AWG confuses even experienced electricians. A larger AWG number means a thinner wire, metric cable is labeled the opposite way, and the same copper size can carry different current depending on insulation, installation method and ambient temperature. If you buy wire in the US or read an American panel schedule, you need a reliable AWG to mm2 conversion chart plus an understanding of when each size is actually used.
This guide gives you a full conversion table from 18 AWG to 4/0, explains the math behind it, compares US and IEC practice, and finishes with a complete 32 A circuit calculation. All ampacity values reference NEC Table 310.16 for copper with 60 C, 75 C and 90 C insulation, and IEC 60364-5-52 for metric context.
Why AWG Still Matters
American Wire Gauge is a logarithmic scale that dates back to the number of drawing operations used to make the wire. Each 3 AWG steps roughly halve or double the cross-section. That is why 10 AWG is about 5.26 mm2 while 13 AWG would be near 2.62 mm2 if it existed as a standard building size. Metric practice under IEC 60364 is simpler: you name the cross-section directly, such as 2.5 mm2 or 6 mm2.
You meet AWG in four common situations. First, imported equipment with US terminals marked 12 AWG or 10 AWG. Second, American DIY guides and generator manuals. Third, solar and automotive cable sold by AWG. Fourth, inspection of an existing US-wired installation. In each case the safe move is to convert to mm2, then size by current, voltage drop and breaker using your local code.
The key rule: conversion is geometry only. Ampacity is a separate question answered by NEC 310.16 in the US or IEC 60364-5-52 and BS 7671 elsewhere. Never assume that equal mm2 means equal allowed current across codes, because temperature ratings and installation methods differ.
AWG to mm2 Conversion Chart
The table below lists the standard solid or stranded AWG conductor, its exact metric area, the nearest IEC nominal size, and diameter. Diameters are for the bare conductor without insulation. Stranded conductors have slightly larger overall diameter for the same copper area.
| AWG | Area mm2 | Nearest IEC size | Diameter mm | Typical use |
|---|---|---|---|---|
| 18 | 0.82 | 0.75 / 1.0 | 1.02 | Signal, thermostat, doorbell |
| 16 | 1.31 | 1.5 | 1.29 | Lighting control, small fixtures |
| 14 | 2.08 | 2.5 | 1.63 | Lighting, 15 A branch circuits |
| 12 | 3.31 | 4.0 | 2.05 | 20 A receptacles, kitchen small appliance |
| 10 | 5.26 | 6.0 | 2.59 | 30 A dryer, water heater |
| 8 | 8.37 | 10.0 | 3.26 | 40-50 A range, feeder |
| 6 | 13.3 | 16.0 | 4.11 | 55-65 A feeder, subpanel |
| 4 | 21.2 | 25.0 | 5.19 | 70-95 A feeder |
| 3 | 26.7 | 25 / 35 | 5.83 | Large feeder |
| 2 | 33.6 | 35.0 | 6.54 | 100 A service segment |
| 1 | 42.4 | 50.0 | 7.35 | Service entrance |
| 1/0 | 53.5 | 50 / 70 | 8.25 | 125-150 A service |
| 2/0 | 67.4 | 70.0 | 9.27 | 175 A service |
| 3/0 | 85.0 | 95.0 | 10.40 | 200 A service |
| 4/0 | 107.2 | 120.0 | 11.68 | 200-230 A service |
Note the mismatch: US sizes fall between IEC steps, so always round up to the next IEC size and recheck current and drop.
How the Math Works
AWG diameter follows a geometric progression. By definition, 36 AWG is 0.005 inch and 0000 (4/0) is 0.46 inch, with 39 steps between them and a ratio of about 1.1229 per step. The diameter formula is d = 0.005 inch x 92^((36-AWG)/39). Area is pi x d2 / 4.
Example for 12 AWG: d = 0.005 x 92^((36-12)/39) = 0.005 x 92^(24/39) = 0.0808 inch = 2.053 mm. Area = 3.1416 x 2.0532 / 4 = 3.31 mm2. For 10 AWG the same formula gives 2.588 mm diameter and 5.26 mm2. You do not need to memorize this, but it explains why the series is uneven and why interpolation between AWG sizes is wrong.
Ampacity by Size: NEC 310.16
Conversion tells you geometry. Ampacity tells you how much current the wire may carry continuously. NEC Table 310.16 gives three columns by insulation temperature. The termination temperature usually limits you to the 60 C or 75 C column even if the wire is rated 90 C.
| AWG copper | mm2 | 60 C A | 75 C A | 90 C A |
|---|---|---|---|---|
| 18 | 0.82 | 14* | 14* | 14 |
| 16 | 1.31 | 18* | 18* | 18 |
| 14 | 2.08 | 15 | 20 | 25 |
| 12 | 3.31 | 20 | 25 | 30 |
| 10 | 5.26 | 30 | 35 | 40 |
| 8 | 8.37 | 40 | 50 | 55 |
| 6 | 13.3 | 55 | 65 | 75 |
| 4 | 21.2 | 70 | 85 | 95 |
| 2 | 33.6 | 95 | 115 | 130 |
| 1/0 | 53.5 | 125 | 150 | 170 |
| 3/0 | 85.0 | 165 | 200 | 225 |
| 4/0 | 107.2 | 195 | 230 | 260 |
Asterisk means small-conductor rules cap 18 AWG at 7 A and 16 AWG at 10 A for most branch circuits under NEC 240.4(D), regardless of the table. Fourteen AWG is capped at 15 A and 12 AWG at 20 A for general branch circuits. Larger breakers are allowed only for specific loads such as motors or HVAC under their articles.
IEC values are close but not identical because the reference installation methods differ. For example IEC 60364-5-52 method C gives 2.5 mm2 copper about 24 to 27 A depending on conditions, while 14 AWG at 2.08 mm2 gives 15 to 25 A under NEC. Always apply the code of the country where the installation is inspected.
US vs IEC Practice
In the US, residential receptacle circuits are typically 12 AWG on a 20 A breaker and lighting on 14 AWG on a 15 A breaker, with cable types NM-B, THHN in conduit, or SER/SEU for feeders. Ground size follows NEC 250.122. Conduit fill follows Chapter 9 tables.
In IEC practice under IEC 60364 and BS 7671, lighting is commonly 1.5 mm2, receptacles 2.5 mm2 on 16 or 20 A, cookers 6 mm2 on 32 A, and feeders 10 to 35 mm2. Protective conductors follow IEC 60364-5-54. The design flow is the same: load current, correction factors, protective device, voltage drop, fault loop.
Substitution rule when you must replace: 14 AWG becomes 2.5 mm2, 12 AWG becomes 4.0 mm2, 10 AWG becomes 6.0 mm2, 8 AWG becomes 10 mm2, 6 AWG becomes 16 mm2. This keeps ampacity at or above the US value and keeps terminations compatible with metric lugs.
Worked Example: Sizing for 32 A
Given: single-phase 230 V load drawing 32 A continuous, copper, PVC insulation, clipped direct, ambient 30 C, no bundling. Find the minimum AWG and the IEC equivalent.
Step 1: try 10 AWG (5.26 mm2). NEC 310.16 at 75 C gives 35 A. Check small-conductor cap: 10 AWG is allowed 30 A for general branch circuits under 240.4(D), so a 30 A breaker is the maximum for a general circuit. For a 32 A load this fails at the breaker rule even though the table says 35 A.
Step 2: try 8 AWG (8.37 mm2). NEC 310.16 at 75 C gives 50 A, at 60 C gives 40 A. Both exceed 32 A. Breaker: next standard size 40 A per NEC 240.6. Cable Iz of 40 A at 60 C is greater than In of 40 A only if terminations are 75 C rated; safest is a 40 A breaker with 75 C terminations, or a 35 A breaker where available.
Step 3: voltage drop check for 25 m run, single phase. Delta-U percent = 2 x I x L x rho / (S x U) x 100. With rho 0.0175 ohm-mm2/m at operating temperature corrected to about 0.021: drop = 2 x 32 x 25 x 0.021 / (8.37 x 230) x 100 = 33.6 / 1925.1 x 100 = 1.75 percent. Limit is 3 percent for lighting and 5 percent for other uses per IEC 60364-5-52 and good US practice. Passes.
Result: use 8 AWG copper on a 40 A breaker with 75 C terminations, or in metric 10 mm2 copper on a 40 A breaker. If the load is continuous at full 32 A for 3 hours or more, apply the 125 percent rule from NEC 210.19(A): 32 x 1.25 = 40 A design current, which confirms the same 8 AWG / 10 mm2 choice.
Mini Case: Garage Subfeed
A 30 m garage feeder must carry 48 A calculated load, copper THHN in conduit, three current-carrying conductors, ambient 38 C. Base choice from NEC 310.16 75 C column is 8 AWG at 50 A, but two corrections apply: temperature factor 0.91 at 38 C and bundling factor 0.80 for 4 to 6 conductors. Derated ampacity = 50 x 0.91 x 0.80 = 36.4 A. Fails.
Next size 6 AWG gives 47.3 A, still below 48 A. Use 4 AWG copper (21.2 mm2, metric 25 mm2) at 61.9 A with a 60 A breaker and ground per NEC 250.122.
Assumptions and When This Does Not Apply
Charts in this article assume copper conductors, not aluminum. They assume not more than three current-carrying conductors in a raceway and 30 C ambient unless corrections are applied. They assume terminations rated to match the column you use. They do not apply to motors, welders, HVAC or PV source circuits, which have their own NEC articles with different sizing rules. They also do not replace short-circuit and ground-fault checks.
Common Mistakes
First, reading AWG backwards: 14 is thinner than 12. Second, using the 90 C column with 60 C receptacles. Third, ignoring the 15 and 20 A small-conductor caps. Fourth, converting AWG to mm2 and keeping the same breaker without rechecking ampacity under the local code. Fifth, forgetting voltage drop on long runs: a wire that passes thermally at 10 m can fail drop at 40 m.
Checklist before you buy: load current with demand, insulation and termination temperature, ambient and bundling corrections, breaker rule including 125 percent for continuous loads, voltage drop under 3 to 5 percent, ground size, conduit fill.
Frequently Asked Questions
See the five questions and answers in the FAQ section. They cover 12 AWG vs 2.5 mm2, the 32 A choice, aluminum AWG, and 4/0 service use.
Related reading on this site: wire ampacity chart explained, breaker sizing from load to wire, voltage drop over distance. Open the free demo at https://gorkycad.com/cad/?demo=1 to draw the circuit, assign the cable size you calculated, and export a single-line diagram with a panel schedule.
Try it on your own plan: open the free demo at https://gorkycad.com/cad/?demo=1 and build the circuit in minutes.
Frequently asked questions
Is 12 AWG the same as 2.5 mm2?
No. 12 AWG is 3.31 mm2, about 32 percent larger than 2.5 mm2. For the same function use 4.0 mm2 metric as the safe substitute, then recheck ampacity and voltage drop.
What AWG do I need for 32 A?
8 AWG copper (8.37 mm2, metric 10 mm2) on a 40 A breaker with 75 C terminations. 10 AWG is capped at 30 A for general branch circuits, so it cannot carry a 32 A load.
Does AWG apply to aluminum too?
Yes, the gauge defines area regardless of metal, but ampacity is lower: 12 AWG aluminum is only 15 A at 75 C versus 25 A copper. Terminations must be rated CO-ALR or dual-rated.
What is 4/0 AWG in mm2?
107.2 mm2, roughly between 95 and 120 mm2 metric. At 75 C copper it carries 230 A and is a standard 200 A residential service conductor.
Can I use the 90 C column directly?
Only if every termination and device in the circuit is rated 90 C. Most breakers and receptacles are 60 C or 75 C, so the 90 C value is used mainly for derating math.