for older installations; 1–10 MΩ — acceptable but investigate the low end, re-test after drying; below 1 MΩ — fail, locate the fault. Always record temperature and humidity with the reading, because insulation resistance roughly halves for every 10 °C of temperature rise.

4. Worked Calculation: Leakage Current at the Limit

Given: a 230 V circuit measures exactly the minimum, R = 1.0 MΩ at 500 V DC test voltage. Leakage current during the test: I = V / R = 500 / 1,000,000 = 0.0005 A = 0.5 mA. At mains voltage the leakage would be roughly 230 / 1,000,000 = 0.23 mA — below the 30 mA RCD threshold, which is why the RCD alone cannot replace this test: a circuit can pass the RCD yet fail insulation, and the fault will grow.

Second example: a damp cable reads 0.2 MΩ. Test current: 500 / 200,000 = 2.5 mA. At 230 V that is about 1.15 mA of continuous leakage — plus the fault is almost certainly localized and will carbonize further. That circuit fails and stays off. Compare: a healthy 500 MΩ cable leaks 500 / 500,000,000 = 0.001 mA — three orders of magnitude less.

5. Preparation: Isolate and Disconnect First

Most megger accidents and most damaged devices come from skipping preparation. Switch off and lock off the supply, verify dead with a two-pole tester, and disconnect the circuit under test at both ends where possible. Remove or disconnect everything the test voltage would destroy: LED drivers, dimmers, surge protective devices (SPDs), timers, smart switches, and any electronic meter on that circuit.

For a whole-board test, open all MCBs and test each outgoing circuit separately — a single low reading on the main switch tells you nothing about which of 20 circuits is bad. Short line and neutral together for the conductor-to-earth test on circuits with electronics you cannot fully remove, and test line-to-neutral separately only on bare wiring. Keep one lead on a clean earth point, not on painted metal.

6. Step-by-Step Measuring Method

Connect the black lead to earth (PE bar or a known earth electrode) and the red lead to the conductor under test. Select 500 V DC for 230/400 V work. Press and hold the test button for a full 60 seconds: the reading climbs as the cable charges like a capacitor, then stabilizes. Record the 60-second value, not the first flash on the display.

Measure each live conductor to earth, then line to neutral with the supply still isolated. On a three-phase board, test L1, L2, L3 to earth and to neutral. Between tests, let the circuit discharge — most testers do this automatically, but leave the leads on for a few seconds after release. If the reading drifts downward instead of stabilizing upward, stop: that is absorption by moisture, and the circuit needs drying and retesting.

7. Typical Failure 1: Moisture and Water Ingress

Moisture is the most common cause of low readings in basements, bathrooms, outdoor circuits, and underground runs. Water does not need to flood the box — condensation inside a junction box or a cable end buried in a damp wall is enough to pull a 500 MΩ cable down to single digits. Outdoor IP44 boxes with failed gaskets are classic offenders.

Diagnosis: the reading starts low and keeps falling during the 60 seconds, and it improves markedly after the circuit is dried with a heater and retested the next day. Fix the ingress first — new gasket, drip loop, sealed gland — then dry, then retest. Replacing the cable without fixing the water path guarantees a repeat failure within a season.

8. Typical Failure 2: Ageing, Heat and Mechanical Damage

PVC insulation hardens and cracks after decades, faster where it runs hot: above luminaires, near heating pipes, in overloaded conduits. Rubber-insulated cable from the last century is now at end of life everywhere. A reading that is uniformly low along a whole old circuit, with no single bad box, points to aged insulation — sectionalize the run and replace it.

Mechanical damage is the third classic: a screw through a cable, a crushed conduit, rodent damage in attics. These often read near zero on one pair of conductors and fine on the rest, which pinpoints the location between the last good and first bad accessory. Thermal imaging after a careful low-voltage load test can confirm the hot spot before opening walls.

9. Mini-Case: A 32 A Kitchen Circuit Reads 0.4 MΩ

A 6 mm² cooker circuit in a ten-year-old flat reads 0.4 MΩ line-to-earth at 500 V — a fail. The tester splits the run at the intermediate junction box: board-to-box reads 800 MΩ (healthy), box-to-cooker reads 0.3 MΩ (fault in the second half). Inside the cooker outlet, the sheath is nicked where it enters a sharp metal knockout, and there are traces of steam condensation.

Repair: new grommet, 200 mm of cable re-terminated, box dried, second test reads 600 MΩ stable over 60 seconds. Total cost is one accessory and an hour; energizing at 0.4 MΩ would have risked a line-to-earth fault under load and a carbonized box. The 60-second stabilization check is what separates a real repair from a reading that passes for five seconds and fails overnight.

10. Assumptions / When This Doesn't Apply

This guide assumes standard 230/400 V wiring with PVC or XLPE insulation tested per IEC 60364-6. It does not apply without changes when: (1) the circuit contains surge protectors, VFDs, or LED drivers that cannot be fully disconnected — use 250 V or test sections; (2) you are testing motors or transformers, which have their own polarization-index procedures; (3) the installation is above 1 kV — different standard and safety regime; (4) the cable is waterlogged along its whole length, where any reading is meaningless until dried; (5) explosive atmospheres apply, where test equipment must be rated for the zone.

11. Checklist Before You Energize

Run this list on every new or repaired circuit: supply isolated and locked; electronics and SPDs disconnected; correct test voltage selected (500 V for 230/400 V); each conductor tested to earth for 60 seconds; line-to-neutral tested on bare wiring; readings at or above 1.0 MΩ and stable; low sections split and retested individually; temperature and humidity recorded; results written into the test sheet with circuit IDs. If any line fails, the circuit stays off — no exceptions for "it will dry out by itself."

12. Documenting Results for the Handover File

A test without a record is worth little at handover. Log date, circuit designation, cable type and length, test voltage, 60-second reading per conductor, ambient conditions, tester serial and calibration date, and the name of the person who tested. Software such as GorkyCAD attaches these records to the circuit schedule so the next inspection can trend them. Rising leakage over years is the earliest warning of insulation ageing — the numbers you write today are the baseline someone will thank you for in five years.

Appendix: Reading, Meaning and Action

Keep this table on the test sheet. It turns the megohm number into a decision on site, so nobody has to argue whether 8 MΩ on a twenty-year-old lighting circuit is a pass or a problem.

Reading at 500 V DCMeaningAction
Above 100 MΩExcellent (new or dry)Energize, log baseline
10–100 MΩGood, normal ageingEnergize, trend yearly
1–10 MΩWeak point developingSplit run, find section, retest
Below 1 MΩFail per IEC 60364-6Stay off, locate fault, repair
Open the free demo and sketch the circuits you want to test: https://gorkycad.com/cad/?demo=1&lang=en — it builds the schedule, the single-line diagram, and the test sheet automatically.

Try it on your own plan: open the free demo at https://gorkycad.com/cad/?demo=1&lang=en — draw walls, place loads, and get a single-line diagram with checks in minutes.

Frequently asked questions

What voltage do I megger a 230 V house circuit with?

500 V DC, per IEC 60364-6 Table 6.1 for circuits up to 500 V. The minimum pass value is 1.0 MΩ. Use 250 V only for SELV/PELV circuits and 1,000 V for systems above 500 V.

Can I megger with the MCB on and appliances plugged in?

No. Isolate the supply, open the MCBs, and disconnect electronics, LED drivers, dimmers and SPDs first. The 500–1,000 V test voltage destroys surge protectors and control boards.

My circuit reads 5 MΩ — pass or fail?

It passes the 1.0 MΩ minimum, but 5 MΩ on a short new run is suspicious. Split the run, find the low section, check for moisture or a nicked sheath, and retest after drying.

Why does the reading keep climbing during the test?

The cable charges like a capacitor (dielectric absorption). Record the stabilized 60-second value. A reading that drifts downward instead indicates moisture absorption.

Does an RCD make insulation testing unnecessary?

No. At the 1.0 MΩ limit, leakage at 230 V is only about 0.23 mA — far below a 30 mA RCD threshold. The RCD protects people; the megger finds the degrading insulation before it becomes a fault.