What is auto panel assembly
Auto panel assembly is a key GorkyCAD Pro feature. The engineer places electrical objects on the floor plan, assigns groups and subgroups — and GorkyCAD automatically composes the distribution panel: selects devices, places them on DIN rails, creates busbars, and outputs the BOM.
This saves 1-3 hours of manual work per panel.
Step 1: Building Feeder Topology
Feeder Topology is a hierarchical power distribution model. GorkyCAD builds it automatically:
- Identifies the power source (main incomer)
- Analyzes consumer groups (lighting, outlets, heavy loads)
- Builds hierarchy: Incomer → Main breaker → RCD → Group breakers → Consumers
- Determines if additional levels are needed (sub-panels, floor panels)
Step 2: Device selection
For each group, GorkyCAD selects:
- MCB: rating = Icalc × 1.25, curve (B/C/D) by load type, breaking capacity by Isc
- RCD: rating ≥ MCB rating, leakage current (10/30/100/300 mA), type (A/AC)
- RCBO: if group needs individual leakage protection
Step 3: DIN rail placement
The placement algorithm solves a 1D bin-packing problem:
- Sorts devices by type: incomer → RCDs → group MCBs → terminals
- Groups by phase (L1, L2, L3 — for 3-phase panels)
- Places left to right, top to bottom (multi-row panels)
- Respects thermal gaps (high-rated breakers — one module gap)
- Reserves 15-20% modules for future expansion
Step 4: Auto-busbars
The busbar connects group MCBs to the RCD. Algorithm:
- Determines which MCBs are fed by which RCD
- Calculates busbar pole count (1P, 2P, 3P)
- Selects busbar length (12, 24, 36, 56 modules)
- Splits long busbars if MCBs exceed one busbar capacity
Step 5: Thermal check
GorkyCAD checks panel thermal conditions:
- Total heat dissipation of breakers at rated load
- Internal panel temperature (considering IP rating, enclosure material, ambient)
- If temperature exceeds 40°C — warning and recommendation to enlarge enclosure
Step 6: Documentation generation
Final step — automatic generation:
- Panel schematic — graphical DIN rail layout with positions
- BOM — complete list with part numbers and quantities
- Label sheet — position table for printing device labels
- Basic 3D view — panel visualization for the client
Result
The engineer gets a fully designed panel in 30 seconds of automatic composition. Just review — and send to production.