NEC Article 220: 3 VA/ft² lighting, 180 VA receptacles, optional dwelling method (220.82).

🇷🇺 PUE — Rules for Electrical Installations (7th ed.)🕰️ PUE-6 — Rules for Electrical Installations (6th ed., 1985)🇺🇸 NEC — National Electrical Code (NFPA 70)🇪🇺 IEC 60364 / HD 60364 (EU national codes)🌎 NOM-001-SEDE, NBR 5410, AEA 90364, RETIE, NCh 4, CNE🇨🇳 GB 50054, GB 50303, JGJ 16, GB/T 16895 (IEC 60364)🇮🇳 IS 732

Document

DocumentNEC 2023, Article 220 Load calculations
Edition2023
StatusCurrent (latest NEC edition)
Issued byNFPA
Applies toLoad calculations: standard and optional dwelling methods

Document structure

№Chapter / section
220.10–220.20General calculation rules
220.42–220.60Lighting, receptacles, appliances
220.82Optional dwelling method
NEC 2023, Article 210 Branch CircuitsNEC 2023, Article 250 Grounding and BondingNEC 2023, Articles 300 (wiring) and 310 (conductors)NEC 2023, Article 230 ServicesNEC 2023, Article 240 Overcurrent ProtectionNEC 2023, Article 625 EV ChargingNEC 2023, Article 110 General requirementsNEC 2023, Article 220 Load calculationsNEC 2023, Article 517 Medical locationsNEC 2023, Article 500 Hazardous locations

Lighting and receptacles (220.42–220.60)

220.12 3 VA per ft² for dwelling lighting; 220.14(I) 180 VA per receptacle; 220.52 two 20 A kitchen circuits (1500 VA each); 220.54 laundry 1500 VA.

Optional method (220.82)

100% of the first 10 kVA + 40% of the remainder; plus AC units (100%).