Soil resistivity (ρ, ohm-metres) is the electrical resistance of a one-metre cube of soil. It is the single most sensitive input in any earth-electrode calculation: double the resistivity and you roughly double the resistance of the same rods. A table can only guess it; four pins in the ground measure it.
US readers: the method below follows IEEE Std 81, the same guide US practice references; results are always reported in Ω·m, so if your meter shows Ω·cm, divide by 100.
TL;DR
- One formula runs the method: ρ = 2πaR, where a is the pin spacing in metres and R is the measured resistance in ohms — the result is soil resistivity in Ω·m, per IEEE Std 81.
- Spacing sets the depth: as a rule of thumb, each reading reflects the soil down to roughly the pin spacing — so several spacings build a depth profile, not one number.
- Falling readings with wider spacing mean better soil below: a classic topsoil-over-clay profile can halve your electrode count versus the table guess.
- Typical loam sits near 100 Ω·m; wet clay reads tens, dry sand hundreds, rock about a thousand — always confirm on site, never design on the table alone.
- Measured resistivity beats tabulated: enter it into the design tool directly instead of picking a soil name from a list.
What soil resistivity actually is
Think of soil as a poor, uneven conductor. Clay holds water and conducts; dry sand and rock barely do. Resistivity compresses all of that — grain size, moisture, salts, temperature, compaction — into one number that formulas can use. It varies with depth, with the seasons, and even across a single plot, which is why one “book value” for a whole site is a gamble.
The Wenner method samples a large volume of ground instead of a lab jar, so it captures the layering and moisture your electrodes will actually meet. That is what makes it the standard field method from IEEE Std 81 to BS 7430 guidance.
The Wenner formula: ρ = 2πaR
Drive four pins in a straight line, equally spaced by distance a, at least 20 times deeper than… no — pins go just deep enough for contact, typically 10–20 cm, with spacing a of 1 m and more. Pass current through the outer pair, read voltage across the inner pair, and the tester gives R. Then:
ρ = 2πaR — with a in metres and R in ohms, ρ comes out directly in ohm-metres.
Repeat the line rotated 90° at the same centre and average the two: a buried pipe or cable near one traverse shows up as a mismatch between the two directions. If the two readings disagree badly, move the test line.
Spacing vs depth: what each reading sees
Current from the outer pins spreads in a bulb whose reach grows with the spacing. As a rule of thumb — typical value, not a standard clause — the reading reflects the soil down to roughly the pin spacing a. So a = 1 m samples the topsoil, a = 4 m sees the upper subsoil, and a = 8–16 m reaches the strata your long or deep-driven rods (deep-driven earth electrodes) would actually live in.
That is why a resistivity survey is a set of spacings, not a single shot: 1, 2, 4, 8 and 16 m is a practical series for a house or small commercial plot. Equal readings at all spacings mean uniform soil; a trend means layers — and layers change the design.
Worked example — topsoil over clay
Wenner readings on a cottage plot (R in ohms, a in metres): a=1 → R=23.6; a=2 → R=10.6; a=4 → R=3.8; a=8 → R=1.2. Apply ρ = 2πaR to each:
a=1: ρ = 2π × 1 × 23.6 ≈ 148 Ω·m. a=2: ρ ≈ 133 Ω·m. a=4: ρ ≈ 95 Ω·m. a=8: ρ ≈ 62 Ω·m.
Readings fall as spacing grows: resistive topsoil over conductive clay. Design conclusion: short 1.5 m rods would sit in ~140 Ω·m soil, while 3 m rods reach the ~60 Ω·m layer — roughly halving the electrode resistance for the same count. So the design uses 3 m rods, and the calculation uses the deeper value, not the topsoil one.
Check the arithmetic against your own layout in the earthing calculator — enter the measured resistivity instead of a soil name and see the resistance change.
Typical values table: clay, loam, sand, gravel, rock
Use this table to sanity-check your readings — never as a substitute for them. All values are typical; confirm on site:
| Soil | Typical resistivity (Ω·m) | What it means for rods |
|---|---|---|
| Wet clay | 40 | Kind soil: short rods usually suffice |
| Dry clay | 80 | Normal soil: standard 3 m rods work |
| Loam | 100 | Reference soil: baseline for estimates |
| Chernozem (black soil) | 30 | Kind soil, but verify moisture in summer |
| Wet sand | 150 | Needs longer rods or more of them |
| Dry sand | 500 | Hard soil: consider deep-driven rods or a ring |
| Gravel | 800 | Hard soil: ring earth electrode territory |
| Rock | 1000 | Extreme: foundation electrode, ring, or soil treatment |
Why the same site gives different values in summer and winter
Two forces move the numbers. Moisture: a dry August topsoil can read several times higher than the same ground after autumn rain. Frost: frozen soil is dramatically more resistive, and the frost line bites exactly the top metre where short rods live — a winter reading at a = 1 m can exceed the summer one by an order of magnitude while a = 8 m barely moves.
Practical consequences: survey in the wet season if you can; always record weather, recent rain and frost depth with the readings; and compare surveys across seasons only at equal spacings. When a design must hold year-round, size electrodes for the worst-season profile and verify with a cold-weather re-test.
From measured ρ to a real design
A measured profile changes three decisions. Depth: pick rod lengths that reach the conductive layer instead of floating in topsoil. Count: recompute the system resistance with the measured ρ — fewer rods in good soil, more (or a ring earth electrode, Type B arrangement per IEC 62305-3) in bad. Acceptance: the target for the finished system — for example the lightning-protection earth commonly specified around 10 Ω (typical value, confirm with your code and inspector) — is checked against a calculation that used your soil, not a book’s.
In GorkyCAD’s earthing workspace the measured-resistivity field overrides the soil-name table, so the plan, the calculation sheet and the bill of quantities all follow your survey. That closes the loop the table-guess leaves open: measure → enter → design → re-measure after installation.
Common mistakes
- Unequal or sloppy spacing. The formula assumes four pins exactly a apart; a 10% spacing error is a 10% resistivity error. Fix: tape-measure every setup, keep pins vertical.
- Pins barely scratching dry crust. Poor contact adds noise that looks like high resistivity. Fix: drive pins 10–20 cm, water the contact points, wait a few minutes.
- Testing next to buried metal. Pipes, cables and existing earthing systems warp the field. Fix: run a second traverse at 90°; if the two disagree, relocate.
- One spacing only. A single a = 2 m reading cannot see layers and may sample exactly the wrong one. Fix: always run a series (1, 2, 4, 8 m minimum).
- Mixing up Ω·m and Ω·cm. Some meters and lab reports use ohm-centimetres; using the number as-is inflates resistivity a hundredfold. Fix: always convert — Ω·m = Ω·cm ÷ 100 — and label the unit.
- Designing on the table value after measuring. The survey sits in a drawer while the calculation uses “loam, 100”. Fix: enter the measured ρ into the design tool the same day.
FAQ
What is the Wenner method in simple terms?
Four pins in a straight line, equal spacing a: current goes through the outer pair, voltage is read across the inner pair, and soil resistivity is ρ = 2πaR. Wider spacing samples deeper soil, so a series of spacings builds a depth profile. It is the standard field method of IEEE Std 81.
How deep does each Wenner reading look?
As a rule of thumb, each reading reflects the soil down to roughly the pin spacing: a = 2 m samples about the top 2 m. It is a typical value, not exact — real current spreads in a bulb. For design, run 1, 2, 4, 8 and 16 m spacings and read the trend.
How do I spot two-layer soil in the numbers?
Convert each spacing with ρ = 2πaR and look at the trend. Steadily falling values mean conductive soil below (for example topsoil over clay); rising values mean resistive ground below. Size your rods to live in the better layer, and calculate with that layer’s value.
What resistivity values should I expect?
Very roughly: wet clay tens of Ω·m, loam around 100, dry sand several hundred, gravel near 800, rock around 1000. Treat these as sanity checks only — moisture, frost and salts move real readings far from any table, so always measure the site.
How do I use measured resistivity in a design?
Pick rod lengths that reach the best measured layer, recompute the system resistance with the measured value, and check it against your target (for example the commonly specified LPS earth of about 10 Ω). In GorkyCAD you enter the measured ρ directly and it overrides the soil table everywhere.
Try it in your browser
Bring your Wenner readings: the earthing calculator turns measured resistivity and rod layout into expected resistance, plan and parts list — free, no install.
Related
- Earthing a home: step-by-step guide