Contactors and relays both switch circuits with a coil — but they live in different worlds. A contactor is a heavy switch built for thousands of amps of motor starting current and millions of operations; a relay is a light signal switch for control logic, alarms, and small loads. Using a relay where a contactor belongs welds the contacts within weeks; using a contactor where a relay belongs wastes a DIN rail and the budget.
This guide compares them by utilization category, endurance, and size, works the selection for a 7.5 kW motor, and shows the standard starter schematic with overload protection. Categories follow IEC 60947-4-1 / 60947-5-1.
1. The One-Sentence Difference
A contactor switches power circuits: motors, heaters, lighting banks — amps to hundreds of amps, with arc chutes and replaceable contacts. A relay switches control circuits: coils, lamps, PLC inputs — milliamps to about 10 A, sealed and compact. If the load draws motor starting current, it is a contactor job, full stop.
2. Comparison Table
| Feature | Contactor (e.g. 9–32 A frame) | Relay (e.g. miniature / interface) |
|---|---|---|
| Typical current | 9–800 A | 0.1–10 A |
| Utilization categories | AC-1 (resistive), AC-3 (motor), AC-4 (plugging) | AC-15 (control AC), DC-13 (control DC) |
| Electrical endurance | 1–2 million ops (AC-3) | 100k–500k ops at rated load |
| Motor switching | Yes, with overload relay | No — welds on inrush |
| Size per pole | 1 DIN module+ per pole path | 6–15 mm slice |
| Replaceable contacts/coils | Often yes | Plug-in, replace whole unit |
AC-3 is the motor category that matters: making and breaking locked-rotor current. AC-1 covers heaters and lighting where current equals running current. Never size a motor starter from the AC-1 column.
3. AC-1 vs AC-3: Why the Same Box Has Two Ratings
A contactor marked "32 A AC-1 / 18 A AC-3" is not two products — it is two duties. AC-1 (cos φ ≥ 0.95) means switching current equals breaking current: easy arcing. AC-3 (squirrel-cage motor) means making about 6× rated current and breaking rated current with an inductive arc: hard duty, hence the lower number. A 7.5 kW motor at 15 A needs the AC-3 rating above 15 A, not the AC-1 rating.
4. Worked Selection: 7.5 kW Motor, 400 V
Given: 7.5 kW, 400 V three-phase, cos φ 0.85, efficiency 0.89. Full-load current: I = P / (√3 × U × cos φ × η) = 7,500 / (1.732 × 400 × 0.85 × 0.89) = 7,500 / 524.2 = 14.3 A. Starting current direct-on-line ≈ 6 × 14.3 ≈ 86 A for a few seconds.
Selection: contactor with AC-3 rating ≥ 14.3 A → 18 A frame (next standard above, e.g. 18 A AC-3 / 32 A AC-1); thermal overload relay set to 14.3 A (adjustable 13–18 A range); upstream breaker 25 A C or motor-protection breaker 14–20 A range. The 9 A contactor "almost fits" — it does not: it would switch 86 A starts on an 9 A AC-3 device and weld within months.
5. Lighting Loads: When Contactors Earn Their Keep
LED high-bay and street lighting banks draw high inrush (capacitor charging, up to 100× for microseconds, specified as Ipeak and pulse width). A relay rated 10 A resistive can weld on a 3 A LED circuit because of that inrush. Lighting contactors (often AC-1/AC-5 rated with inrush data) or inrush limiters solve it: size from the driver's peak current and the number of drivers per pole, not from steady watts.
Rule: above about 2–3 kW of LED on one switch, or any high-bay row, use a contactor with published LED ratings; below that, a quality relay or smart switch with inrush data suffices.
6. Standard Schematic: Contactor + Thermal Overload
Power path: breaker → contactor main poles (L1/L2/L3) → thermal overload relay → motor terminals U/V/W, with PE continuous to the frame. Control path: start button (NO) in parallel with the contactor auxiliary NO contact for latching, stop button (NC) in series, overload NC trip contact in series with the coil, coil returned to neutral. Pressing start energizes the coil, the auxiliary seals it in, pressing stop or an overload trip drops it out.
The overload relay is thermal (or electronic EOLR): it integrates I²t and trips on sustained overcurrent while tolerating the seconds-long start. It does not protect against short circuits — that is the breaker's job. Coordination type 1 vs 2 (whether the contactor survives a short) is selected from the manufacturer's tables.
7. Mini-Case: The Relay That Welded Every Month
A ventilation fan (4 kW, ~8.5 A) was switched by a 10 A interface relay driven from a timer. Every 4–6 weeks the fan "wouldn't stop" — the relay contacts had welded on starting inrush (~50 A). The fix kept the timer and relay for control but added an 12 A AC-3 contactor for power: the relay now switches only the 0.2 A contactor coil, the contactor switches the motor. No welding in two years; the contactor's electrical life at this load exceeds a million operations.
8. Endurance and Maintenance Reality
AC-3 endurance curves derate fast with current: a contactor rated 1.5 million operations at rated current may manage only 200,000 at 1.5× current. Count operations where it matters (hourly HVAC cycling adds up: 24 starts/day × 365 = 8,760/year — fine; a packaging machine at 600/hour needs a solid-state or oversized device). Keep spare contact tips or a spare contactor for critical motors; relays are throwaway plug-ins.
9. Solid-State and Smart Alternatives
Solid-state contactors (SSRs) switch silently with no wear — right for high-cycle heaters and lighting — but they leak, drop 1–1.5 V (heat!), and fail shorted, so they need heatsinks and a series disconnect. Soft starters and VFDs replace the whole starter where starting current or speed control matters. None of these remove the need for isolation and short-circuit protection upstream.
10. Assumptions / When This Doesn't Apply
This selection logic assumes standard 400 V / 50 Hz squirrel-cage motors with direct-on-line or star-delta starting. Adjust when: (1) star-delta or soft starter is used — size from the reduced starting current and the starter vendor's tables; (2) the load is DC — DC breaking is harsher, use DC-rated devices; (3) safety switching (emergency stop) applies — safety contactors with mirror contacts and monitored feedback are mandatory; (4) explosive atmospheres apply — Ex-rated gear only; (5) switching exceeds ~1 million operations/year — go solid-state or oversize two frames.
11. Checklist: Specifying a Starter in 60 Seconds
Motor kW, voltage, full-load amps (calculate, don't guess); starting method (DOL × 6, star-delta × 2, soft starter per curve); contactor AC-3 rating above full-load amps; overload range covering the exact amps; breaker from coordination tables; enclosure size with heat dissipation; auxiliary contacts for control logic. Write all seven on the inquiry and the panel builder cannot misinterpret it.
12. From Starter to Panel Documentation
Every starter belongs on the single-line diagram with its designation, rating, and overload setting, and in the equipment schedule with the motor it serves. When the motor is replaced with a bigger one in five years, the file tells the next engineer exactly which contactor and overload to recheck — instead of discovering welded contacts the hard way.
Appendix: Contactor Frames for Common Motor Sizes (400 V)
The table below covers the motors found in most small plants. Full-load currents assume cos φ 0.85 and efficiency 0.89; always recalculate from the motor nameplate when it differs. Pick the AC-3 frame at or above full-load current, then the overload range that brackets it — never the reverse.
| Motor | Full-load current | Contactor AC-3 | Overload range | Breaker (guide) |
|---|---|---|---|---|
| 4.0 kW | 8.2 A | 9 A | 7–10 A | 16 A |
| 5.5 kW | 11.2 A | 12 A | 9–13 A | 20 A |
| 7.5 kW | 14.3 A | 18 A | 13–18 A | 25 A |
| 11 kW | 21.0 A | 25 A | 17–25 A | 32 A |
| 15 kW | 28.6 A | 32 A | 23–32 A | 40 A |
Three specification mistakes repeat across projects. First, copying the AC-1 rating into the motor column of the schedule — the 32 A AC-1 / 18 A AC-3 device gets ordered as "32 A" and fails on motors. Second, setting the overload to the breaker rating instead of the motor amps — the motor then cooks at 115 % while the dial says "protected." Third, forgetting auxiliary contacts: one NO for the seal-in plus one spare NO/NC for signaling costs nothing at order time and a new contactor when forgotten.
Draw the starter circuit once and let the schedule fill itself: https://gorkycad.com/cad/?demo=1&lang=en — free demo with motor-circuit checks built in.
Draw the motor circuit once and get protection right: open the free demo at https://gorkycad.com/cad/?demo=1&lang=en — starters, overloads, and cable sizing with automatic checks.
Frequently asked questions
Can I switch a 7.5 kW motor with a 16 A relay?
No. A 7.5 kW / 400 V motor draws about 14.3 A running and ~86 A starting. You need an 18 A AC-3 contactor plus a thermal overload set to 14.3 A. A relay will weld on the starting inrush.
What is the difference between AC-1 and AC-3?
AC-1 is resistive duty (heaters, lighting banks): making current equals running current. AC-3 is motor duty: making ~6× rated current with an inductive arc. Always use the AC-3 column for motors.
Do I need an overload relay if I have a circuit breaker?
Yes — they do different jobs. The breaker clears short circuits in milliseconds; the thermal overload tolerates the motor start and trips on sustained overload. A starter has both.
Why did my lighting relay weld on a small LED load?
LED drivers draw huge inrush (tens of amps for microseconds) even on a 3 A circuit. Use a contactor with published LED ratings or an inrush limiter above ~2–3 kW of LED per switch.
Contactor vs soft starter vs VFD — which one?
Contactor: simple on/off at full inrush. Soft starter: reduced starting current, same speed. VFD: speed control and soft start. Protection and isolation are still required upstream in all three cases.