Demand factor and diversity factor both answer how much of the connected load runs at once — but they divide different things, and mixing them up double-discounts the load. Demand factor is maximum demand over connected load for one system or panel. Diversity factor is the sum of individual maximum demands over the coincident maximum demand of the group. One number sizes the service; the other explains why the service is smaller than the sum of its feeders.
This guide defines both per NEC Article 220 (220.42 lighting, 220.52 appliance and laundry, 220.53–220.56), works a full 12 kW house example, and gives you a table of the demand factors inspectors actually apply.
Definitions That Do Not Overlap
Demand factor = max demand of a system ÷ total connected load of that system. It is always ≤ 1. A house with 12 kW of connected load that never exceeds 7 kW has a demand factor of 0.58. Diversity factor = sum of individual max demands ÷ coincident max demand of the whole. It is always ≥ 1. Four feeders peaking at 3 kW each at different times (sum 12) with a coincident peak of 7 kW give diversity 12 / 7 = 1.71. Note the relationship: diversity factor = 1 / (coincident demand factor of the group).
NEC Demand Factors You Will Actually Use
NEC Article 220 bakes demand factors into the service calculation instead of summing nameplates.
| Load type | NEC reference | Demand applied |
|---|---|---|
| General lighting + receptacles, first 3,000 VA | 220.42 | 100% |
| Next 3,001–120,000 VA | 220.42 | 35% |
| Remainder over 120,000 VA | 220.42 | 25% |
| Small-appliance + laundry (each 1,500 VA) | 220.52 | 100% into lighting total |
| 4+ fixed appliances | 220.53 | 75% of nameplate sum |
| Dryer | 220.54 | 5,000 VA or nameplate, whichever larger |
| Range | 220.55 | Table 220.55 (e.g. 8 kW for one 12 kW range) |
These are the numbers that turn a scary nameplate total into a legal service size.
Worked Example: 12 kW House to Calculated Load
Given a small dwelling with connected loads: lighting and receptacles 6,000 VA (by 3 VA/sq ft), two small-appliance circuits 3,000 VA, laundry 1,500 VA, dryer 5,000 VA, range 12,000 VA nameplate. Connected total = 27,500 VA. Now apply NEC demand. Step 1 — lighting block: 6,000 + 3,000 + 1,500 = 10,500 VA; first 3,000 at 100% = 3,000; remaining 7,500 at 35% = 2,625; lighting demand = 5,625 VA. Step 2 — dryer: 5,000 VA at 100% (single dryer) = 5,000. Step 3 — range per Table 220.55 column C: 8,000 VA. Step 4 — total demand = 5,625 + 5,000 + 8,000 = 18,625 VA. At 240 V that is 18,625 / 240 = 77.6 A → an 80–100 A service calculation, from a 27.5 kVA nameplate pile. The overall demand factor is 18.6 / 27.5 = 0.68.
Same House Through the Diversity Lens
Now meter each feeder at its own peak: lighting block peaks 4.0 kW (evening), dryer 5.0 kW (Saturday), range 8.0 kW (Thanksgiving) — sum of individual maxima = 17.0 kW. The coincident whole-house peak (all three rarely peak together) meters at 12.5 kW. Diversity factor = 17.0 / 12.5 = 1.36. Demand factor of the whole = 12.5 / 27.5 = 0.45 on nameplate, or 12.5 / 17.0 = 0.74 on summed peaks. Same house, three ratios — each answers a different question, which is why the terms are not interchangeable.
Demand Table for Quick Service Math
Compact version for dwelling estimates at 120/240 V single-phase.
| Block | Connected example | Demand | Result |
|---|---|---|---|
| Lighting + receptacles + SABC + laundry | 10,500 VA | 3,000 × 100% + 7,500 × 35% | 5,625 VA |
| Dryer (1 unit) | 5,000 VA | 100% | 5,000 VA |
| Range 12 kW (Table 220.55) | 12,000 VA | column C | 8,000 VA |
| 4 fixed appliances 8,000 VA | 8,000 VA | 75% (220.53) | 6,000 VA |
| Total service | 35,500 VA connected | — | 24,625 VA ≈ 103 A |
Add HVAC at 100 percent of the larger of heat vs cool (220.82) — it does not get a demand discount in the standard method.
Mini-Case: Why the 200 A Panel Is Half Empty
A homeowner opens a 200 A panel with forty 20 A breakers (800 A of handle ratings) and worries it is overloaded. Breaker handles sum connected capacity, not demand. The calculated load per Article 220 is 78 A; the metered peak over a year is 61 A. Demand factor on connected breakers: 61 / 800 = 0.08 — normal. Diversity across branch peaks vs the coincident peak: about 1.4. The panel is fine; handle sums are not a load calculation and inspectors do not add them.
Second example, small office: 30 kW connected (lighting 8 kW, receptacles 6 kW, five workstations 5 kW, two split AC units 7 kW, misc 4 kW). Lighting and receptacles diversify hard — measured coincident peak 18 kW, so demand factor 18 / 30 = 0.60. Feeder math at 208 V three-phase, power factor 0.9: I = 18,000 / (1.732 × 208 × 0.9) = 18,000 / 324.2 = 55.5 A → a 60 A feeder with 6 AWG-class conductors. Sized by nameplate the same office would demand 30,000 / 324.2 = 92.5 A and a 100 A feeder — nearly double the copper for load that never coincides. The saving is one full wire size plus a smaller panel, which is exactly what the demand factor is for.
Assumptions and When This Does Not Apply
- NEC demand tables are for dwellings and the occupancies named in each section — commercial kitchens, schools, and hospitals have their own tables.
- The optional methods (220.82, 220.83) replace this math with simpler formulas — do not mix standard and optional in one calculation.
- Diversity factor needs metered or well-estimated non-coincident peaks; guessing all four peaks at nameplate fabricates diversity.
- EV chargers at 100 percent continuous plus on-demand heat can collapse diversity — size those at full current.
- IEC 60364 applies simultaneity (ks/ku) differently from NEC demand — do not swap the tables across standards.
Common Mistakes
- Applying demand factor and diversity factor to the same number — double discounting.
- Summing breaker handles as if they were load.
- Using Table 220.55 column A/B/C interchangeably for ranges.
- Discounting HVAC or EV charging that Article 220 requires at 100 percent.
- Quoting diversity without stating the metering window the peaks came from.
How Inspectors Check Your Demand Math
Inspectors rarely recompute the whole service by hand; they check the structure. First they verify you picked one method — standard or optional — and did not blend Table 220.55 with the 220.82 flat formula in the same calculation. Then they walk the lighting block: is the square footage times 3 VA present, are the two small-appliance circuits and laundry each at 1,500 VA inside that block, and did the first 3,000 VA stay at 100 percent with the rest at 35 percent. Appliances come next: four or more fixed appliances must show the 75 percent line from 220.53, and the range must cite Table 220.55 with the right column — column C for a single range, which is where most DIY calculations go wrong by entering the full nameplate. Finally they check that HVAC entered at 100 percent of the larger of heating vs cooling with no demand discount, and that the final amps divided by 240 V land on a standard service size at or above the result. Present the calculation as a labeled table with one row per block plus the NEC reference per row, and the review takes minutes instead of a second trip.
Demand Factors for EV and HVAC Additions
Two modern loads break the old diversity assumptions and must be handled explicitly. EV supply equipment is a continuous load at 100 percent with the 125 percent breaker multiplier on top: a 32 A charger counts 32 A in the service math and takes a 40 A breaker, and NEC 625.42 allows a reduction only with a listed energy management system that provably sheds the load. Heat pumps and electric backup heat count at 100 percent of the larger mode per 220.82 — a 12 kW strip plus a 5 kW compressor does not average to 8.5 kW in any code method. Practical approach for an existing 100 A house adding both: recompute the base with the standard method, add EV plus heat at full value, and if the total crosses roughly 80 A, price the 200 A upgrade before buying the equipment. That single recomputation prevents the classic failure of a main breaker tripping every winter evening after two clean-looking individual permits.
See Also
Continue with the full house load calculation, the subpanel and feeder sizing guide, and the kW-to-amps math that converts these VA totals into breaker sizes.
Enter your own connected loads and watch the demand math apply per circuit: open the free demo at https://gorkycad.com/cad/?demo=1 and build the panel schedule.
Try it free in your browser: open the demo at https://gorkycad.com/cad/?demo=1 — draw the plan, run the load math, and export a panel schedule.
Frequently asked questions
What is the difference between demand factor and diversity factor?
Demand factor is max demand over connected load of one system (always 1 or less). Diversity factor is the sum of individual peaks over the coincident peak (always 1 or more). One sizes equipment; the other explains non-coincident peaks.
What NEC sections cover dwelling demand loads?
220.42 for lighting (100/35/25 percent blocks), 220.52 for small-appliance and laundry at 1,500 VA each, 220.53 at 75 percent for 4+ appliances, 220.54/220.55 for dryer and range.
What is the calculated load of the 12 kW example house?
18,625 VA (77.6 A at 240 V): lighting block 5,625 + dryer 5,000 + range 8,000 per Table 220.55. Overall demand factor 0.68 on the 27.5 kVA nameplate total.
Can I just add up breaker ratings?
No. Breaker handles sum connected capacity, not demand. A 200 A panel with 800 A of handles at 61 A metered peak is normal — demand factor 0.08.
Does diversity apply to EV chargers?
Barely. Continuous EV charging at full current has no diversity against itself — size EV circuits at 100 percent continuous plus 125 percent breaker sizing.