Clause-by-clause review of PUE-6 ch. 7.1: intakes, risers, flat boards, sockets without earthing, kitchen stoves — and differences from PUE-7.
| Document | PUE-6 (1985), Chapter 7.1 Residential buildings |
| Edition | 1985 (ПУЭ-6) |
| Status | Historical (replaced by PUE-7 ch. 7.1 in 2003) |
| Issued by | Ministry of Energy of the USSR |
| Applies to | Residential and public buildings, 1985 edition |
| № | Chapter / section |
|---|---|
| 7.1.1–7.1.20 | General building requirements |
| 7.1.21–7.1.45 | Intakes, boards, meters |
| 7.1.46–7.1.70 | Wiring, luminaires |
| 7.1.71–7.1.90 | Sockets, switches, kitchens |
Supply 380/220 V with earthed neutral; separate group circuits for lighting and power.
7.1.24–28 Risers with flat branches via flat boards.
7.1.36 Flat board: intake switch + group fuses/breakers.
7.1.55 Aluminium 2.5 mm² standard (APPV/APV); copper 1.5 mm².
7.1.61 Sockets in bathrooms prohibited.
7.1.62 Switches at 1.5–1.7 m; sockets at 0.8–1.0 m.
7.1.75–80 Electric stoves: dedicated circuit, TN-C earthing via PEN.