NBR 5410 (Brazil) Low-voltage installations — translation

Clause-by-clause translation of Brazilian NBR 5410:2004: 30 mA IDR in wet areas (6.4.3), socket quantities (9.5), bathroom zones, NBR 14136 sockets.

🇷🇺 PUE — Rules for Electrical Installations (7th ed.)🕰️ PUE-6 — Rules for Electrical Installations (6th ed., 1985)🇺🇸 NEC — National Electrical Code (NFPA 70)🇪🇺 IEC 60364 / HD 60364 (EU national codes)🌎 NOM-001-SEDE, NBR 5410, AEA 90364, RETIE, NCh 4, CNE🇨🇳 GB 50054, GB 50303, JGJ 16, GB/T 16895 (IEC 60364)🇮🇳 IS 732

Document

DocumentNBR 5410 (Brazil) Low-voltage installations
Edition2004 (изм. 2008/2019)
StatusCurrent (Brazil)
Issued byABNT (Brazilian Association of Technical Standards)
Applies toBrazilian low-voltage building installations: protection, infrastructure, socket counts, 30 mA IDR

Document structure

№Chapter / section
4Protection against electric shock
5Protection against thermal effects
6Protection against overcurrent
9Installation infrastructure: socket quantities
9.2Bathrooms and wet areas
NBR 5410 (Brazil) Low-voltage installationsNOM-001-SEDE-2012 (Mexico) Electrical installationsRETIE (Colombia) Technical regulation of electrical installationsAEA 90364 (Argentina) Electrical installations regulation

Overview

NBR 5410 — Brazil's main low-voltage standard (up to 1000 V AC), based on IEC 60364 with Brazilian specifics: 127/220 V 60 Hz, NBR 14136 sockets (type N), mandatory IDR in wet areas.

Shock protection (4–5)

IEC 60364-4-41 measures: automatic disconnection, double insulation, SELV/PELV.

6.4.3 30 mA IDR mandatory: bathroom sockets, outdoor sockets, kitchens/laundries, outdoor equipment circuits. Fire IDR 300 mA at the intake.

Socket quantities (9.5)

9.5.2.2 Living rooms: one per 5 m of perimeter; kitchens: one per 3.5 m (min 3); bathroom: min one near the sink; 20 A sockets for AC units and appliances.

Bathrooms (9.2)

Zones 1–2; sockets only in zone 2 and beyond, ≥ 0.6 m from zone 1, on 30 mA IDR or SELV; IPX4 in zones 1–2, IPX7 in the shower.

Wiring

6.2.4 Minimum sections: lighting 1.5 mm², sockets 2.5 mm²; 6.2.5 voltage drop ≤ 4% lighting / 7% power.