Most battery banks fail for boring reasons: the load was underestimated, the usable capacity was confused with the nameplate, or nobody planned for two cloudy days in a row. This guide sizes a solar battery bank from measured daily energy, honest depth of discharge, and the number of backup days you actually need.

We work one complete example — a house using 10 kWh per day with 2 days of backup — and give you tables for lithium iron phosphate versus lead-acid, plus inverter and cable checks. Norms referenced: IEC 60364-4-41 for protection, IEC 60364-5-52 for wiring, and manufacturer cycle-life data for depth of discharge.

1. Start from daily energy, not peak power

Battery sizing is an energy problem measured in kilowatt-hours, while inverter sizing is a power problem measured in kilowatts. Confusing the two is the most common mistake. First list every load with watts and hours per day, multiply, and add a 15 to 20 percent margin for measurement error and growth.

A fridge at 150 W running an equivalent of 8 full-load hours uses 1.2 kWh per day. A 3 kW well pump running 40 minutes uses 2.0 kWh. Lights, electronics, and a washing machine add the rest. Our worked house totals 8.6 kWh of metered loads, and with a 16 percent margin we design for 10 kWh per day of AC energy out of the inverter.

2. The sizing formula in one line

Usable energy needed equals daily AC energy times backup days, divided by inverter efficiency. Nameplate energy equals usable energy divided by allowable depth of discharge, divided by the temperature and aging factor. Write both steps down so anyone can audit the result.

Formula: E_usable = E_day x N_days / eta_inv. Then E_nameplate = E_usable / (DoD x k_age_temp). Here eta_inv is typically 0.90 to 0.95 for a modern hybrid inverter, DoD is 0.80 to 0.90 for LiFePO4 and 0.50 for flooded or AGM lead-acid, and k_age_temp is 0.85 to 1.0 depending on climate and end-of-life reserve.

3. Worked example: 10 kWh per day, 2 backup days

Given: E_day = 10 kWh AC, N = 2 days, eta_inv = 0.93, LiFePO4 DoD = 0.85, k_age_temp = 0.95. Step one: E_usable = 10 x 2 / 0.93 = 21.5 kWh of usable storage. Step two: E_nameplate = 21.5 / (0.85 x 0.95) = 21.5 / 0.8075 = 26.6 kWh nameplate.

At 51.2 V nominal that is 26,600 / 51.2 = 520 Ah. Practical build: six 51.2 V 100 Ah server-rack modules give 30.7 kWh nameplate and 24.9 kWh usable at 85 percent DoD with the aging factor included — comfortably above the 21.5 kWh target. Same math with AGM lead-acid at 50 percent DoD needs 21.5 / 0.50 = 43 kWh nameplate, or about twenty 12 V 200 Ah blocks — roughly double the footprint and weight.

4. Battery comparison table

The table below uses typical 2026 retail figures for stationary storage. Check your supplier datasheets — cycle life depends strongly on the exact DoD and temperature in the warranty fine print.

ParameterLiFePO4 (51.2 V rack)AGM lead-acid (12 V)Flooded lead-acid
Usable DoD for daily cycling80 to 90 percent50 percent50 percent
Cycle life at stated DoD4000 to 6000 cycles800 to 1200 cycles1000 to 1500 cycles
Round-trip efficiency94 to 97 percent80 to 85 percent75 to 82 percent
MaintenanceNone, BMS built inNone, sealedWatering, ventilation
Footprint for 25 kWh usableAbout 0.5 square meterAbout 1.5 square meterAbout 1.7 square meter

5. Convert energy into amp-hours at your bus voltage

Amp-hours only mean something together with voltage. Energy in watt-hours divided by nominal bus voltage gives amp-hours: Ah = Wh / V_nom. A 48 V system (16 LiFePO4 cells, 51.2 V nominal) needs one quarter of the amp-hours of a 12 V system for the same energy.

That is why anything above about 3 kWh of storage belongs on 48 V: at 12 V our 21.5 kWh usable bank would demand 1,800 Ah of bus capacity and currents above 200 A, which means very heavy cable and large voltage drop. At 51.2 V the same bank is about 420 Ah usable, and a 5 kW inverter draws under 110 A at full load.

Cable check for the example bank: 110 A over 2 meters one-way on 70 sq mm copper gives R = 0.0175 x 4 / 70 = 0.001 ohms round trip, so drop is 110 x 0.001 = 0.11 V — negligible. Size battery cable for fault withstand and termination temperature first, voltage drop second; anything above 2 meters one-way deserves the same two-line calculation before you buy copper.

6. Size the inverter separately

The inverter must carry the largest coincident peak in kilowatts and start the largest motor. Add all loads that can run at once, apply a realistic coincidence factor, then check the single largest motor start against the inverter surge rating, typically 2 times continuous for 5 seconds.

Example: evening peak of 4.2 kW running plus a 1.1 kW well pump starting at 4 times running (4.4 kW surge) needs 4.2 + 4.4 = 8.6 kW of momentary capacity. A 6 kW hybrid with 12 kW surge covers it; a 5 kW unit with 10 kW surge also covers it with less headroom. An 8 kW unit is justified only if an electric cooker and the pump coincide regularly.

Check the battery discharge rate too: 8.6 kW of surge from a 30.7 kWh LiFePO4 bank is 0.28C, well inside continuous ratings, and the steady 4.2 kW evening peak is 0.14C. If the surge exceeded 1C on lithium or 0.3C on AGM, the bank would sag under load even with enough kilowatt-hours — energy without power delivery is the second most common undersizing mistake.

7. Autonomy days: the honest trade-off

Each extra backup day adds one full daily load of usable capacity. Two days is the usual residential compromise; three days doubles the battery bill for an event that happens a few times per year. Off-grid cabins that must ride out a week of bad weather either accept generator backup or pay for it in lithium.

Backup daysUsable kWh neededLiFePO4 nameplate (85 percent DoD)Comment
110.812.7 kWhGrid-tied with outages under a day
221.525.3 kWhStandard resilient home
332.338.0 kWhWeak grid or frequent storms

8. Temperature, aging, and the factors people skip

Lead-acid loses usable capacity fast below freezing — at minus 10 degrees Celsius expect roughly 60 percent of the 20-hour rating. LiFePO4 keeps capacity but most battery management systems refuse to charge below 0 degrees, so an unheated shed in a cold climate needs a heated enclosure or a low-temperature charge cutoff with a warning.

Plan end of life on day one: size so the bank still meets the autonomy target at 80 percent state of health. That is the k_age_temp factor of 0.85 to 0.95 in the formula. A bank that exactly meets the target when new will miss it in year six.

9. Mini-case: the 10 kWh house, final bill of materials

A two-bedroom house with a fridge, washing machine, office, LED lighting, and a small well pump metered 8.6 kWh per day over two weeks. With margin the design value is 10 kWh. Two backup days at 93 percent inverter efficiency need 21.5 kWh usable. Six LiFePO4 rack modules (30.7 kWh nameplate) deliver 24.9 kWh usable at 85 percent DoD after aging reserve.

Paired with a 6 kW hybrid inverter (12 kW surge), a 125 A battery breaker, and 2 x 70 sq mm copper battery cables under 2 meters, the system rides through two overcast days and starts the pump without dimming the lights. Total installed storage cost lands roughly 40 percent below the equivalent AGM bank over ten years because the lead-acid set needs replacement twice.

11. Maintenance and commissioning checklist

Torque every terminal to the datasheet value and record it — loose lugs cause most thermal events in battery rooms. Verify polarity with a meter before closing the battery breaker, then confirm the battery management system sees all cells or modules within 50 mV at rest.

Run a capacity test in the first month: discharge a known load from full to the low-voltage cutoff and compare delivered kilowatt-hours with the design usable energy. Log the result as the baseline for warranty claims. Check quarterly in year one: terminal torque, enclosure temperature spread, firmware version, and any cell-voltage drift alarms. Keep a one-page log — it pays for itself the first time a warranty question arises.

Between inspections, watch two numbers on the monitoring portal: overnight state-of-charge drift between parallel strings and the spread between highest and lowest cell at top of charge. A string that consistently finishes 5 percent lower than its neighbors has a weak module or a high-resistance lug — find it with a thermal camera at 0.3C discharge before it becomes a warranty claim in year eight.

12. Assumptions and when this does not apply

Assumptions: inverter efficiency 0.93; LiFePO4 DoD 85 percent daily; AGM DoD 50 percent; aging and temperature factor 0.95; 48 V bus; moderate climate with batteries indoors. This method does not apply when the main load is seasonal electric heating (size from the worst month, not the average day); when the site needs more than 3 days of true autonomy (do a generator-hybrid study instead); when batteries sit in unheated space below freezing (add heating or switch chemistry); when the inverter also back-feeds the grid (utility export limits may cap the design); or when loads above 10 kW run continuously (that is a commercial design with demand metering).

Try it free in your browser — open the demo: https://gorkycad.com/cad/?demo=1

Frequently asked questions

How many kWh of battery do I need per day of backup?

Roughly your daily AC kWh divided by inverter efficiency (about 1.08x at 93 percent), then divided by usable DoD. For 10 kWh per day that is about 12.7 kWh of LiFePO4 nameplate per backup day.

Is LiFePO4 really cheaper than lead-acid?

Per usable kWh over ten years, usually yes: 4000 to 6000 cycles at 80 to 90 percent DoD versus about 1000 cycles at 50 percent for lead-acid, plus higher round-trip efficiency. Lead-acid wins only on upfront price.

Can I mix old and new batteries?

Do not mix ages, capacities, or chemistries in one bank. The weakest block limits the whole string and ages the new units prematurely. Expand with an identical batch or a separate managed string.

What size inverter pairs with a 25 kWh bank?

Energy does not set inverter size — coincident peak does. Most 10 kWh per day homes fit a 5 to 6 kW hybrid with double surge; verify the largest motor start against the surge rating.

Do batteries work in an unheated garage?

LiFePO4 keeps capacity in the cold but usually blocks charging below 0 C; lead-acid loses roughly 40 percent of capacity at minus 10 C. Put the bank in heated space or add a heated, ventilated enclosure.