An EV charger is the biggest single load most homes ever add. A 7.4 kW charger pulls as much as an electric shower, and a 22 kW charger pulls as much as a small apartment block connection. Size the circuit wrong and you get nuisance tripping at best and overheated cable at worst.

This guide gives you the three standard sizes — 7.4 kW, 11 kW and 22 kW — with the exact breaker, wire size and RCD type for each, plus the load math that tells you whether your panel can take it. All calculations follow NEC continuous-load rules and IEC 60364-4-41 for protection.

1. The short answer: breaker and wire by charger size

If you only need the numbers, here they are. The rest of the article shows where each number comes from and what to check before you buy cable. Current is calculated at 230/400 V with unity power factor, and the breaker follows the 125% continuous-load rule (NEC 210.20(A)).

ChargerSupplyCurrentBreakerCopper wire (Cu)RCD
7.4 kW1-phase 230 V32.2 A40 A, 2P3x6 sq mm (up to 30 m)Type A 40 A 30 mA or Type B
11 kW3-phase 400 V15.9 A20 A, 4P (3P+N)5x4 sq mmType A 4P 30 mA
22 kW3-phase 400 V31.8 A40 A, 4P (3P+N)5x6 sq mm (5x10 over 35 m)Type A 4P 30 mA or Type B

These are minimums for copper cable in conduit or wall at 30 C ambient. Long runs, hot garages, grouped cables or aluminium conductors all push you one size up. Voltage drop must stay within 5% total (NEC 210.19(A) informational note; IEC 60364-5-52).

2. Why an EV charger is a continuous load

NEC Article 100 defines a continuous load as one where the maximum current continues for 3 hours or more. An EV charges for 4 to 10 hours at full current, so it is the textbook example. NEC 210.20(A) requires the breaker to be rated at least 125% of a continuous load, and NEC 210.19(A) applies the same 125% factor to conductor sizing before derating.

That single rule explains the whole table. A 32 A charger needs conductors and a breaker rated for 32 x 1.25 = 40 A minimum. If you size the breaker at exactly the charger current, it will run at 100% for hours, heat up, and eventually trip — not a fault, just physics of thermal breakers.

3. 7.4 kW single-phase: the full calculation

Most homes have single-phase 230 V service, so 7.4 kW is the maximum practical home charger without a service upgrade. Given: P = 7400 W, U = 230 V, power factor = 1.0 (onboard charger is resistive for sizing purposes).

I = P / U = 7400 / 230 = 32.2 A. Continuous rating needed: 32.2 x 1.25 = 40.25 A. So the breaker is 40 A (2-pole for line plus neutral). Conductor: 6 sq mm copper carries 41 A in conduit (NEC Table 310.16, 75 C column) or 32 A buried — check your method, but 6 sq mm is the standard answer up to about 30 m. At 45 m the drop is (2 x 45 x 32.2 x 0.0034) / 230 = 4.3%, still inside 5% but close, so consider 10 sq mm beyond 40 m.

4. 11 kW three-phase: the full calculation

Given: P = 11000 W, U = 400 V line-to-line, cos phi = 1.0. I = P / (sqrt(3) x U) = 11000 / (1.732 x 400) = 11000 / 692.8 = 15.9 A per phase. Continuous rating: 15.9 x 1.25 = 19.9 A, so a 20 A four-pole breaker is exact.

Conductor: 4 sq mm copper (5 conductors: L1/L2/L3/N/PE) carries 32 A in conduit per NEC 310.16 adjusted for three current-carrying conductors, comfortably above 20 A with headroom for grouping and temperature. This is why 11 kW is popular in Europe: modest current, thin cable, easy on the panel. Check that your service is actually three-phase — many US/UK homes are single-phase and cannot use this charger without a supply upgrade.

5. 22 kW three-phase: the full calculation

Given: P = 22000 W, U = 400 V. I = 22000 / 692.8 = 31.8 A per phase. Continuous rating: 31.8 x 1.25 = 39.7 A, so a 40 A four-pole breaker. Conductor: 5x6 sq mm copper minimum; beyond 35 m step to 5x10 sq mm for voltage drop.

Drop check on 40 m of 6 sq mm: per-phase drop = sqrt(3) x I x L x (R cos + X sin) / 1000. With R = 3.3 ohm/km and X = 0.08: dU = 1.732 x 31.8 x 40 x 3.3 / 1000 = 7.27 V, which is 1.8% of 400 V — fine. On single long runs past 50 m, do the full calculation with reactance and temperature correction (see our voltage drop guide). Also confirm the car accepts 22 kW AC: many cars limit AC charging to 11 kW, in which case a 22 kW wallbox buys you nothing.

6. Breaker, wire and disconnect: what to buy

Buy a dedicated circuit: no other loads on the EV breaker, cable run straight from the panel to the wallbox. Breaker characteristic C for all three sizes (magnetic trip 5–10x In per IEC 60898 / UL 489 inverse-time). Add a lockable disconnect within sight of the charger if your inspector requires it (NEC 625.23).

ChargerBreaker (char. C)Wire CuConduit (min)Disconnect
7.4 kW40 A 2P3x6 sq mm3/4 in EMT40 A isolator
11 kW20 A 4P5x4 sq mm3/4 in EMT20 A 4P isolator
22 kW40 A 4P5x6 sq mm1 in EMT40 A 4P isolator

Torque terminations to the breaker datasheet value — loose 32 A terminations are the most common real-world failure on EV circuits, not undersized cable.

7. RCD: why Type A minimum, and when you need Type B

EV chargers produce smooth DC residual currents that can blind a standard Type AC RCD (IEC 60364-4-41, IEC 61851-1). Minimum is Type A 30 mA, which handles pulsating DC up to 6 mA. If the wallbox has no built-in 6 mA DC detection, you need Type B (or Type EV / Type F-EV) that trips on smooth DC.

Checklist: wallbox datasheet says built-in 6 mA DC protection — Type A 30 mA upstream is enough; no such statement — install Type B 30 mA. Never share one RCD between the EV circuit and house circuits: a DC leak from the car can blind protection for the whole board. Dedicated RCBO on the EV circuit is the clean answer.

8. Mini case: 200 A panel, 7.4 kW charger, AC and dryer

House: 200 A service, existing loads — 5-ton AC (30 A), dryer (24 A), kitchen (40 A diversified), rest of house 35 A. Total existing demand by NEC 220.82 optional method: 129 A. Add EV at continuous 40 A rating: 169 A, under 200 A — fits with 31 A spare. Inspector math passes.

Now the same house with only 100 A service: 129 A existing already exceeds it (real panels rely on diversity, but the calculation says no). Options: load-management wallbox (CT clamps throttle the car when the house peaks — NEC 625.42 allows it), or service upgrade to 200 A. This is the step most DIY quotes skip, and the one inspectors fail most often.

9. Common mistakes that fail inspection

  • Breaker sized at charger current instead of 125% — 32 A breaker on a 32 A charger trips after hours.
  • Type AC RCD on an EV circuit — blind to DC leakage, violates IEC 61851-1 intent.
  • Sharing the EV RCD with house circuits — one DC fault blinds everything downstream.
  • Aluminium cable at copper ampacity — terminate correctly and upsize (6 Cu = 4 AWG Al roughly, check Table 310.16 aluminium column).
  • No load calculation submitted — inspector asks for NEC Article 220 math, not just the wallbox manual.

10. Assumptions and when this does not apply

  • Assumes 230/400 V, 50/60 Hz, copper conductors at 30 C ambient, not more than 3 current-carrying conductors in a conduit.
  • Assumes the car actually accepts the wallbox power — many cars cap AC at 7.4 or 11 kW.
  • Does not cover DC fast chargers (25 kW+), which need utility coordination and are not a branch-circuit job.
  • Does not cover TT island systems or ungrounded services — earthing and RCD selection differ (see NEC 250 and IEC 60364-4-41).
  • Local amendments (California Title 24, UK BS 7671 Section 722) can add metering, PEN-fault or isolation rules on top of this guide.

See also: Breaker size from load to wire · Home load calculation · Wire ampacity chart explained

Try it free in your browser — open the demo: https://gorkycad.com/cad/?demo=1

Frequently asked questions

Do I need a 40 A breaker for a 7.4 kW charger?

Yes. 7.4 kW draws 32.2 A continuously, and NEC 210.20(A) requires 125%, which is 40.25 A. A 32 A breaker will eventually trip on long charges.

Can I install an 11 kW charger on single-phase?

No. 11 kW needs three-phase 400 V at 15.9 A per phase. On single-phase 230 V the same power would draw 47.8 A, which most homes cannot supply.

Type A or Type B RCD for an EV charger?

Type A 30 mA minimum if the wallbox has built-in 6 mA DC detection; otherwise Type B 30 mA. Never use Type AC on an EV circuit.

Will a 22 kW charger overload a 100 A panel?

Very likely. 22 kW alone is rated 40 A continuous. Do an NEC Article 220 load calculation first, or use a load-managing wallbox with CT clamps.

What wire for a 22 kW charger at 40 meters?

5x6 sq mm copper minimum, and check drop: about 1.8% at 40 m. Beyond 35-40 m step up to 5x10 sq mm for margin.

Related reading