What is selectivity
Protection selectivity is the system's ability to disconnect only the damaged section, leaving everything else energized.
Example without selectivity: short circuit in an outlet → main breaker trips → entire house without power.
Example with selectivity: S/C in an outlet → only that line's group breaker trips → other groups keep working.
Types of selectivity
- Current-based — upstream breaker has higher rating
- Time-based — upstream breaker trips with a delay
- Energy-based — modern breakers with energy selectivity
How GorkyCAD checks it
GorkyCAD automatically checks selectivity in the panel hierarchy:
- Builds protection chain from final breaker to main
- Compares ratings and characteristics (B/C/D)
- On violation — warning and recommendation
Practical example
Apartment panel: main C40 → RCD 40A/30mA → group breakers C16.
S/C in outlet (Isc ≈ 200 A): C16 trips in 0.01 s, C40 doesn't react in time. Selectivity achieved.
S/C at input (Isc ≈ 1500 A): both trip. Need to reconsider — e.g., main breaker with D characteristic.