Clause-by-clause translation of Brazilian NBR 5410:2004: 30 mA IDR in wet areas (6.4.3), socket quantities (9.5), bathroom zones, NBR 14136 sockets.
| Document | NBR 5410 (Brazil) Low-voltage installations |
| Edition | 2004 (изм. 2008/2019) |
| Status | Current (Brazil) |
| Issued by | ABNT (Brazilian Association of Technical Standards) |
| Applies to | Brazilian low-voltage building installations: protection, infrastructure, socket counts, 30 mA IDR |
| № | Chapter / section |
|---|---|
| 4 | Protection against electric shock |
| 5 | Protection against thermal effects |
| 6 | Protection against overcurrent |
| 9 | Installation infrastructure: socket quantities |
| 9.2 | Bathrooms and wet areas |
NBR 5410 — Brazil's main low-voltage standard (up to 1000 V AC), based on IEC 60364 with Brazilian specifics: 127/220 V 60 Hz, NBR 14136 sockets (type N), mandatory IDR in wet areas.
IEC 60364-4-41 measures: automatic disconnection, double insulation, SELV/PELV.
6.4.3 30 mA IDR mandatory: bathroom sockets, outdoor sockets, kitchens/laundries, outdoor equipment circuits. Fire IDR 300 mA at the intake.
9.5.2.2 Living rooms: one per 5 m of perimeter; kitchens: one per 3.5 m (min 3); bathroom: min one near the sink; 20 A sockets for AC units and appliances.
Zones 1–2; sockets only in zone 2 and beyond, ≥ 0.6 m from zone 1, on 30 mA IDR or SELV; IPX4 in zones 1–2, IPX7 in the shower.
6.2.4 Minimum sections: lighting 1.5 mm², sockets 2.5 mm²; 6.2.5 voltage drop ≤ 4% lighting / 7% power.
Automatic single-line diagrams, PUE/GOST/IEC calculations, specification and PDF — from one model.
Start freeData is for reference. Final design decisions must follow current regulations and a qualified engineer.
← Back to the country: Latin America: electrical installation rules (NOM, NBR 5410, RETIE, CNE) · World electrical installation rules