NEC 2023, Articles 300 (wiring) and 310 (conductors) — translation

Clause-by-clause translation of NEC Articles 300 and 310: NM cables and EMT, cable protection, burial depths, ampacity per Table 310.16, AWG to mm².

🇷🇺 PUE — Rules for Electrical Installations (7th ed.)🕰️ PUE-6 — Rules for Electrical Installations (6th ed., 1985)🇺🇸 NEC — National Electrical Code (NFPA 70)🇪🇺 IEC 60364 / HD 60364 (EU national codes)🌎 NOM-001-SEDE, NBR 5410, AEA 90364, RETIE, NCh 4, CNE🇨🇳 GB 50054, GB 50303, JGJ 16, GB/T 16895 (IEC 60364)🇮🇳 IS 732

Document

DocumentNEC 2023, Articles 300 (wiring) and 310 (conductors)
Edition2023
StatusCurrent (latest NEC edition)
Issued byNFPA
Applies toWiring methods (300) and conductors/ampacity (310)

Document structure

№Chapter / section
300.1–300.25General wiring methods
310.3–310.10Conductors: types, insulation
310.12Dwelling service simplified sizing
Table 310.16Ampacity table (60/75/90 °C)
NEC 2023, Article 210 Branch CircuitsNEC 2023, Article 250 Grounding and BondingNEC 2023, Articles 300 (wiring) and 310 (conductors)NEC 2023, Article 230 ServicesNEC 2023, Article 240 Overcurrent ProtectionNEC 2023, Article 625 EV ChargingNEC 2023, Article 110 General requirementsNEC 2023, Article 220 Load calculationsNEC 2023, Article 517 Medical locationsNEC 2023, Article 500 Hazardous locations

Wiring (300.1–300.25)

300.4 Cable protection plates at wall/beam penetrations.

300.5 Burial depths: UF cables 0.45 m (18 in), conduits 0.15 m (6 in) with protection, under driveways 0.6 m (24 in); above-ground exits protected.

300.15 Splices only in accessible boxes.

Conductors (310.3–310.10)

310.3 Conductor types per environment: THHN, THWN-2, XHHW-2 (90 °C class).

310.12 Simplified dwelling sizing 120/240 V: up to 100 A — 4 AWG copper (2 AWG aluminium).

Ampacity Table 310.16

Copper at 75 °C, ≤ 3 conductors in conduit: 14 AWG — 20 A; 12 AWG — 25 A; 10 AWG — 35 A; 8 AWG — 50 A; 6 AWG — 65 A; 4 AWG — 85 A; 2 AWG — 115 A; 1/0 — 150 A. Correction factors: ambient, 4–6 conductors 0.8, 7–9 — 0.7.

Practical takeaways

12 AWG (3.31 mm²) — 25 A, close to 2.5 mm² per PUE (27 A). The difference: AWG sizes and 60/75/90 °C columns; dwellings use 75 °C.

Design with GorkyCAD Pro

Automatic single-line diagrams, PUE/GOST/IEC calculations, specification and PDF — from one model.

Start free

Data is for reference. Final design decisions must follow current regulations and a qualified engineer.