Every wire loses some voltage along its length. The question is how much loss is acceptable — and the famous 3 percent and 5 percent numbers come from NEC informational notes, not from hard code rules. NEC 210.19(A) Informational Note 4 suggests 3 percent maximum drop on branch circuits, and NEC 215.2(A) Informational Note 2 suggests 5 percent total from service to the farthest outlet. They are design guidance that inspectors treat seriously for motors, HVAC, and EV chargers, even though a circuit at 6 percent is not a code violation by itself.

This article traces where the numbers come from, shows the calculation with the K-factor formula, and gives ready length tables for common wire sizes so you can check a run in seconds.

Where 3 Percent and 5 Percent Come From

The NEC informational notes exist because utilization equipment is designed around nominal voltage with a tolerance band (typically ±10 percent at the device per NEMA and UL standards). The 3 percent branch plus 2 percent feeder split keeps the farthest outlet within about 5 percent of service voltage under load, leaving margin for utility sag. IEC 60364-5-52 takes a similar approach with a 5 percent total recommendation (3 percent for lighting in some national implementations). Neither document makes the number a shall-code violation — but energy codes, utility interconnection rules, and motor warranties often reference them as if they were.

The Voltage-Drop Formula (Single-Phase)

VD = 2 × K × I × L / CM. K is 12.9 for copper and 21.2 for aluminum (these encode resistivity at operating temperature). I is current in amps, L is one-way length in feet, CM is the conductor circular-mil area (12 AWG = 6,530; 10 AWG = 10,380; 8 AWG = 16,510; 6 AWG = 26,240). Percent drop = VD / circuit volts × 100. For three-phase, replace the leading 2 with 1.732. Always use the actual load current, not the breaker rating — a 20 A breaker feeding a 9 A lighting load drops less than half what the breaker math suggests.

Worked Calculation: 16 A, 80 ft, 12 AWG, 120 V

Given: 16 A load, 80 ft one-way, 12 AWG copper (6,530 CM), 120 V. Step 1: VD = 2 × 12.9 × 16 × 80 / 6,530 = 33,024 / 6,530 = 5.06 V. Step 2: percent = 5.06 / 120 = 4.21 percent. Verdict: over the 3 percent branch recommendation — upsize to 10 AWG: VD = 33,024 / 10,380 = 3.18 V = 2.65 percent, pass. Same load at 240 V would be only 1.33 percent on 12 AWG — which is why 240 V circuits tolerate long runs so much better.

Max-Length Table at 3 Percent, 120 V Copper

One-way feet before hitting 3 percent drop, copper, 120 V circuits.

Wire12 A16 A20 A
14 AWG62 ft47 ft37 ft
12 AWG99 ft74 ft59 ft
10 AWG157 ft118 ft94 ft
8 AWG250 ft187 ft150 ft

Read it as a planning tool: a 16 A table saw 100 ft from the panel on 12 AWG is over (74 ft max) — pull 10 AWG (118 ft max) instead.

Max-Length Table at 3 Percent, 240 V Copper

Same basis at 240 V — lengths double for the same current because the base voltage doubles.

Wire20 A30 A40 A
12 AWG119 ft79 ft59 ft
10 AWG189 ft126 ft94 ft
8 AWG300 ft200 ft150 ft
6 AWG477 ft318 ft238 ft

The 30 A / 100 ft cell confirms article one's answer: 10 AWG reaches 126 ft at 3 percent only if you accept the full 3.0 — at 100 ft it lands at 3.11 percent with exact K math, so 8 AWG is the safe pick.

When You Must Not Exceed the Limit

Treat the notes as mandatory for: motor circuits (hard starting, torque falls with the square of voltage — a 5 percent sag costs about 10 percent starting torque); EV chargers and heat pumps running hours at full current (heat in the wire plus nuisance undervoltage faults); fire pumps and life-safety loads (separate NEC articles impose their own drop limits); and any circuit already near the low end of the utility tolerance. For a 60 W lighting load on a lightly loaded circuit, 4 percent causes no symptom — note it and move on.

How to Fix an Over-Limit Run

Four fixes in order of cost: upsize the wire one step (cheapest at rough-in); split the load across two circuits (halves the current, halves the drop); move to 240 V where the appliance allows it (quarters the percentage for the same watts on shared-neutral designs); relocate the subpanel closer to the load center and feed it once with large wire instead of running five long branch circuits. Never fix drop by upsizing the breaker — the breaker follows the smallest wire on the circuit.

Concrete metric example: a 16 A socket circuit, 30 m one-way in 2.5 sq mm copper at 230 V. Warm resistivity is about 0.021 ohm·sq mm/m, so VD = 2 × 0.021 × 30 × 16 / 2.5 = 8.06 V, which is 8.06 / 230 = 3.5 percent — over the branch-circuit target. Two compliant fixes: pull 4 sq mm instead (VD = 2 × 0.021 × 30 × 16 / 4 = 5.04 V = 2.2 percent, pass), or split the sockets into two 8 A groups on separate breakers (VD per group halves to about 1.75 percent on the same 2.5 sq mm). At acceptance the inspector or engineer checks this live: full load switched on, voltmeter at the farthest outlet, drop computed against the no-load voltage at the panel. If the measured drop exceeds the design value, the usual findings are a loose termination or a longer actual route than the drawing shows — both worth fixing before sign-off.

Mini-Case: EV Charger 110 ft From the Panel

A 32 A EV charger at 240 V, 110 ft one-way, copper. On 8 AWG: VD = 2 × 12.9 × 32 × 110 / 16,510 = 90,816 / 16,510 = 5.50 V = 2.29 percent — pass. The installer first priced 10 AWG (VD = 8.75 V = 3.65 percent, fail) and the charger manufacturer requires under 3 percent for warranty. Difference in wire cost: about one step of copper. Difference in outcome: full-rate 7.7 kW charging vs thermal throttling on summer afternoons.

Assumptions and When This Does Not Apply

  • Tables assume copper at operating temperature via K = 12.9; aluminum uses K = 21.2 and runs about 60 percent shorter for the same size.
  • Load current means simultaneous running current; intermittent loads (saws, welders) are judged by heating plus starting performance, not one number.
  • Power factor below 0.9 lengthens effective drop on reactive loads — motor circuits should use the full complex calculation or manufacturer tables.
  • High ambient temperature raises resistance; the K-factor math already assumes warm wire, but derated ampacity may govern first.
  • DC, high-frequency, and very long underground runs add reactance and skin effects the simple formula omits.

Common Mistakes

  • Quoting 3 percent as a hard NEC rule and failing inspections over 3.1 percent on a lighting circuit.
  • Sizing drop by breaker amps instead of actual load amps, oversizing everything.
  • Forgetting the one-way vs round-trip factor and doubling length twice.
  • Checking drop but skipping the 125 percent continuous-load upsizing.
  • Fixing drop with a bigger breaker instead of bigger wire.

Quick Aluminum Derate for the Same Tables

Aluminum at the same AWG runs shorter than copper because K rises from 12.9 to 21.2 — roughly 60 percent more drop per amp. As a planning shortcut, multiply the copper lengths in both tables by 0.61 for the same AWG in aluminum, or simply use the copper length of two sizes smaller wire. Example: the 120 V table gives 10 AWG copper 118 ft at 16 A; the same 10 AWG in aluminum manages about 72 ft, while 8 AWG aluminum reaches roughly 114 ft and becomes the practical pick for a 100 ft run. Feeders are where aluminum wins back the difference: 2 AWG aluminum at 100 A and 240 V costs far less than 2 AWG copper for a 150 ft service run, and the larger cross-section erases the resistivity penalty. Always terminate aluminum on AL-rated lugs, follow the antioxidant instructions, and torque with a calibrated wrench — most aluminum failures investigators see are termination failures, not wire failures.

See Also

Run the same math interactively with the voltage-drop calculator, cross-check the wire against the ampacity chart, and feed the result into the breaker-to-wire guide before you buy copper.

Sketch the long run with its real length and load — the demo at https://gorkycad.com/cad/?demo=1 computes drop per circuit as you draw.

Try it free in your browser: open the demo at https://gorkycad.com/cad/?demo=1 — draw the plan, run the load math, and export a panel schedule.

Frequently asked questions

Are 3 percent and 5 percent actual code requirements?

No. They are informational notes to NEC 210.19(A) and 215.2(A) — strong design guidance, enforceable only if a local amendment or another article (fire pump, sensitive loads) adopts them.

What is the single-phase voltage-drop formula?

VD = 2 × K × I × L / CM with K = 12.9 copper, 21.2 aluminum. Divide volts lost by circuit volts for percent. Three-phase uses 1.732 instead of 2.

How far can 12 AWG go at 16 A and 120 V?

About 74 ft before hitting 3 percent. At 80 ft the drop is 4.21 percent — step up to 10 AWG (2.65 percent).

Does 240 V really double the allowed distance?

For the same current, yes: percent is volts lost over base volts, so doubling base halves percent. Same watts at 240 V quadruples the advantage.

When must I treat the limit as mandatory?

Motors, EV chargers, heat pumps, fire pumps, life-safety loads, and any circuit near the low end of utility tolerance — plus any job where the spec or warranty cites the notes.