RCD requirements by country: Russia 30 mA (PUE 7.1.79), Europe 30 mA (IEC 4-41), US GFCI 4–6 mA, China 30 mA, India 30 mA, Brazil 30 mA — table, types, fire RCDs.
| Parameter | Side 1 | Side 2 |
|---|---|---|
| Россия | 30 мА на розетки (7.1.79), 10 мА ванная | undefined |
| Европа (IEC) | 30 мА на розетки (411.3.3), тип A минимум | undefined |
| США | GFCI 4–6 мА в розетках (210.8) + AFCI | undefined |
| Китай | 30 мА (JGJ 16 7.7.10), 10 мА ванная | undefined |
| Индия | 30 мА мокрые зоны (IS 732) | undefined |
| Бразилия | 30 мА IDR (NBR 5410 6.4.3) | undefined |
Compares phase/neutral currents, trips on earth leakage: RCD (EU), GFCI (US), IDR (Brazil), 漏电保护器 (China).
Russia 30 mA (10 mA bathroom); EU 30 mA all sockets ≤ 32 A; UK 30 mA; US GFCI 4–6 mA in receptacles; China 30 mA; India 30 mA wet zones; Brazil 30 mA; Australia 30 mA.
Type A minimum in EU/Russia (pulsating DC); type F for VFDs; type B for EV chargers and inverters.
Russia 100–300 mA (7.1.84); EU 300 mA; China ≤ 500 mA; US GFPE 100 mA for services > 1000 A.
Automatic single-line diagrams, PUE/GOST/IEC calculations, specification and PDF — from one model.
Start freeData is for reference. Final design decisions must follow current regulations and a qualified engineer.