Clause-by-clause translation of Argentine AEA 90364 (IEC 60364-based): parts 7-771 (dwellings) and 7-701 (bathrooms), 30 mA RCDs, testing.
| Document | AEA 90364 (Argentina) Electrical installations regulation |
| Edition | 2017 |
| Status | Current (Argentina) |
| Issued by | AEA (Argentine Electrotechnical Association) |
| Applies to | Argentine building installations: 220/380 V, 50 Hz, parts 7-771 (dwellings) and 7-701 (bathrooms) |
| № | Chapter / section |
|---|---|
| 1–5 | General, protection |
| 7-701 | Bathrooms |
| 7-771 | Dwellings |
| 8 | Verification and testing |
AEA 90364 is based on IEC 60364 with national parts 7-xxx. Voltage 220/380 V, 50 Hz; type I sockets.
IEC parts 4-41, 4-43, 5-52, 5-53 apply. TN-S/TN-C-S for buildings.
6.4.3 30 mA RCD for residential socket circuits, bathrooms, outdoor; 300 mA fire RCD.
7-771.4 Socket counts: one per 6 m²; kitchen — min 4 sockets.
7-771.6 All sockets earthed; socket circuits via 30 mA RCD.
Zones 0–2 as IEC 60364-7-701; no sockets in zones 0–1; zone 2 via 30 mA RCD/SELV.
Insulation resistance, PE continuity, RCD test button, fault loop impedance; periodic checks every 10 years (housing) / 5 years (public).