India: electrical installation rules (IS 732, IE Rules, National Electrical Code)

Indian electrical codes: IS 732:2019 (Electrical Wiring Code), IE Rules 1956, National Electrical Code. 230/400 V, IS 1293 sockets, IS 3043 earthing, RCD requirements.

🇷🇺 PUE — Rules for Electrical Installations (7th ed.)🕰️ PUE-6 — Rules for Electrical Installations (6th ed., 1985)🇺🇸 NEC — National Electrical Code (NFPA 70)🇪🇺 IEC 60364 / HD 60364 (EU national codes)🌎 NOM-001-SEDE, NBR 5410, AEA 90364, RETIE, NCh 4, CNE🇨🇳 GB 50054, GB 50303, JGJ 16, GB/T 16895 (IEC 60364)🇮🇳 IS 732

Key facts

DocumentIS 732:2019, IE Rules 1956, National Electrical Code
Voltage230/400 V
Frequency50 Hz
SocketsIS 1293 (6 A / 16 A, 3 pins)
EarthingTN-S, TN-C-S, TT

Terminology in the native language

Native termTransliterationEnglish translation
विद्युतvidyutelectricity
तारtārwire
अर्थिंगarthingearthing
फ्यूज़fusefuse
स्विचswitchswitch
सॉकेटsocketsocket outlet
वोल्टताvoltatāvoltage
भारbhārload
परिपथparipathcircuit
वितरण बोर्डvitaran boarddistribution board
मीटरmeterenergy meter
सुरक्षाsurakshāsafety

IS 732 and IE Rules

India's key documents: IS 732:2019 "Electrical Wiring Code" — the wiring code (current edition), IE Rules 1956 — historical Electricity Rules (mandatory safety and operation requirements) and National Electrical Code (NEC India) — a design guideline. Supporting standards: IS 3043 (earthing), IS 1293 (sockets), IS 5039, IS 5216, IS 8884.

Voltage and systems

The household network is 230/400 V, 50 Hz (single-phase 230 V, three-phase 400 V). Sockets follow IS 1293: 6 A and 16 A, three round pins (BS 546-compatible). Earthing — TN-S, TN-C-S, TT: local earth electrode (TT) per IS 3043 is common for homes, TN in urban buildings.

Protection and safety

IS 732 recommends (and mandates for wet areas) 30 mA RCDs; fire-protection RCDs of 100–300 mA at the intake. MCBs per IS/IEC 60898 are mandatory for overcurrent protection.

Wiring and materials

Copper cables per IS 694 (PVC-insulated), sizes in mm² (1.0; 1.5; 2.5; 4; 6 — minimum 1.0 mm² lighting, 1.5 mm² sockets). Concealed wiring in conduits or open. Colors: phase — red/brown/black, neutral — black/blue, PE — green/green-yellow (IS 732:2021).

India vs PUE

ParameterIndiaRussia (PUE)
Voltage230/400 V, 50 Hz230/400 V, 50 Hz
SocketsIS 1293 (3 round pins, 6/16 A)Type C/F
RCD30 mA (wet areas mandatory)30 mA (sockets mandatory)
EarthingTN-S/TT, IS 3043TN-C-S (new homes)
BasisBS + IEC + own ISPUE-7 + GOST R 50571

Inspection and operation

Wiring is done by licensed electricians; commissioning and periodic checks follow IE Rules. Acceptance includes earthing and insulation resistance tests (IS 732, Annex).

Related references

Clause-by-clause review

Translation of key sections and clauses with numbers:

Design with GorkyCAD Pro

Automatic single-line diagrams, PUE/GOST/IEC calculations, specification and PDF — from one model.

Start free

Data is for reference. Final design decisions must follow current regulations and a qualified engineer.