RCD types AC, A, B — differences and when to use each

Complete breakdown of RCD types: what leakage currents they detect, where they are mandatory, what PUE and IEC 60755 say. With comparison table.

Author: GorkyCAD Team

What is an RCD

An RCD (Residual Current Device) disconnects a circuit when earth leakage current appears. It's the primary protection against electric shock and fires caused by leakage.

Operating principle: the RCD measures the difference between phase and neutral currents. In normal operation, Iphase = Ineutral, difference = 0. A leakage through a human body or damaged insulation creates a differential current — the RCD trips in 20-40 ms (at 5×IΔn).

BUT: not all RCDs are equal. The type determines what form of leakage current the device responds to.

RCD Types per IEC 60755 / GOST R 51326.1

Type AC

Responds only to sinusoidal AC leakage current.

  • Cheapest and most common
  • Suitable for: incandescent lamps, resistive heating, general socket circuits without electronics
  • NOT suitable for: circuits with SMPS, inverters, dimmers, washing machines, dishwashers, air conditioners, computers

Type A

Responds to sinusoidal AC + pulsating DC leakage current.

Pulsating DC arises in circuits with half-wave rectification — virtually all modern electronics: SMPS, dimmers, chargers.

  • Mandatory for: washing/dishwashing machines (inverter-controlled motors), air conditioners, computers, server rooms
  • Recommended by IEC for all residential socket circuits
  • Price: 30-50% higher than AC

Type B

Responds to AC + pulsating DC + smooth DC leakage current.

Used where DC leakage is possible: solar inverters, EV charging stations (Mode 3, IEC 61851), VFDs, UPS, medical equipment.

  • Mandatory for EV charging stations (IEC 61851-1)
  • Mandatory for transformerless solar inverters
  • Price: 3-5× higher than AC

Type F (new)

Responds to AC + pulsating DC + mixed-frequency currents (up to 1 kHz). Intermediate between A and B. For single-phase inverter circuits (inverter AC compressors, VFD washing machines).

Type B+ (newest)

Extended B: additionally responds to currents up to 20 kHz. For high-frequency inverters.

Comparison table

CharacteristicType ACType AType FType BType B+
Sinusoidal AC✅✅✅✅✅
Pulsating DC❌✅✅✅✅
Freq. up to 1 kHz❌❌✅✅✅
Smooth DC❌❌❌✅✅
Freq. up to 20 kHz❌❌❌❌✅
Price (relative)1×1.5×2.5×4×6×
Typical useHeaters, lampsSockets, appliancesInverter AC, washersEV, solar invertersMedical, industrial VFDs

RCD selection for an apartment

Lighting (LED): Type A (LED drivers produce pulsating leakage)

Socket circuits: Type A — mandatory per modern standards

Washing/dishwasher: Type A (or F for inverter-motor models)

Electric stove: Type A (electronic controls)

Air conditioner: Type F (inverter compressor generates mixed-frequency currents)

EV charger: Type B (IEC 61851-1, mandatory)

Common mistakes

  1. Type AC for the whole apartment — doesn't protect against pulsating leakage, RCD may "go blind" from core saturation
  2. Type B where Type A suffices — 4× overpayment
  3. Incomer RCD rated too low — nuisance tripping from cumulative natural leakage

How GorkyCAD helps

  • Auto-selects RCD type based on consumer composition per group
  • Recommends Type A/F when inverter-based equipment is present
  • Warns if Type AC is on a group with a washing machine

Frequently asked questions

Is this article free?
Yes, all articles and calculators are completely free.
Where can I run calculations?
The site offers 21 free calculators: cable sizing, breakers, RCD, voltage drop and more.