The one-paragraph answer

Use copper for branch circuits (receptacles, lighting, small appliance runs) and anywhere terminations are ordinary devices. Use aluminum for large feeders and service entrances (typically 2 AWG / 35 mm² and larger) where the savings are huge and terminations are purpose-built lugs. Both are fully code-legal when installed per their rules — NEC 310.16 lists ampacities for each metal side by side, and NEC 110.14 governs the terminations that make or break aluminum.

The failures people blame on aluminum are almost always termination failures: no antioxidant, wrong connector, or an un-torqued lug on a metal that creeps under pressure. Modern AA-8000 series alloy with listed connectors and torqued terminations has a service record going back to the 1980s without the problems of 1960s-era alloy. Respect the rules and aluminum is boring — which is exactly what you want from wire.

Ampacity head-to-head (NEC 310.16, 75 °C column)

Ampacity tables list copper and aluminum separately because aluminum has about 61 percent of copper conductivity. The practical result: aluminum needs roughly one to two AWG sizes larger for the same current. The table below uses the 75 °C column, which governs most breaker terminations (the 90 °C column is for derating math only — the termination rating caps you at 75 °C in nearly all residential work).

Size (AWG/kcmil)Copper 75 °C (A)Aluminum 75 °C (A)Typical use
12 AWG25*20*Lighting / receptacles (Cu only in practice)
10 AWG35*25*Small branch circuits (Cu only in practice)
8 AWG5040Range / dryer tails, small feeders
6 AWG6550Cooktop, subpanel feeder
4 AWG8565Subpanel feeder
3 AWG10075100 A feeder (Cu)
1 AWG130100100 A feeder (Al)
2/0175135150–200 A range
4/0230180200 A service (Al standard)
250 kcmil255205200 A+ service (Cu alternative)

*12 and 10 AWG are capped by NEC 240.4(D) small-conductor rules at 20/30 A for copper and 15/25 A for aluminum regardless of the table. In practice aluminum below 8 AWG is effectively off the table for new branch circuits.

Cost per foot: where aluminum wins big

Copper pricing tracks the commodities market, but the ratio is stable: aluminum conductors cost roughly one-quarter to one-third the price of equal-length copper at feeder sizes, and the gap widens as sizes grow because you are paying mostly for metal weight. A 100 ft run of 3 AWG copper THHN might run $250–$400 at 2025–2026 US retail, while the electrically equivalent 1 AWG aluminum runs $90–$160 — savings of $150 or more on a single homerun (market estimates; copper is volatile, so check the day price).

On small branch circuits the savings evaporate: a 250 ft coil of 12/2 NM-B copper is $60–$100, and aluminum NM-B in small sizes barely exists in the market. Labor also tilts small work toward copper — every electrician stocks it, every device accepts it, no special connectors. The economic crossover sits around 6–4 AWG: below that copper wins on simplicity, above that aluminum wins on price.

Remember the total job cost, not just wire: aluminum feeders need listed lugs (usually already on panels and disconnects), antioxidant compound ($8 a tube that lasts dozens of terminations), and a torque screwdriver ($30–$60). Those fixed costs vanish into a feeder job and would dwarf a receptacle-circuit job — one more reason to split the metals by application.

Worked example: 100 A feeder, 100 ft

Given: a 100 A subpanel feeder, 100 ft one-way (200 ft of conductor loop for voltage-drop math), 240 V, 75 °C terminations, copper THHN in conduit vs aluminum XHHW in conduit.

Step 1 — size from NEC 310.16. 100 A at 75 °C needs 3 AWG copper (100 A) or 1 AWG aluminum (100 A). Check the 83-percent dwelling rule (NEC 310.12): a 100 A dwelling feeder needs only 83 A ampacity — 4 AWG copper (85 A) or 2 AWG aluminum (90 A) would legally serve, but most installers pull the full 100 A size for future headroom.

Step 2 — check voltage drop. Loop resistance of 200 ft of 3 AWG copper (≈0.245 Ω/1000 ft) is 0.049 Ω; at 80 A continuous-equivalent load, drop = 80 × 0.049 ≈ 3.9 V, or 1.6 percent of 240 V — fine. For 1 AWG aluminum (≈0.156 Ω/1000 ft): 200 ft gives 0.031 Ω, drop ≈ 2.5 V, about 1.0 percent — actually better, because the larger aluminum size overcompensates. Both pass the 3 percent branch/feeder guidance.

Step 3 — price it. Roughly $250–$400 for the copper conductors vs $90–$160 for aluminum (2025–2026 retail, market estimate). Same current, same legality, half the drop, a third of the price. That is why services and feeders are aluminum country. For feeder planning, see our subpanel sizing guide.

Termination rules that make aluminum safe (NEC 110.14)

Every aluminum failure story traces to one of three sins: a connector not listed for aluminum, no antioxidant on a connection that needs it, or a lug never torqued. The code answers each: NEC 110.14(A) requires terminals listed and identified for the conductor material — look for AL9CU / CU9AL (or CO/ALR on devices) markings; unmarked pressure connectors default to copper-only.

NEC 110.14(D) requires tightening to the equipment torque value shown on the label or instructions — typically 35–50 inch-pounds for feeder lugs. Aluminum creeps: an under-torqued lug loosens further with thermal cycling, resistance climbs, and the joint cooks. A $40 torque screwdriver and thirty seconds per lug is the entire prevention program. Re-torque manufacturer guidance should be followed where stated.

Antioxidant (oxide-inhibitor) compound is required by most lug manufacturers instructions for aluminum, which makes it mandatory via NEC 110.3(B) (install per listing and instructions). Brush it on freshly stripped, shiny conductor, assemble immediately before the oxide skin reforms, and torque once — repeated loosening and re-tightening work-hardens the joint.

Where each metal is allowed — and where it is not

Copper is allowed everywhere, full stop. Aluminum has practical and code boundaries: solid aluminum smaller than 8 AWG is effectively banned from new branch circuits by market reality plus NEC 240.4(D) limits; many local amendments and insurer rules restrict or forbid extending old small-size aluminum branch wiring without listed remediation. New small aluminum branch circuits are a non-starter — do not design them.

Aluminum feeders, services, and large branch circuits (ranges, dryers, subpanels, HVAC) are mainstream and explicitly tabulated in NEC 310.16. Utility service drops are aluminum almost universally. The AA-8000 series alloy required by modern standards (AA-8176 and similar) fixed the creep and fatigue problems of the 1960s AA-1350 alloy — new feeder aluminum is a different material with a 40-year track record.

Inside equipment, follow the label: most modern panel lugs, meter sockets, and disconnects are dual-rated AL9CU. If a lug is marked copper-only, either use copper or change the lug — never land aluminum under it. And never mix bare copper and aluminum in direct contact outdoors without a listed bi-metal connector; galvanic corrosion eats the joint. Device-level detail lives in our copper vs aluminum overview.

ApplicationCopperAluminum
Receptacle and lighting branch circuitsStandard choiceDo not use for new work
Kitchen small-appliance circuitsStandard choiceDo not use for new work
Range, dryer, cooktop (30–50 A)AllowedAllowed at 8 AWG and larger, listed lugs
Subpanel feedersAllowedPreferred on cost
Service entrance conductorsAllowedIndustry standard

Voltage drop and conduit fill: aluminum needs more room

The larger aluminum size for equal current has two knock-on effects. First, conduit fill: 1 AWG aluminum XHHW (~0.36 in diameter) needs bigger conduit than 3 AWG copper for the same three-conductor-plus-ground pull. Check NEC Chapter 9 Table 1: one wire 53 percent fill, two wires 31 percent, three or more 40 percent. A feeder that fit 1-inch EMT in copper may need 1-1/4 inch in aluminum — price the conduit step-up against the wire savings.

Second, voltage drop usually improves with aluminum at equal ampacity, because the upsized conductor has lower resistance than the copper it replaces (shown in the 100 A example: 1.0 vs 1.6 percent). But at equal physical size aluminum drops about 64 percent more voltage — so never substitute same-size aluminum for copper. Always re-size from the table, then verify drop with the distance formula from our voltage drop guide.

Bending space matters too: larger aluminum needs the enclosure wire-bending room of NEC 312.6. In a cramped existing panel, the physically smaller copper conductors may be the only thing that fits legally — another reason copper owns retrofit branch work.

Old small-size aluminum branch wiring: what to do

Houses wired roughly 1965–1975 with solid aluminum 12 and 10 AWG need remediation, not panic. The recognized repairs, in order of preference: a full copper replacement of the branch circuits (best, most expensive), Copalum crimp remediation by a certified installer (excellent, limited availability), or AlumiConn lug connectors at every termination torqued to spec (widely available, recognized by insurers). All three end the creep-and-oxidize cycle at terminations.

What does not fix it: “CO/ALR” receptacles alone (they address only the device end, not every splice in the circuit), antioxidant without re-termination, or simply torquing old connections and hoping. Every splice, every switch, every receptacle in the aluminum portion needs the listed treatment — partial remediation leaves partial risk.

Budget $2,000–$4,000 for AlumiConn-style remediation of a typical house (market estimate), versus $8,000–$20,000 for a full rewire. The full method comparison is in our aluminum remediation guide.

Common mistakes (all of them termination mistakes)

  • Aluminum under a copper-only lug. Unmarked connectors are copper-only by default. Land aluminum there and galvanic corrosion plus creep guarantees a hot joint.
  • Skipping antioxidant. Aluminum oxide reforms in seconds and is an insulator. No compound, no torquing discipline — no reliable joint.
  • No torque tool. “Good and tight” over-torques small lugs (cracked conductor) and under-torques large ones (future hot spot). NEC 110.14(D) requires the listed value — use the tool.
  • Same-size substitution. Swapping 12 AWG aluminum for 12 AWG copper loses a third of ampacity. Re-size from NEC 310.16 every time.
  • Aluminum for small branch circuits. Nothing in the code blesses new 12 AWG aluminum receptacle circuits in homes. Copper owns that territory.

Lay out feeders and branch circuits with correct sizes before you buy a foot of wire: open the GorkyCAD demo and build the panel schedule with our free single-line tools.

Frequently asked questions

Is aluminum wire safe in a house?

Modern AA-8000 series aluminum in feeder and service sizes, terminated in listed AL9CU lugs with antioxidant and proper torque per NEC 110.14, is safe and code-legal with a decades-long record. The hazard is 1960s–70s small-size solid aluminum branch wiring with unremediated terminations.

What size aluminum equals 3 AWG copper for 100 A?

1 AWG aluminum carries 100 A at 75 °C per NEC 310.16, matching 3 AWG copper. For dwelling feeders the NEC 310.12 83-percent rule allows 2 AWG aluminum (90 A) for a 100 A dwelling feeder.

Why is aluminum wire cheaper than copper?

Aluminum is far more abundant and lighter, so equal length costs roughly a quarter to a third of copper at feeder sizes. The ratio moves with copper commodity prices, which are volatile.

Do I need antioxidant on aluminum connections?

Yes wherever the lug manufacturer instructions call for it — which is nearly always for aluminum. NEC 110.3(B) makes the listing instructions mandatory, so skipping the compound is a code violation, not just bad practice.

Can I connect aluminum wire to a regular outlet?

No. Standard receptacles are copper-only. Existing small-size aluminum branch circuits need listed remediation (Copalum or AlumiConn) at every termination, and new receptacle circuits should simply be copper.