The short answer
For a typical 50 A, 120/240 V subpanel feeder with 75 °C terminations, use 6 AWG copper or 4 AWG aluminum for the two hot conductors and the neutral, with a 10 AWG copper (or 8 AWG aluminum) equipment grounding conductor. Protect the feeder with a 50 A double-pole breaker in the main panel, run all four wires, and keep neutral and ground separate in the subpanel.
That answer covers the common case. Long runs, high ambient temperature, more than three current-carrying conductors in one conduit, and 60 °C terminations can all force a larger size, so read the sections below before you buy wire.
Ampacity: what NEC 310.16 says
Conductor ampacity comes from NEC Table 310.16, and the column you may use is set by the lowest temperature rating in the circuit: conductor insulation, breaker terminals, and panel lugs. Most modern breakers and panels are rated 75 °C, but older 60 °C equipment limits you to the 60 °C column even if the wire itself is marked THHN-2 (90 °C).
| Conductor | 60 °C column | 75 °C column | Good for 50 A? |
|---|---|---|---|
| 8 AWG copper | 40 A | 50 A | Only with 75 °C terminations throughout |
| 6 AWG copper | 55 A | 65 A | Yes, the standard choice |
| 6 AWG aluminum | 40 A | 50 A | Only with 75 °C terminations throughout |
| 4 AWG aluminum | 55 A | 65 A | Yes, the standard aluminum choice |
Notice the pattern: 8 AWG copper and 6 AWG aluminum sit exactly at 50 A in the 75 °C column with zero margin. Any derating for temperature or fill drops them below 50 A. That is why experienced electricians default to 6 AWG copper or 4 AWG aluminum: one size up buys real headroom for a few dollars per foot.
Copper vs aluminum for a 50 A feeder
Copper costs more per foot but terminates easily, needs smaller conduit, and resists corrosion at connections. Aluminum costs substantially less for the same ampacity but needs one size larger conductors, antioxidant compound per manufacturer instructions, and terminals explicitly rated for aluminum (marked AL/CU or CO/ALR where applicable). Both are fully code-compliant when installed per their listings.
For a 50 A feeder the practical comparison is 6 AWG copper vs 4 AWG aluminum. Aluminum saves money on long runs but the larger conduit and careful termination practice eat part of the savings. For short indoor runs under 50 feet, most installers choose copper for simplicity. For a 150-foot run to a detached garage, aluminum often wins on total installed cost. Either way, torque every lug to the labeled value with a torque screwdriver: loose aluminum terminations, not aluminum itself, cause the failures people blame on the metal.
Voltage drop over distance
NEC informational notes recommend keeping feeder voltage drop to about 3 percent (210.19(A) Note 3). For a 240 V feeder, 3 percent is 7.2 V. The voltage-drop formula for a single-phase 240 V circuit is Vd = 2 × K × I × L / CM, where K is 12.9 for copper, I is current, L is one-way length in feet, and CM is the circular-mil area of the conductor (6 AWG = 26,240 CM).
Worked example: 50 A load, 100 feet one-way, 6 AWG copper. Vd = 2 × 12.9 × 50 × 100 / 26,240 = 129,000 / 26,240 = 4.9 V, which is 2.0 percent of 240 V. Acceptable. Stretch that run to 150 feet: Vd = 2 × 12.9 × 50 × 150 / 26,240 = 7.4 V, or 3.1 percent, just over the recommended limit. The fix is 4 AWG copper (41,740 CM): Vd = 193,500 / 41,740 = 4.6 V, or 1.9 percent. Run this math with your actual length before buying wire, or use a voltage drop calculator to check distance against size.
Breaker and subpanel ratings
The feeder breaker in the main panel must be 50 A (or smaller): the breaker protects the feeder conductors, so its rating may not exceed the conductor ampacity after all derating. A 50 A double-pole breaker on 6 AWG copper at 75 °C is the textbook pairing.
The subpanel itself may be rated higher than the feeder. A 100 A rated subpanel fed from a 50 A breaker is completely normal: the panel rating is a maximum, and the 50 A feeder breaker is what limits the actual current. This combination is popular because the larger panel gives more breaker spaces and allows a future feeder upgrade to 100 A without replacing the panel. What you must not do is the reverse: a 60 A breaker protecting 8 AWG conductors rated 40–50 A is an overload waiting for an inspector to catch it.
Conduit sizing and fill
Individual THHN/THWN conductors in conduit must comply with NEC Chapter 9 fill limits: 53 percent for one conductor, 31 percent for two, 40 percent for three or more. A 50 A feeder carries four wires (two hots, neutral, ground), so the 40 percent limit applies to the three current-carrying conductors plus the ground.
| Feeder set | Minimum EMT | Minimum PVC Sch 40 | Notes |
|---|---|---|---|
| 3 × 6 AWG Cu + 1 × 10 AWG ground | 3/4 in | 1 in | Comfortable pull, room for bends |
| 3 × 4 AWG Al + 1 × 8 AWG ground | 1 in | 1-1/4 in | Aluminum needs the larger pipe |
| 6/3 NM-B cable (indoor only) | n/a | n/a | No conduit needed where NM is allowed |
When in doubt, go one trade size up: the cost difference between 3/4-inch and 1-inch conduit is small, but the difference in pulling effort through two 90-degree bends is enormous. Verify any combination with a conduit fill calculation before rough-in.
The 4-wire feeder and separated neutral and ground
Every subpanel feeder needs four wires: two ungrounded hots, one grounded neutral, and one equipment grounding conductor. The neutral carries normal return current; the ground carries only fault current. In the subpanel these two systems must stay separate: remove the bonding jumper or screw, land all neutrals on the isolated neutral bar, and land all grounds on the ground bar bonded to the enclosure.
The reason is fault clearing. If neutral and ground are bonded in the subpanel, normal neutral current splits onto the grounding conductors and metal enclosures, energizing every grounded surface downstream. Keep them apart everywhere except the main service disconnect, and ground-fault current gets a clean low-impedance path that trips the breaker fast.
Detached buildings need their own grounding
A feeder to a separate building or structure triggers NEC 250.32: the detached garage or shed needs its own grounding electrode system (typically one or two ground rods) connected to the subpanel ground bar. This local electrode handles lightning and voltage surges at the remote building; it does not replace the equipment grounding conductor in the feeder, which is still required and still provides the fault-clearing path back to the main panel.
Bond the electrode conductor to the ground bar only, never to the neutral bar. Test the electrode if your jurisdiction requires a resistance reading, and document the rod locations on the as-built plan so a future excavator does not find them with a backhoe.
Common 50 A feeder mistakes
- 8 AWG copper on a 60 A breaker: 8 AWG tops out at 50 A even at 75 °C. Size the breaker to the wire, not to the plans wish list.
- Three-wire feeder to a subpanel: hot-hot-neutral with no ground was legal decades ago for existing installs only. New feeders need four wires, always.
- Neutral bonded in the subpanel: leaving the bonding screw in puts neutral current on every grounded surface. Remove it and verify with a continuity check.
- No electrode at a detached building: the feeder ground alone does not satisfy 250.32. Drive the rod and connect it to the ground bar.
- Ignoring voltage drop on long runs: a 50 A conductor that is fine at 60 feet can be 5 percent down at 180 feet. Do the Vd = 2KIL/CM math first.
If you are still sizing the load itself, work through a breaker sizing calculation first, then sketch the feeder on the floor plan. The free GorkyCAD demo lets you place the subpanel, draw the feeder route, and export the layout before you trench or pull conduit.
Worked example: sizing a 120-foot feeder
Given: a 50 A subpanel in a detached garage, 120 feet one-way from the main panel, 75 °C terminations throughout, PVC conduit underground. Step 1: base ampacity. From Table 310.16, 6 AWG copper at 75 °C gives 65 A and 4 AWG aluminum gives 65 A, so both clear the 50 A breaker with margin.
Step 2: voltage drop. Try 6 AWG copper (26,240 CM) at a realistic 40 A continuous-equivalent load: Vd = 2 × 12.9 × 40 × 120 / 26,240 = 123,840 / 26,240 = 4.7 V, or 2.0 percent of 240 V. Acceptable. At the full 50 A the drop is 5.9 V (2.5 percent), still inside the 3 percent recommendation. Step 3: conduit. Three 6 AWG THWN plus one 10 AWG ground fit in 1-inch PVC Schedule 40 with room to pull. Step 4: grounding. Drive the ground rod at the garage per NEC 250.32, land it on the ground bar, keep neutral isolated. Result: 6 AWG copper, 50 A breaker, 1-inch PVC, 4-wire plus local electrode. If the run were 180 feet instead, the same math pushes past 3 percent and 4 AWG copper (or 2 AWG aluminum) becomes the answer.
Frequently asked questions
Can I use 8 AWG copper for a 50 A subpanel?
Only if the 8 AWG copper conductors are rated 75 °C and the calculated load plus conditions allow it. In practice most installers use 6 AWG copper for a 50 A feeder because 8 AWG at 60 °C terminations is limited to 40 A. Check the 75 °C column of NEC 310.16 and your terminal ratings before choosing 8 AWG.
Is a 100 A subpanel OK on a 50 A feeder breaker?
Yes. The subpanel rating is the maximum it can handle, not what it must be fed with. A 100 A rated panel fed from a 50 A breaker in the main panel is a common and compliant setup, and it leaves room for a future feeder upgrade.
Do I need a ground rod at a detached garage subpanel?
Yes. A separate building or structure supplied by a feeder needs its own grounding electrode system under NEC 250.32, connected to the subpanel ground bar. The feeder still carries a separate equipment grounding conductor back to the main building.
Can neutral and ground share a bar in a subpanel?
No. In a subpanel, neutral and equipment ground must be separate: remove the bonding jumper, land neutrals on the isolated neutral bar, and land grounds on the ground bar bonded to the enclosure. They bond together only at the main service.
What size conduit for a 50 A subpanel feeder?
It depends on the conductors. Three 6 AWG THHN plus one 10 AWG ground fit comfortably in 3/4-inch EMT or 1-inch PVC Schedule 40. Aluminum 6 AWG feeders and cable assemblies need larger conduit, so always run a conduit-fill calculation per NEC Chapter 9 before buying.