A residual current device that never trips is a decoration. It sits in the board, carries current perfectly, and does nothing on the day a fault flows through a person. Regular testing is the only way to know it still works, and the test button on the front is only half of the story.
This guide shows the full RCD test: what the button proves, what an instrument test adds, pass limits at rated and five times rated current under IEC 61008 and IEC 61009, how to do a ramp test, and what to write down so the record means something next year.
1. What the built in test button proves
The front button connects a resistor between one live pole and the opposite neutral, creating an artificial residual current inside the device. It proves the mechanics move and the electronics fire. It does not prove the installation trips in time, because it bypasses the wiring, the earth path, and the actual fault loop. Press it every six months, record the result, but never call that a complete test.
If the button fails to trip the device, replace the RCD before any instrument test. A device that cannot trip itself will not protect anyone.
2. Instrument test: what you actually measure
A calibrated RCD tester injects a known residual current between line and earth at the far end of the circuit and times the trip. Standard points are half rated current, where the device must not trip; rated current, where it must trip within 300 ms for general type; and five times rated current, where it must trip within 40 ms. Type S selective devices allow longer delays by design and are tested against their own curves.
| Test current | General type must | Type S selective |
|---|---|---|
| 0.5 x rated, e.g. 15 mA on 30 mA | Not trip within 2 s | Not trip within 2 s |
| 1 x rated, e.g. 30 mA | Trip within 300 ms | Trip 130 to 500 ms |
| 5 x rated, e.g. 150 mA | Trip within 40 ms | Trip 50 to 150 ms |
| Ramp rising current | Trip between 50 and 100 percent of rated | Same band |
Test both half cycles at 0 and 180 degrees where the instrument offers it, because electronic RCDs can be polarity sensitive. Record the slower of the two readings.
3. Worked example: 30 mA socket circuit
Circuit: 20 m of 2.5 sq mm copper feeding four sockets, RCD rated 30 mA type AC general. Tester at the farthest socket injects 15 mA: no trip after 2 s, pass. Injects 30 mA at 0 degrees: trips in 42 ms; at 180 degrees: 38 ms; both under 300 ms, pass. Injects 150 mA: trips in 18 ms, under 40 ms, pass. Ramp test: trips at 22 mA, inside the 15 to 30 mA band, pass. Total test time about three minutes. Result: device and earth path healthy.
Now the failing variant: same setup but the 150 mA test takes 68 ms. The device trips, so a casual check would call it fine. Against the 40 ms limit it fails. That delay at high fault current means higher let through energy during a real fault, and the RCD must be replaced.
4. Ramp test and what it tells you
The ramp test raises residual current slowly, typically 0.2 to 0.5 times rated per step, and records the current where the device trips. A healthy 30 mA unit trips between 15 and 30 mA. Tripping at 12 mA suggests nuisance sensitivity from age or contamination; tripping above 30 mA means it may ignore a dangerous fault. Trending ramp values over years shows degradation long before a hard failure.
Always isolate electronic loads that leak DC before a ramp test on type AC devices, because DC bias can blind them and give a false high reading. Test at the device terminals if the circuit reading is suspect.
5. Type A, F, B and DC blindness
Type AC responds to sinusoidal residual current only. Type A adds pulsating DC from rectifiers, LED drivers, and washing machine controls. Type F adds high frequency components from variable speed drives. Type B covers smooth DC from electric vehicle chargers and large solar inverters. Testing a type AC device on a circuit full of electronics can pass on the tester yet fail on a real pulsating fault.
Match the type to the load: sockets with phone chargers and LED lighting deserve type A minimum; heat pumps and washing machines need type F or A depending on manufacturer data; EV chargers need type B or a dedicated DC detection device. The wrong type is a design defect no test interval can fix.
6. Where to test from
Test from the farthest point of each protected circuit, not just at the board. A test at the board terminals proves the device but hides a broken earth in the circuit wiring. Testing at the socket proves the whole fault path including the protective conductor. On a board with six RCD protected circuits, that means six far end tests, not one board test copied six times.
For RCBO boards, test each RCBO on its own circuit. For a single RCD protecting several circuits through miniature breakers, test each outgoing circuit separately and note which breaker was on.
7. Recording results that survive audit
| Field | Example entry |
|---|---|
| Circuit and location | Kitchen sockets, board QF7, RCD 30 mA No. 3 |
| Instrument and date | Tester 14, calibrated until 2026-09 |
| 0.5x result | 15 mA, no trip, pass |
| 1x results | 42 ms at 0 deg, 38 ms at 180 deg, pass |
| 5x result | 18 ms, pass |
| Ramp | 22 mA, pass |
| Verdict and action | Pass, retest in 12 months |
Write numbers, not ticks. A tick cannot be trended, and a tick cannot prove which limit was applied.
8. Typical failures and fixes
Trips at half current: aging mechanism, moisture, or shared neutral across two RCDs. Fix the wiring fault first, then retest. Fails to trip at rated current: replace the device. Slow at five times: replace the device. Ramp above rated: replace or uprate the type. Nuisance tripping after rain: water in an outdoor box or underground joint, not a faulty RCD. Find the leak with insulation testing section by section.
Never adjust or lubricate an RCD to make it pass. A device that needs help to trip is a device that has already failed.
9. Assumptions and when this does not apply
This guide assumes low voltage AC installations with IEC 61008 RCCBs or IEC 61009 RCBOs, general or selective types, tested with a calibrated instrument. It does not cover fire protection 100 to 300 mA devices assessed by different time rules, medical IT systems with insulation monitoring instead of RCDs, or DC residual monitoring in EV and solar plants, which follow their own standards. Limits here are for 50 Hz sinusoidal test current; other waveforms need the manufacturer curves.
10. Mini case: the tripping freezer circuit
A shop reported a freezer circuit tripping its 30 mA RCD every night. The owner wanted the RCD removed. Tests showed 1x at 28 ms and 5x at 16 ms, both passing, but the ramp tripped at 14 mA, right at the sensitive edge, and insulation to earth measured 0.8 Mohm on a damp section of cable behind the freezer. Night condensation pushed leakage over the edge. The fix was a new cable section and a dedicated circuit, not RCD removal. Ramp plus insulation data saved a protection device from being blamed for a wiring fault.
11. How often to test
Press the button every six months. Run the instrument test at handover, after any modification, after any fault that operated the device, and then on a fixed cycle, yearly for commercial premises and at each tenancy change for rentals. Keep the record with the board schedule so the next electrician sees trends, not just the last tick.
12. Test intervals by premises type
Homes deserve an instrument test at handover, after any board change, and then at each tenancy change or at least every five years, with the button pressed every six months by the occupant. Shops and offices need yearly instrument tests because usage is heavier and modifications are frequent. Construction site boards and outdoor festival supplies need testing before first use and then every three months, since damage and moisture accumulate fast. Industrial plants follow their maintenance regime, typically yearly, with critical socket circuits tested every six months.
Whatever the interval, the record format stays the same: numbers, instrument identity, calibration date, and verdict. A folder with five years of ramp values shows degradation curves that justify replacement budgets; a folder of ticks justifies nothing. Set the next due date on the board schedule the day you test, not someday later.
Bring spare blank labels and a marker on every test visit. Devices without legible ratings cannot be verified against any table, so relabelling as you go steadily turns an unknown board into a documented one without extra trips.
Photograph each board schedule before leaving site so the office record matches the field reality exactly.
Try it on your own plan: open the free demo at https://gorkycad.com/cad/?demo=1&lang=en — draw rooms, place the board, run checks and export a PDF parts list.
Frequently asked questions
Does the test button replace an instrument test?
No. The button proves the mechanics inside the device. Only an instrument injecting current at the far end proves the device plus the wiring trips within 300 ms at rated and 40 ms at five times rated current.
What fails an RCD even if it trips?
Tripping too slowly: over 300 ms at rated current or over 40 ms at five times for general type. It trips, but too late to limit energy properly.
Why test at the farthest socket?
Because the earth path is part of protection. A board terminal test hides a broken protective conductor in the circuit.
When do I need type A instead of AC?
Where loads produce pulsating DC: LED drivers, electronics, washing machines, chargers. Type AC can be blind to those faults.
What numbers must the record contain?
Half current no trip, both 1x times, 5x time, ramp current, instrument identity and calibration date, and a dated verdict.