Why electric tankless units draw so much current

A tank-style heater spreads its energy use over hours: a 4.5 kW element reheats stored water slowly, drawing under 19 A. A tankless unit keeps no hot water in reserve, so it must deliver full heating power the instant a tap opens. Raising 2.5 gallons per minute by 70°F takes roughly 24 kW of continuous power, which is why whole-house electric models start at 18 kW and run to 27 kW and beyond. At 240 V every kilowatt equals about 4.17 A, so a 24 kW unit pulls a full 100 A — as much as an entire small apartment with lights, fridge, and laundry running.

That single fact drives every electrical decision that follows: feeder, breakers, panel busbar, and service conductors must all absorb a load dwarfing the range (40–50 A) and dryer (30 A). Point-of-use minis of 3–8 kW are a different animal — a 6 kW unit draws 25 A on one 30 A circuit — so a small heater is easy while a whole-house unit can trigger a service upgrade costing thousands.

Amp draw table: kilowatts to amps at 240 V

Heating elements have power factor 1.0, so the math is simple division: I = P / U. A 24,000 W unit at 240 V draws 24,000 / 240 = 100 A exactly. The table below covers common whole-house and point-of-use sizes at 240 V single phase.

Unit size (kW)Current at 240 V (A)Typical use
3.514.6Single hand sink, point of use
833.3Single shower in warm climate
1354.2Small home, 1–1.5 baths
1875.02-bath home, moderate climate
24100.0Whole house, 2–3 baths
27112.5Whole house, cold climate
36150.0Large home, needs 300 A+ service

At 208 V (apartments, some commercial buildings), current runs higher: multiply by 240 / 208 = 1.154, so a 24 kW unit draws 115.4 A. Size breaker and wire for the nameplate voltage confirmed with a meter, never an assumed nominal. For any load conversion, see our kW to amps calculator and the wire ampacity chart explained.

Breaker sizing: the 125 percent rule

A water heater is a continuous load — it can run at full power for three hours or more on a cold morning — so conductors and protection are sized at 125 percent of the nameplate current. For storage-type heaters this is explicit in NEC 422.13; inspectors apply the same continuous-load treatment in NEC 210.19(A)(1) and 215.2(A)(1) to whole-house tankless units. The procedure: multiply nameplate amps by 1.25, then round up to the next standard breaker size in NEC 240.6(A) — 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, and so on.

Worked examples: 13 kW draws 54.2 A; 54.2 × 1.25 = 67.7 A, so use a 70 A breaker. 18 kW draws 75 A; 75 × 1.25 = 93.75 A, so use a 100 A breaker. 24 kW draws 100 A; 100 × 1.25 = 125 A, so use a 125 A breaker. 27 kW draws 112.5 A; 112.5 × 1.25 = 140.6 A, so use a 150 A breaker. These figures assume a single-circuit unit; most real 24–27 kW models split the load across two or three modules, each sized the same way from its module rating. Our breaker size calculator walks through the same 125 percent step for any load.

Wire size: 8, 6, or 4 AWG copper

Conductors follow the same 125 percent rule without exceeding their temperature rating. Use the 75°C column of NEC Table 310.16 for terminations rated 75°C (virtually all modern breakers and heaters), but remember that NM-B cable (Romex) is limited to the 60°C column by NEC 334.80 even though its conductors are rated higher. That one detail decides many tankless installs: 6 AWG NM-B is good for only 55 A, while 6 AWG THHN in conduit is good for 65 A.

Circuit breakerMin. copper NM-BMin. copper THHN in conduitGround (NEC 250.122)
40 A8 AWG (40 A at 60°C)8 AWG (50 A at 75°C)10 AWG
60 A4 AWG (70 A at 60°C)6 AWG (65 A at 75°C)10 AWG
70 A4 AWG (70 A at 60°C)4 AWG (85 A at 75°C)8 AWG
100 A2 AWG (95 A — short by 5; use 1 AWG)3 AWG (100 A at 75°C)8 AWG
125 A1/0 AWG1 AWG (130 A at 75°C)6 AWG
150 A2/0 AWG1/0 AWG (150 A at 75°C)6 AWG

For long runs add voltage drop: 80 feet of 3 AWG at 100 A drops about 3.9 V (1.6 percent) — acceptable — while undersized 6 AWG would exceed 3 percent and run hot at terminations. Run the numbers with our voltage drop calculator before you buy 100 feet of expensive copper, and check bundling and ambient-temperature derating in our long-run wire sizing guide.

How many circuits a whole-house unit needs

A 27 kW heater is rarely one 150 A circuit: manufacturers divide the elements into two or three modules with their own breakers, because 150 A branch circuits need enormous wire and special breakers. Typical nameplates read: 18 kW — two 40 A circuits; 24 kW — two 60 A or three 40 A circuits; 27 kW — three 40 A or two 60 A circuits; 36 kW — four 40 A or three 60 A circuits. The nameplate, not a rule of thumb, is the authority — NEC 110.3(B) requires installing listed equipment per its instructions.

Multiple circuits change the panel plan: three 40 A double-pole breakers need six spaces a crowded panel may lack. The fix is a subpanel near the heater — one feeder sized for the total (e.g. 150 A in 1/0 AWG for 27 kW), then short branch runs — which doubles as the required disconnect within sight. If your panel is full, read our 100 A vs 200 A service guide before buying the heater.

Service size check: will a 200 A panel survive?

Do this arithmetic before purchasing anything. Add the heater at 100 percent (it is continuous and noncoincident with nothing) to the Article 220 demand of the rest of the house. A compact example: general lighting and receptacles for a 1,500 sq ft home (4,500 VA) plus two small-appliance circuits (3,000 VA) plus laundry (1,500 VA) gives 9,000 VA; the optional method of NEC 220.82 takes the first 10,000 VA at 100 percent and the remainder at 40 percent. Add an 8 kW range (8,000 VA), a 5 kW dryer (5,000 VA), and a 3-ton air conditioner (about 7,200 VA): connected general total ≈ 29,000 VA, demand ≈ 10,000 + 0.40 × 19,000 = 17,600 VA, or about 73 A at 240 V.

Now add the tankless at full face value: 24 kW = 100 A, so total demand ≈ 173 A. A 200 A service covers it with 27 A of headroom — legal but tight, with no room for a future EV charger. With a 27 kW unit (112.5 A) the total hits ≈ 186 A, pointing to a 300–400 A service or a smaller heater plus a point-of-use unit. Also check the lateral and meter socket: many 200 A sockets cannot legally carry a continuous 173 A without a class-320 meter upgrade.

Disconnect, GFCI, and other code rules

NEC 422.31 and 422.32 require a disconnecting means within sight of the appliance (visible and under 50 feet away) for fixed equipment over 300 VA. A breaker in a panel you can see from the heater qualifies; otherwise install a non-fused disconnect switch next to the unit, or use a breaker with a listed lock-off device that stays in place with or without the lock installed. The inspector will check this on every tankless install, and a panel around the corner does not count as within sight.

GFCI is generally not required for a hardwired indoor tankless heater — NEC 422.5(A) lists the covered appliances, and whole-house water heaters are not among them — though local amendments and outdoor/pool locations differ. Two rules that bite: torque every lug per NEC 110.14(D), since a loose 100 A lug starts fires, and bond per NEC 250.4 with ground sized from Table 250.122, never downsized because the run is short.

Worked example: sizing a 24 kW unit end to end

Given: a 24 kW unit, nameplate two circuits at 60 A maximum each, 240 V, 40 feet from the panel. Step 1 — current per module: 12,000 / 240 = 50 A. Step 2 — continuous sizing: 50 × 1.25 = 62.5 A minimum conductor ampacity. Step 3 — breaker: the nameplate caps each circuit at 60 A, and conductor rated ≥62.5 A on a 60 A breaker is compliant.

Step 4 — wire: 6 AWG NM-B is rated only 55 A at 60°C per NEC 334.80, so NM-B must be 4 AWG; in EMT with THHN, 6 AWG at 75°C is rated 65 A and passes. Step 5 — ground: 10 AWG copper per Table 250.122. Step 6 — disconnect: the panel is around a corner, so add a 60 A non-fused disconnect within sight of the heater. Step 7 — voltage drop: 40 feet of 6 AWG at 50 A drops ~1.6 V (0.7 percent) — fine. That is the complete, inspectable answer.

Five mistakes that fail inspection

The same five errors show up on failed tankless inspections again and again. Check your plan against each one before the inspector arrives.

  1. One 60 A breaker for a 27 kW unit. The nameplate demands two or three circuits; a single 60 A breaker trips constantly and violates NEC 110.3(B). Size from the nameplate, not a forum post.
  2. 6 AWG Romex on a 60 A heater circuit. NM-B is capped at the 60°C column (55 A for 6 AWG), so a 50 A continuous module needing 62.5 A of conductor fails on Romex. Use 4 AWG NM-B or switch to THHN in conduit.
  3. No disconnect within sight. A panel in another room does not satisfy NEC 422.32. Budget $80–150 (market estimate) for a disconnect switch next to the heater.
  4. Skipping the load calculation. Landing a 100 A heater on a 150 A service with a 40 A range and 30 A dryer guarantees overload. Do the Article 220 math first.
  5. Aluminum feeder without rated terminations. Aluminum is legal for 100 A+ feeders, but every lug must be AL-rated and torqued per NEC 110.14(D). Dry-torqued aluminum loosens, overheats, and fails.

Tankless vs tank vs heat pump: electrical footprint

If the service math scared you, compare honestly. A 50-gallon tank uses one 30 A circuit with 10 AWG — trivial for any panel. A heat-pump heater uses 1–2 kW on a 15–20 A circuit and cuts energy roughly two-thirds, though it needs drainage and 700+ cubic feet of air. Tankless wins on endless hot water and space, loses on first cost and demand.

Heater typeTypical powerBreaker / wireService impact
Tankless 24 kW24 kW, 100 A2 × 60 A / 6 AWG THHNOften forces 200 A+ service
Tank 50 gal4.5 kW, 18.8 A1 × 30 A / 10 AWGFits almost any panel
Heat-pump 50 gal1–2 kW, under 10 A1 × 15–20 A / 12 AWGSmallest footprint, lowest bills

Sketch your panel and loads before you buy: draw the floor plan, place the heater, and lay out the circuits with a free tool like GorkyCAD demo — single-line diagram and load schedule in minutes, then confirm breaker and wire picks with our panel schedule template and house load calculation guide. Costs in this article are market estimates, not a quote — get a licensed electrician to verify your service math.

Frequently asked questions

Does a 27 kW tankless water heater need three breakers?

In most cases yes. A 27 kW unit at 240 V draws about 112.5 A, and manufacturers split that load across two or three internal heating modules, each fed by its own breaker — commonly three 40 A or two 60 A circuits. One single 60 A breaker on a 27 kW unit is undersized and will trip or overheat the conductors. Always follow the nameplate: it lists the exact number and size of required circuits.

What size breaker for an 18 kW tankless water heater?

An 18 kW unit at 240 V draws 75 A, and 75 × 1.25 = 93.75 A, so the next standard size up is 100 A per NEC 240.6(A). That assumes a single-circuit unit. Many 18 kW models use two 40 A circuits instead — check the nameplate, because the wiring plan is completely different.

Can I put a tankless water heater on a 100 A service?

Almost certainly not for a whole-house unit. A 24 kW heater alone draws 100 A, which consumes the entire service before lights, range, dryer, or HVAC are counted. Point-of-use units of 3–8 kW can work on a 100 A service if the load calculation allows it. Whole-house electric tankless normally needs a 200 A service at minimum, and large homes often need 300–400 A.

Does an electric tankless water heater need a neutral wire?

Most whole-house 240 V units need two hot conductors plus equipment ground only — no neutral, because the heating elements are pure 240 V loads. Some units with 120 V control boards or displays do require a neutral. Check the wiring diagram on the unit: if it shows L1, L2, and ground only, run a 2-wire plus ground cable, not 3-wire.

Why does my tankless water heater keep tripping the breaker?

The usual causes are an undersized breaker (ignoring the 125 percent continuous-load factor), loose terminations heating up under a 60–100 A load, or a unit wired to a single circuit when the nameplate requires two or three. Less common causes are a shorted heating element or low voltage raising current draw. Measure actual current with a clamp meter and compare it to the nameplate before upsizing anything.