A motor that runs at 12 A can draw 80 A for the first second. Size the breaker for the run and it trips on every start; size it for the start and the cable cooks during a stall. The fix is matching the starting method — direct-on-line, star-delta, or soft starter — to the right trip curve and thermal protection. This guide covers NEC Article 430 practice with worked numbers.
Why starting current is 6–8× running current
At standstill the rotor looks like a shorted secondary, so locked-rotor current is limited only by winding impedance — typically 6–8 times full-load current (FLA) for standard induction motors, lasting 0.5–5 s depending on load inertia. A 7.5 kW 400 V motor draws about 15 A running but 90–120 A during a direct start. Protection must ride through this transient yet still trip fast on a genuine short circuit — that tension is the entire art of motor branch-circuit design. How to use this guide: find your motor in the table, note the DOL and star-delta columns, then follow the worked pump example with your own FLA and starting time. Keep it nearby when ordering breakers, contactors, and overload relays. The tables plus the pump example answer nine out of ten motor-circuit questions without another reference.
Motor full-load currents and starting multiples
Representative 400 V three-phase values (verify against the motor nameplate and NEC Table 430.250). Starting multiple assumes direct-on-line; star-delta and soft starters reduce it (next section).
| Motor (400 V 3-ph) | FLA ≈ (A) | DOL start ≈ (A) | Star-delta ≈ (A) |
|---|---|---|---|
| 2.2 kW | 5.0 | 30–40 | 10–13 |
| 4.0 kW | 8.5 | 51–68 | 17–23 |
| 5.5 kW | 11.5 | 69–92 | 23–31 |
| 7.5 kW | 15.5 | 93–124 | 31–41 |
| 11 kW | 22.0 | 132–176 | 44–59 |
| 15 kW | 30.0 | 180–240 | 60–80 |
| 22 kW | 43.0 | 258–344 | 86–115 |
| 30 kW | 58.0 | 348–464 | 116–155 |
DOL vs star-delta vs soft starter
Direct-on-line (DOL) applies full voltage instantly: cheapest, harshest — full 6–8× inrush and mechanical shock. Good to about 5.5–7.5 kW on stiff supplies. Star-delta starts in star (voltage ÷ √3, current ≈ ⅓ of DOL, torque ≈ ⅓) then switches to delta: cheap reduced-voltage starting for unloaded starts (fans, pumps, unloaded conveyors). Soft starters and VFDs ramp voltage/frequency: adjustable current limit (typically 3–4×), smooth torque, the right answer for loaded starts and frequent cycling. Never use star-delta on a loaded start — the motor stalls at the star-to-delta transition and draws DOL current anyway.
Trip curves C vs D: which one and why
MCB curves define the magnetic (instantaneous) band: B 3–5×, C 5–10×, D 10–20× of rated current per IEC 60898 / GOST R 50345 equivalents referenced in IEC 60364. DOL motors need D-curve (or motor-protection breakers with adjustable magnetic pickup) so the 6–8× start stays below the magnetic threshold with margin. Control and lighting circuits stay on B/C. A C16 on a 15 A DOL motor (magnetic band 80–160 A vs start 93–124 A) is a coin toss — that is why it «sometimes trips». Change to D16 (160–320 A band) and the start clears reliably while short circuits still trip instantly.
Quick selector for protective devices on motor circuits:
| Device | Magnetic band / setting | Use it for |
|---|---|---|
| B-curve MCB | 3–5x In | Control circuits, lighting |
| C-curve MCB | 5–10x In | Star-delta starts, small DOL to 4 kW |
| D-curve MCB | 10–20x In | DOL motors above 4 kW |
| Motor-protection breaker | Adjustable 6–14x + thermal | Any motor, precise coordination |
| Overload relay | Set to nameplate FLA | Overload and phase-loss duty |
Thermal overload relay: the part breakers can't do
Breakers protect cables against short circuits; the thermal overload relay protects the motor against sustained overcurrent (overload, phase loss, stalled rotor). Set it to motor FLA from the nameplate (NEC 430.32: typically 115–125% of FLA depending on service factor), class 10 for normal starts, class 20–30 for long run-ups. Size contactor to AC-3 duty at the motor current. A breaker alone — even D-curve — will not save a motor running at 130% current for twenty minutes; the overload relay will.
Worked example: 11 kW pump, DOL vs star-delta
Given: 11 kW, 400 V, FLA 22 A, DOL start 6.5× = 143 A for ~2 s. DOL option: cable 3×4 mm² (Iz ≈ 32 A in conduit at 30 °C — verify with ampacity and derating), D25 breaker (magnetic 250–500 A clears the 143 A start), overload relay set to 22 A. Star-delta option: start ≈ 48 A — a C25 (125–250 A band) now clears it, cable stays 3×4 mm², plus three contactors and a timer. Verdict: DOL with D-curve is cheaper here; star-delta wins above ~15 kW or on weak supplies where 143 A sags the whole shop. Always confirm voltage drop during start stays within utility limits.
Short-circuit rating and cable check
Check two numbers after selecting the breaker: (1) breaking capacity (kA rating) ≥ prospective fault current at the motor terminals — see kA ratings explained; (2) cable thermal withstand I²t within the let-through of the device per IEC 60364-4-43. Long submain runs to remote motors often fail on voltage drop before ampacity — upsize copper for drop, not just heat.
Assumptions / when this doesn't apply
This guide assumes: (1) standard 50/60 Hz induction motors — synchronous, DC, and servo motors follow drive-vendor rules; (2) nameplate FLA known — never size from kW alone when the plate gives amps; (3) starting time under ~5 s — crushers, centrifuges, and large fans need engineered starting studies; (4) supply stiff enough that DOL sag is acceptable — islanded generators often force soft starters; (5) overload relay present — without it, no breaker curve makes the motor safe. When an assumption fails, stop and engineer it properly: long run-up times need a starting study, weak supplies need measured sag during start, and missing nameplates need a clamp-meter reading before any breaker is ordered. Guessing the FLA is how motors burn out in the first month.
Mini case: the compressor that tripped every Monday
A 7.5 kW compressor on C16 tripped on cold Monday starts but ran fine warm. Measurements: run 15.2 A, cold start 118 A for 1.8 s — inside the C-curve magnetic band (80–160 A). Fix: D16 breaker (160–320 A band), cable verified 3×2.5 mm² adequate for 15.5 A with derating, overload relay confirmed at 15.5 A class 10. Result: zero trips in six months, no cable change, one breaker swap. Cost of diagnosis: one clamp-meter reading during a start. Second scenario: the same pump on a 150 m rural overhead line with 8 percent sag during start. Measured start current rises slightly while torque drops with the square of voltage, so run-up stretches from 2 s to 6 s and the class 10 relay trips on a warm day. Fix: class 20 overload relay giving the longer start time headroom, plus a soft starter limited to 3.5 times FLA. The breaker stays D25; only the starting profile and the thermal class change, and the pump now starts even at evening voltage dip.
Common mistakes
First, C-curve on DOL motors above ~4 kW. Second, no overload relay («the breaker will protect it» — it won't). Third, star-delta on loaded starts. Fourth, sizing cable to FLA without derating for a hot plant room full of bundled conduits. Fifth, ignoring the feeder total — six DOL motors starting together need sequencing or a bigger service, not six bigger breakers.
Contactor sizing and control basics
Size the contactor to AC-3 duty at full-load current with margin: a 22 A motor wants a 25 A or 32 A AC-3 contactor for frequent starts, never an exactly-at-the-limit unit. Coil voltage follows the control scheme (230 V common, 24 V safest in wet locations). Add overload auxiliary contacts for trip signaling, a start/stop station with seal-in contact, and emergency stop where machinery rules require. For star-delta add three contactors plus a timer with a short pause at changeover; overlapping star and delta contactors is a phase-to-phase short, so mechanical plus electrical interlocking is mandatory on every starter. Test the starter quarterly: measure coil pickup voltage, check contact wear through the inspection window, verify the timer actually transfers under load, and confirm the overload test-trip button opens the contactor. Ten minutes with a meter beats a midnight emergency callout every single time, starting today.
Power factor and demand notes for feeders
Large lightly loaded motors run at poor power factor (0.6 to 0.75), inflating feeder current without doing work. Correcting with capacitors at the motor control center trims feeder amps and utility penalties, but never oversize capacitors on VFD-fed motors since the drive handles displacement itself. Soft starters cut inrush demand charges where utilities bill peaks: shaving a 300 A start to 120 A can move a site into a lower bracket. Log running current, starts per hour, and winding temperature for the first month; those three trends predict failures months ahead.
Try it now: sketch your panel or installation in the free GorkyCAD demo — it computes currents, suggests breaker sizes, and builds a single-line diagram in minutes.
Test your motor circuit in the free GorkyCAD demo at https://gorkycad.com/cad/?demo=1 — FLA, starting current, curve selection, and cable check on one page.
Frequently asked questions
How many times FLA is motor starting current?
Typically 6–8× full-load current for direct-on-line induction motors, lasting 0.5–5 s. Star-delta cuts it to about one-third; soft starters limit it to roughly 3–4×.
When do I need a D-curve breaker for a motor?
For direct-on-line starts where 6–8× FLA would enter a C-curve magnetic band (5–10×). D-curve (10–20×) rides through the start while still tripping instantly on short circuits.
Can I use star-delta for any motor?
Only for unloaded or lightly loaded starts (fans, pumps, unloaded conveyors). Star gives one-third torque — a loaded motor stalls at changeover and draws DOL current anyway.
What sets motor overload protection?
The thermal overload relay, set to nameplate FLA (NEC 430.32: typically 115–125% depending on service factor). Breakers protect cables; the relay protects the motor.
What cable do I need for an 11 kW 400 V motor?
FLA ≈ 22 A, so 3×4 mm² copper in conduit is the usual answer after derating — then verify voltage drop and short-circuit rating for the actual run length.