At 12 V, a modest 1 kW load draws 83 A — more than a whole apartment feeder at 230 V. Low-voltage DC systems punish thin cable twice: heating from high current and voltage drop that stalls inverters long before the cable feels warm. This guide sizes battery cable by both current and drop, with fuse coordination and a full 3 kW inverter example. How to use this guide: read the sizing table for your voltage first, then run the two-step check (ampacity, then drop) on your own length and current. The 3 kW example shows every substitution; repeat it with your cutoff voltage and run length. Print the sizing table and tape it inside the battery cabinet door for future troubleshooting.

Why 12/24/48 V systems eat cable

Power is power: I = P / U. The same 1000 W draws 83 A at 12 V, 42 A at 24 V, 21 A at 48 V. Double the system voltage and current halves — losses (I²R) quarter. That is why installers push 24 V above ~1 kW and 48 V above ~3 kW: the cable stays manageable and the voltage drop stays within the inverter's input window. If your 12 V cable quote looks absurd, raising system voltage is usually cheaper than buying copper.

Battery cable sizing table by power and voltage

Minimum copper cross-sections for runs up to 3 m one-way at 25 °C, keeping drop under ~3% (verify your run length in the next section). Fuse ratings assume time-delay characteristics matched to cable ampacity.

Load (W)12 V: current / cable / fuse24 V: current / cable / fuse48 V: current / cable / fuse
50042 A / 10 mm² / 60 A21 A / 4 mm² / 30 A10 A / 2.5 mm² / 16 A
100083 A / 25 mm² / 100 A42 A / 10 mm² / 60 A21 A / 4 mm² / 30 A
2000167 A / 50 mm² / 200 A83 A / 25 mm² / 100 A42 A / 10 mm² / 60 A
3000250 A / 2×50 mm² / 300 A125 A / 35 mm² / 160 A63 A / 16 mm² / 80 A
5000— / busbar only208 A / 70 mm² / 250 A104 A / 25 mm² / 125 A

Step 1 — size by current (ampacity)

Take continuous current I = P / Umin, using the lowest battery voltage (10.5 V for 12 V lead-acid under load, 21 V for 24 V, 42 V for 48 V) — not nominal. A «3 kW at 12 V» inverter draws 3000 / 10.5 = 286 A at cutoff, not 250 A. Size cable ampacity above that after temperature derating (engine rooms hit 40–50 °C; see derating and ampacity basics). Fine-stranded flexible cable (class 5/6) with proper lug crimps is mandatory at these currents — stiff building wire cracks at terminals.

Step 2 — check voltage drop (usually governs)

DC drop: ΔU = 2 × ρ × L × I / S, with ρ = 0.0175 Ω·mm²/m for copper, L one-way length, S in mm². Keep drop under 3% for inverter feeds (0.36 V at 12 V!) and 5% for general DC loads per IEC 60364-5-52 guidance adapted to ELV. Example: 125 A over 2 m on 35 mm²: ΔU = 2 × 0.0175 × 2 × 125 / 35 = 0.25 V (1.0% of 24 V — fine). The same run at 12 V and 250 A needs 70 mm² for equal drop. When drop governs, upsize copper — never «accept» 8% drop on an inverter feed.

Fuses and disconnects: every battery positive gets one

Fuse the battery positive within 150–200 mm of the terminal (Class T, ANL, or Mega for main feeds; MIDI/ATO for branches), rated above continuous current but below cable ampacity — typically 1.25× continuous, next standard size down if that exceeds cable rating. Fuse each parallel string separately, fuse the inverter feed separately from DC distribution, and provide a battery disconnect switch rated for full current. Unfused battery cable is a fire starter: a dropped wrench across 25 mm² delivers kiloamps with no upstream device to clear it.

Fuse and disconnect pairing for common battery feeders (verify against cable ampacity after derating):

Cable (copper)Main fuseDisconnect switch
10 mm²60 A ANL / Mega100 A battery switch
25 mm²100–125 A ANL200 A battery switch
35 mm²160 A ANL200 A battery switch
50 mm²200 A Class T300 A battery switch
70 mm²250 A Class T400 A battery switch

Worked example: 3 kW inverter on 24 V, 2 m run

Given: 3000 W inverter, 24 V bank (cutoff 21 V), 2 m one-way, copper, 30 °C. Step 1: Imax = 3000 / 21 = 142.9 A. Step 2: cable by current → 35 mm² (Iz ≈ 150 A). Step 3: drop check: ΔU = 2 × 0.0175 × 2 × 142.9 / 35 = 0.286 V = 1.2% of 24 V — passes the 3% limit. Step 4: fuse 1.25 × 125 A nominal = 156 A → 160 A ANL at the battery positive, below cable ampacity. Step 5: lugs: 35 mm² tinned copper, M8, hydraulic crimp + adhesive heat-shrink. Compare with the voltage-drop method and the AC cable procedure — same physics, harsher numbers at low volts.

Lugs, torque, and routing that prevent fires

Most battery failures are terminations, not cable: strip to the lug depth, crimp with the correct die (a loose crimp runs 30–50 °C hotter), torque to spec, protect with adhesive-lined heat-shrink, and support heavy cable so weight doesn't hang on the terminal. Route positive and negative together (minimizes inductance and fault loop), keep signal wiring away from battery feeds, ventilate lead-acid banks (hydrogen), and never parallel old and new batteries in one bank without checking balance currents.

Assumptions / when this doesn't apply

This guide assumes: (1) copper conductors at ≤30 °C ambient — aluminum needs roughly 1.6× section and is rare in battery feeds; (2) lead-acid or LFP banks with the cutoff voltages above — exotic chemistries have different windows; (3) runs under ~5 m — longer runs (remote sheds, boats) need a dedicated drop calculation, often forcing 48 V; (4) continuous ratings — cranking/starting surges follow engine-maker rules, not this guide; (5) installations under IEC 60364 / ABYC-style practice — utility-scale storage has its own standards. When an assumption fails, redo the math for your case: measure ambient where the cable actually runs, look up your chemistry's cutoff voltages, and compute drop for the true one-way length including every lug and shunt. Document the numbers on the wiring diagram for the next person.

Mini case: the campervan that kept rebooting

A 2 kW 12 V inverter on 16 mm² over a 3 m run: current 2000/10.5 = 190 A (already above 16 mm² ampacity), drop = 2 × 0.0175 × 3 × 190 / 16 = 1.25 V (10.4%). Under load the inverter saw 11.1 V, hit low-voltage cutoff, and rebooted — diagnosed as «faulty inverter» twice. Fix: system rebuilt at 24 V with 25 mm² (83 A, drop 0.35 V / 1.5%), 100 A fuse. Same inverter power, one-third the copper stress, zero reboots. The cable didn't feel hot — the inverter starved silently.

Common mistakes

First, sizing to nominal 12/24 V instead of cutoff voltage — understates current by 12–15%. Second, forgetting the return path (factor of 2 in ΔU). Third, no fuse at the battery («the inverter has one» — it protects itself, not your cable). Fourth, automotive chassis-return thinking on house systems — run a proper negative cable. Fifth, paralleling thin cables instead of one correct section without matched length and terminations.

Busbars and parallel runs for big banks

Above about 200 A at 12 V or 400 A at 24 V, single cables become unwieldy, so switch to copper busbar with one correctly sized tap per load. When paralleling cables, keep both runs the same length, same lugs, same routing, and fuse each run individually; unequal paths share current unevenly and one run silently overloads. Torque busbar bolts to spec with spring washers where vibration exists, cover live bars with insulating boots, and label polarity at every joint. A tidy busbar with four labeled taps beats a nest of six paralleled cables every time.

Disconnects, shunts, and monitoring

Install a master battery switch rated for continuous full current, a precision shunt in the negative lead for coulomb-counting monitors, and a fuse between battery and shunt wiring. Size the shunt so normal current lands mid-scale for accuracy. Program the monitor with exact bank capacity and charge efficiency; default settings misreport state of charge by 15 to 20 percent. Review the first week of current logs: unexpected nighttime draws reveal loads wired before the shunt or bypassing the fuse entirely.

Try it now: sketch your panel or installation in the free GorkyCAD demo — it computes currents, suggests breaker sizes, and builds a single-line diagram in minutes.

Plan the DC side in the free GorkyCAD demo at https://gorkycad.com/cad/?demo=1 — currents, drop, fuse ratings, and a parts list in one place.

Frequently asked questions

What size cable do I need for a 3 kW inverter?

On 24 V with a 2 m run: 35 mm² copper with a 160 A fuse at the battery (142.9 A at 21 V cutoff, 1.2% drop). On 12 V the same power needs roughly double the copper — consider 48 V instead.

Should battery cable be sized by current or voltage drop?

By both: ampacity first, then voltage drop — and drop usually governs below 48 V. A cable that is thermally fine can still starve an inverter at 10% drop.

What fuse goes on a battery cable?

A fast-acting fuse (Class T, ANL, Mega) within 150–200 mm of the battery positive, rated ~1.25× continuous current but below cable ampacity. Fuse every parallel string separately.

Is 12 V or 24 V better for 2 kW?

24 V: current halves (83 vs 167 A), losses quarter, cable drops from 50 to 25 mm². Above ~1 kW, 24 V is almost always cheaper overall; above ~3 kW go 48 V.

Why does my inverter reboot under load?

Usually voltage drop, not a faulty inverter: measure DC volts at the inverter terminals under load. If it sags near cutoff while the battery holds up, the cable is too thin or too long.