Copper costs more per meter than aluminum, yet aluminum needs a larger size for the same current and far more care at terminations. Choose wrong and you get hot lugs, flicker, or a failed inspection. Choose right and aluminum can save serious money on long feeders without sacrificing safety.

This guide compares copper and aluminum with real ampacity numbers from NEC Table 310.16, explains the 61 percent conductivity rule, covers oxidation and connection rules, and shows when aluminum is justified. References: NEC 310.16, NEC 110.14, NEC 250.122, IEC 60364-4-43 and BS 7671 context where noted.

The One Number That Explains Everything

Aluminum has about 61 percent of the conductivity of copper for the same cross-section. In practice that means you go up roughly two AWG steps or one to two IEC steps to carry the same current. A 20 A copper branch in 12 AWG becomes 10 AWG aluminum. A 100 A copper feeder in 2 AWG becomes 1/0 aluminum.

Weight and price work the other way. Aluminum is about one third the density of copper, so even a larger aluminum conductor is lighter. On feeders above 30 to 50 A and runs longer than 20 to 30 m, aluminum is often 30 to 60 percent cheaper installed, depending on the market. On short branch circuits the saving is small and rarely worth the extra care.

Memorize this: copper wins on small circuits and tight spaces, aluminum wins on big, long feeders installed correctly.

Ampacity Side by Side: NEC 310.16

Values below are 75 C column, three or fewer conductors, 30 C ambient. Small-conductor caps from NEC 240.4(D) still apply to copper 14/12/10 AWG.

CopperCu 75 CAluminum equivalentAl 75 CMetric pair
14 AWG 2.08 mm220 A*12 AWG 3.31 mm220 A*2.5 Cu vs 4.0 Al
12 AWG 3.31 mm225 A*10 AWG 5.26 mm225 A*4.0 Cu vs 6.0 Al
10 AWG 5.26 mm235 A*8 AWG 8.37 mm240 A*6.0 Cu vs 10 Al
8 AWG 8.37 mm250 A6 AWG 13.3 mm250 A10 Cu vs 16 Al
6 AWG 13.3 mm265 A4 AWG 21.2 mm265 A16 Cu vs 25 Al
4 AWG 21.2 mm285 A2 AWG 33.6 mm290 A25 Cu vs 35 Al
2 AWG 33.6 mm2115 A1/0 AWG 53.5 mm2120 A35 Cu vs 50/70 Al
1/0 AWG 53.5 mm2150 A3/0 AWG 85 mm2155 A50 Cu vs 95 Al

Star means capped at 15, 20 and 30 A for general branch circuits. The table shows the core pattern: aluminum needs roughly 1.6 times the copper area. In metric terms IEC 60364-5-52 gives a similar ratio: 16 mm2 copper and 25 mm2 aluminum are the classic feeder pair, as are 25 mm2 copper and 35 mm2 aluminum.

Cost Math With Real Proportions

Take a 40 m, 60 A single-phase feeder in conduit. Option A: 6 AWG copper (13.3 mm2) at 75 C = 65 A. Option B: 4 AWG aluminum (21.2 mm2) at 75 C = 65 A. Both pass thermally before corrections.

Material: copper 6 AWG uses about 0.119 kg per meter per conductor, two conductors plus ground over 40 m is roughly 12 to 14 kg of copper. Aluminum 4 AWG uses about 0.057 kg per meter per conductor, total under 6 kg. Even before labor, aluminum material is typically half the price or less on this size. Conduit size may grow one step for aluminum, which eats a small part of the saving.

Labor is nearly identical if terminations are done right. The saving disappears on short runs: a 10 m, 20 A branch saves only a few dollars with aluminum but adds termination risk. Rule of thumb: consider aluminum from 6 AWG / 16 mm2 upward and runs above 20 m.

Connections and Oxidation: Where Fires Start

Aluminum forms a hard oxide layer within minutes in air. The oxide is an insulator. Old 1960s failures came from plain steel screws, no antioxidant, and metals that expand differently with heat. Modern practice fixes all three: dual-rated AL9CU or CO-ALR devices, antioxidant compound where the maker requires it, correct torque with a torque screwdriver, and no mixing of metals without a listed connector.

NEC 110.14 requires terminals to be identified for the conductor material. If the lug says CU only, aluminum is a code violation. If it says AL7CU or AL9CU, both metals are allowed within the temperature rating. Torque to the labeled value per NEC 110.14(D). Re-torque is not a maintenance plan; a correctly torqued, listed connection does not need periodic tightening.

Never land aluminum directly under a device screw made only for copper. Never nick aluminum when stripping, because a nick becomes a hot spot. Never use push-in backstabs with aluminum. In damp locations prefer tin-plated lugs and keep antioxidant in the joint per maker instructions.

When Aluminum Is Justified

Service entrances: 200 A in 4/0 aluminum instead of 2/0 copper is standard US practice and explicitly covered by NEC 310.16. Feeders to subpanels, garages, workshops and outbuildings: 60 to 100 A aluminum feeders save the most money. Long underground runs where conduit upsizing is cheap relative to copper savings.

Overhead drops and large commercial feeders are aluminum by default: the weight saving dominates. Utility conductors are almost all aluminum for the same reason. In IEC countries, aluminum is common from 16 mm2 upward for distribution, while final branch circuits stay copper.

When Copper Is Non-Negotiable

Branch circuits 15 and 20 A in homes: copper 14 and 12 AWG. Small boxes where a larger aluminum conductor will not fit or will stress the device. Control, signal and electronics wiring. Any termination not listed for aluminum. Short runs where the saving is under 10 percent. Vibration or frequent flexing, where copper fatigue life is far better.

Also choose copper where future additions are likely: a copper 100 A subpanel feeder leaves more spare conduit fill than the aluminum equivalent for later upsizing.

Worked Calculation: 60 A Garage Feeder

Given: 230 V single-phase, calculated load 54 A, 35 m in PVC conduit, three current-carrying conductors, ambient 35 C, copper vs aluminum decision. Correction factors: temperature 0.94 at 35 C for 75 C column, bundling 0.80 for 4 to 6 conductors per NEC Table 310.15(C)(1).

Copper try 6 AWG base 65 A: derated = 65 x 0.94 x 0.80 = 48.9 A. Fails against 54 A. Next 4 AWG base 85 A: 85 x 0.94 x 0.80 = 63.9 A. Passes. Breaker 60 A, ground 10 AWG copper per NEC 250.122 for 60 A protection.

Aluminum try 4 AWG base 65 A: 65 x 0.94 x 0.80 = 48.9 A. Fails. Next 3 AWG base 75 A: 75 x 0.94 x 0.80 = 56.4 A. Passes. Next standard breaker 60 A. Ground 8 AWG aluminum or 10 AWG copper per 250.122. Both designs work; aluminum saves material cost at the price of one larger conduit size and stricter termination discipline.

Voltage drop check for the aluminum choice, 35 m, 54 A, 26.7 mm2: drop percent = 2 x 54 x 35 x 0.028 / (26.7 x 230) x 100 with aluminum rho about 0.028. Numerator 105840, denominator 6141, result 1.72 percent. Passes the 5 percent feeder guideline.

Ground Size Follows the Breaker

Equipment ground size comes from NEC 250.122 based on the overcurrent device, not the phase conductor metal. A 60 A feeder needs 10 AWG copper ground whether the phases are 6 AWG copper or 4 AWG aluminum. For 100 A use 8 AWG copper, for 125 A use 6 AWG copper, for 200 A use 6 AWG copper or 4 AWG aluminum. When you upsize phases for voltage drop, upsize the ground proportionally per NEC 250.122(B). At a detached building the feeder ground and the local electrodes work together: the feeder ground clears faults back to the source while rods stabilize voltage and handle lightning energy.

Feeder breakerGround copperGround aluminum
30 A10 AWG8 AWG
60 A10 AWG8 AWG
100 A8 AWG6 AWG
200 A6 AWG4 AWG

Mini Case: 100 A House Feeder

A 28 m feeder must carry 88 A after demand. Copper 2 AWG at 115 A passes directly with a 100 A breaker. Aluminum needs 1/0 AWG at 120 A with a 100 A breaker. The aluminum feeder costs roughly 40 percent less in material, needs 1-1/4 inch instead of 1 inch conduit, and lands on 100 A dual-rated lugs torqued to 50 lbf-in. Inspection passes because every termination is AL-rated and torqued. The homeowner never sees a difference in use.

Assumptions and When This Does Not Apply

This comparison assumes 75 C terminations, not more than three current-carrying conductors before corrections, and dry indoor or conduit installation. It does not apply to flexible cords, appliance whips with maker-supplied leads, or fire-rated circuits with mineral insulation. It does not override motor, HVAC or PV articles that size conductors differently. Local amendments may ban aluminum below a threshold such as 25 mm2 or No. 6 AWG.

Common Mistakes

Putting aluminum on CU-only devices is the classic violation. Skipping antioxidant where required, under-torquing, and reusing old twist connectors not listed for aluminum are next. Sizing aluminum by the copper row of the table guarantees an undersized conductor. Forgetting that the ground also changes size per NEC 250.122 leaves an undersized equipment ground. Buried aluminum needs insulation and jacket rated for the location; bare aluminum has restricted uses.

Before you buy: confirm every lug is AL-rated, confirm torque values, confirm conduit fill with the larger size, confirm ground size, and confirm the local code allows aluminum at that size.

Frequently Asked Questions

Answers cover the 61 percent rule, antioxidant, mixing metals, and service sizes. Related reading: wire ampacity chart, conduit fill, breaker sizing. Try the layout in the free demo at https://gorkycad.com/cad/?demo=1.

Size the feeder in the free demo: https://gorkycad.com/cad/?demo=1 — draw the run, set copper or aluminum, and export the schedule.

Frequently asked questions

Is aluminum wire safe?

Yes when installed to code: AL-rated terminations, correct torque, antioxidant where required, and proper size from NEC 310.16. Most 1960s failures came from CU-only devices and untorqued joints, both now code violations.

How much larger must aluminum be?

About 1.6 times the copper area, or roughly two AWG steps. Examples: 12 AWG Cu pairs with 10 AWG Al, 6 AWG Cu with 4 AWG Al, 2 AWG Cu with 1/0 Al.

Do I need antioxidant paste?

Follow the connector maker. Most modern AL-rated lugs for building wire either include it or require it. Even when optional, it is cheap insurance on aluminum terminations.

Can I join copper and aluminum?

Only with a connector listed for both metals, such as an AL9CU lug or an approved twist connector with compound. Direct copper-to-aluminum contact under one screw is not allowed.

What size aluminum for 100 A?

1/0 AWG aluminum (53.5 mm2, metric 50 to 70 mm2) at 75 C carries 120 A and lands on a 100 A breaker. Copper equivalent is 2 AWG at 115 A.