BS 7671 (18th ed.): 30 mA RCDs for all sockets, type G sockets, 3/5% voltage drop, EICR checks.
| Document | BS 7671 UK Wiring Regulations |
| Edition | 2018 (18-е изд., ред. 2022) |
| Status | Current (United Kingdom) |
| Issued by | IET (Institution of Engineering and Technology) |
| Applies to | UK wiring regulations: type G sockets, RCDs, EICR |
| № | Chapter / section |
|---|---|
| Part 1–2 | Scope, terms |
| Part 4 | Protection: 30 mA RCDs |
| Part 5 | Sections, type G, voltage drop |
| Part 7 | Special locations |
| Part 6 | EICR verification |
411.3.4 30 mA RCD for all socket circuits ≤ 32 A in dwellings; 300 mA fire RCD recommended at the intake; 0.4 s TN disconnection.
Type G sockets (13 A, fused plugs); 1.5/2.5 mm²; voltage drop 3% lighting / 5% others.
701 bathrooms, 702 pools, 710 medical — per IEC 60364-7.
EICR: homes every 10 years; rentals/commercial every 5 years; pools 3 years.