A 30 A circuit at the panel is one thing. The same 30 A at the end of a 100 ft run is another. Wire size for a long run is decided by two independent checks: ampacity (NEC Table 310.16) and voltage drop (NEC 210.19(A) Informational Note 4 and 215.2(A) Informational Note 2). On short runs ampacity governs. On a 100 ft run at 30 A, voltage drop often governs, which is why 10 AWG copper — perfectly good for 30 A on paper — can fail the drop check.

This guide gives you the answer table first, then shows the full calculation so you can repeat it for any distance, current, and material. All numbers below use copper at 75 C unless aluminum is stated, single-phase 240 V for the 30 A examples, and the standard voltage-drop formula with K = 12.9 for copper and K = 21.2 for aluminum.

Short Answer Table: Wire Size by Current and Distance

The table below assumes 240 V, copper THHN in conduit, 75 C terminations, 3 percent maximum drop on the branch circuit. Sizes are the larger of the ampacity requirement (NEC 310.16) and the voltage-drop requirement. Aluminum sizes are shown in parentheses where they differ.

Load50 ft100 ft150 ft
20 A, 240 V12 AWG Cu (10 Al)10 AWG Cu (8 Al)8 AWG Cu (6 Al)
30 A, 240 V10 AWG Cu (8 Al)8 AWG Cu (6 Al)6 AWG Cu (4 Al)
40 A, 240 V8 AWG Cu (6 Al)6 AWG Cu (4 Al)4 AWG Cu (2 Al)
50 A, 240 V6 AWG Cu (4 Al)6 AWG Cu (3 Al)3 AWG Cu (1 Al)

Read the 30 A row: at 50 ft, 10 AWG copper passes both checks. At 100 ft you step up to 8 AWG copper (6 AWG aluminum). At 150 ft you need 6 AWG copper. If your run is 120 V instead of 240 V, the drop doubles for the same watts — go one to two sizes larger than this table.

Why 10 AWG Can Fail at 100 ft and 30 A

NEC Table 310.16 lists 10 AWG copper at 30 A (75 C column, THHN). That is the ampacity check, and it passes. But voltage drop is a second, independent check. For a single-phase circuit the drop is VD = 2 × K × I × L / CM, where K is 12.9 for copper, I is current in amps, L is one-way length in feet, and CM is the circular-mil area of the conductor. For 10 AWG, CM = 10,380.

Plug in 30 A and 100 ft: VD = 2 × 12.9 × 30 × 100 / 10,380 = 77,400 / 10,380 = 7.46 V. On a 240 V circuit that is 7.46 / 240 = 3.11 percent — just over the 3 percent branch-circuit recommendation. The wire is not unsafe, but motors start harder, heaters deliver less, and an inspector or engineer checking the 3 percent note will flag it. Step up to 8 AWG (CM = 16,510): VD = 77,400 / 16,510 = 4.69 V = 1.95 percent. Comfortable pass.

The Two Checks: Ampacity First, Drop Second

Always run both checks and take the larger size. Step one: ampacity from NEC 310.16 at the termination temperature (usually the 75 C column for breakers and panels, or the 60 C column for older devices — check the marking). Apply derating for ambient temperature and bundling (NEC 310.15(B)) before comparing. Step two: voltage drop with the formula above against 3 percent for the branch circuit and 5 percent total (feeder plus branch) per the informational notes to 210.19(A) and 215.2(A). The notes are recommendations, not hard rules, but exceeding them with motors, EV chargers, or long HVAC runs causes real symptoms.

Full Worked Calculation: 30 A, 100 ft, 240 V, Copper

Given: load 30 A continuous-ish, one-way distance 100 ft, 240 V single-phase, copper, target 3 percent max on this run. Step 1 — ampacity: 10 AWG copper is rated 30 A at 75 C, so the minimum code size is 10 AWG. Step 2 — drop on 10 AWG: VD = 2 × 12.9 × 30 × 100 / 10,380 = 7.46 V = 3.11 percent. Verdict: fails the 3 percent target. Step 3 — try 8 AWG (16,510 CM): VD = 2 × 12.9 × 30 × 100 / 16,510 = 4.69 V = 1.95 percent. Verdict: passes with margin. Answer: use 8 AWG copper with a 30 A breaker. If the load is continuous (3+ hours at full current, NEC 210.19(A)(1)), the breaker and wire must additionally be sized at 125 percent: 30 × 1.25 = 37.5 A, so a 40 A breaker on 8 AWG copper.

Same Math for 120 V: Drop Doubles

At the same wattage, halving the voltage doubles the current and doubles the percentage drop, because the volts lost stay similar while the base shrinks. A 3,600 W load draws 15 A at 240 V but 30 A at 120 V. On 10 AWG at 100 ft and 120 V: VD = 7.46 V as before, but 7.46 / 120 = 6.2 percent — badly over. You would need 6 AWG copper (CM = 26,240): VD = 77,400 / 26,240 = 2.95 V = 2.46 percent. Practical rule: for 120 V general-purpose runs over 80 ft at 20–30 A, start the check at 8 AWG, not 12.

Copper vs Aluminum on Long Runs

Aluminum has higher resistivity (K = 21.2 vs 12.9), so it needs roughly two AWG steps larger than copper for the same drop. For the 30 A / 100 ft case: 6 AWG aluminum (CM = 26,240) gives VD = 2 × 21.2 × 30 × 100 / 26,240 = 127,200 / 26,240 = 4.85 V = 2.02 percent — a pass, and exactly what the table shows. Use only AA-8000 series aluminum with AL-rated lugs, antioxidant where the manufacturer requires it, and torque to spec. Never mix metals on the same lug unless it is listed for it.

Reference data behind every number in this guide:

SizeCopper CMAluminum CMK used
12 AWG6,5306,530Cu 12.9 / Al 21.2
10 AWG10,38010,380Cu 12.9 / Al 21.2
8 AWG16,51016,510Cu 12.9 / Al 21.2
6 AWG26,24026,240Cu 12.9 / Al 21.2

Breaker Sizing That Goes With the Wire

The breaker protects the wire, so it follows the final wire size, not the other way round. Standard mapping at 75 C: 12 AWG → 20 A, 10 AWG → 30 A, 8 AWG → 40–50 A (40 A typical for branch circuits, 50 A with 75 C terminations throughout), 6 AWG → 55–65 A. For continuous loads multiply the load by 1.25 before picking the breaker (NEC 210.19(A)(1) and 210.20(A)). A 30 A continuous load needs a 40 A breaker, and the wire must carry 37.5 A after derating — which pushes the 100 ft example firmly to 8 AWG copper minimum.

Mini-Case: Workshop Subpanel 100 ft From the House

A homeowner runs a 30 A feeder 100 ft to a detached workshop (table saw plus dust collector, 240 V). First attempt: 10 AWG copper on a 30 A breaker — passes ampacity, fails drop at 3.11 percent, and the saw bogs down on startup. Corrected design: 8 AWG copper, 30 A breaker (non-continuous mixed load), ground rod plus equipment ground per NEC 250.32, subpanel with separate neutral and ground. Measured drop under 29 A load: about 4.5 V (1.9 percent) — matches the calculation within a tenth. Cost of the correction at rough-in: one wire size. Cost after drywall: a new pull.

Assumptions and When This Does Not Apply

  • Distances are one-way; the formula already accounts for the round trip with the factor of 2 — do not double the length yourself.
  • Three-phase calculations use VD = 1.732 × K × I × L / CM, which gives lower drop per amp — this article covers single-phase only.
  • Underground runs in cold soil and high-temperature attics need ambient derating first; hot attics can force a larger size before drop is even checked.
  • Motor starting current (5–7× running) is a separate check from running drop — very long motor circuits may need upsizing beyond the 3 percent math.
  • Local amendments can make the 3 percent note mandatory — verify with the authority having jurisdiction.

Common Mistakes

  • Sizing by ampacity only and ignoring drop past 80 ft.
  • Using the 90 C column for the final size when terminations are rated 75 C.
  • Doubling the distance in the formula (the 2× already covers out and back).
  • Running 120 V high loads long distances instead of splitting or going 240 V.
  • Forgetting the 125 percent continuous-load multiplier on EV and HVAC circuits.

See Also

If you size wires often, keep these next to this guide: the amps-to-square-mm calculator walkthrough, the ampacity chart explained with the 75 C vs 90 C trap, and the voltage-drop calculator with the same K-factor math worked for any distance.

Draw the 100 ft run, place the panel and the load, and let the software run both checks at once: open the free demo at https://gorkycad.com/cad/?demo=1 and build the circuit with the real distances.

Try it free in your browser: open the demo at https://gorkycad.com/cad/?demo=1 — draw the plan, run the load math, and export a panel schedule.

Frequently asked questions

Why does 10 AWG fail at 100 ft and 30 A if it is rated 30 A?

Because ampacity and voltage drop are separate checks. 10 AWG carries 30 A thermally per NEC 310.16, but at 100 ft it drops 7.46 V, which is 3.11 percent of 240 V — over the 3 percent branch-circuit recommendation. 8 AWG drops only 1.95 percent.

What is the voltage-drop formula for single-phase?

VD = 2 × K × I × L / CM, with K = 12.9 for copper and 21.2 for aluminum, I in amps, L one-way feet, CM circular mils. Divide by the circuit voltage for percent.

Is the 3 percent limit a code rule?

No. NEC 210.19(A) Informational Note 4 recommends 3 percent on branch circuits and 5 percent total. It is enforceable only if locally adopted, but motors and chargers show symptoms above it.

What size aluminum for 30 A at 100 ft?

6 AWG AA-8000 aluminum: drop is about 4.85 V or 2.02 percent at 240 V. Use AL-rated lugs and torque to specification.

Do I need a bigger breaker with bigger wire?

Not automatically. The breaker follows the load and the wire minimums; upsizing wire for drop does not require upsizing the breaker unless the load is continuous at 125 percent.