IEC 60364-5-54 Earthing and protective conductors — translation

IEC 60364-5-54: electrodes (542), PE sizes (table 54.2), bonding (544), PEN (546).

🇷🇺 PUE — Rules for Electrical Installations (7th ed.)🕰️ PUE-6 — Rules for Electrical Installations (6th ed., 1985)🇺🇸 NEC — National Electrical Code (NFPA 70)🇪🇺 IEC 60364 / HD 60364 (EU national codes)🌎 NOM-001-SEDE, NBR 5410, AEA 90364, RETIE, NCh 4, CNE🇨🇳 GB 50054, GB 50303, JGJ 16, GB/T 16895 (IEC 60364)🇮🇳 IS 732

Document

DocumentIEC 60364-5-54 Earthing and protective conductors
Edition2011 (в ред. 2022)
StatusCurrent (IEC 60364-5-54)
Issued byIEC
Applies toEarthing arrangements and protective conductors: electrodes, PE sizes, bonding

Document structure

№Chapter / section
542Earth electrodes
543Protective conductors
544Equipotential bonding
546PEN conductors
IEC 60364-4-41 Protection against electric shockIEC 60364-5-52 Wiring systemsIEC 60364-5-53 Switchgear and surge protectionIEC 60364-7-701 Rooms with baths and showersIEC 60364-4-43 Overcurrent protectionIEC 60364-6 Verification of installationsIEC 62305 Lightning protection (parts 1–4)IEC 60364-7-710 Medical locationsIEC 60364-5-54 Earthing and protective conductorsIEC 60364-7-702 Pools and fountainsBS 7671 UK Wiring RegulationsAS/NZS 3000 Wiring Rules (Australia/NZ)

Electrodes (542)

Rod, strip, plate, ring, foundation electrodes; TT: RA × Ia ≤ 50 V.

PE (543)

Table 54.2: S ≤ 16 → S; 16 < S ≤ 35 → 16 mm²; S > 35 → S/2. Separate PE: 2.5 mm² protected / 4 mm² unprotected.

Bonding (544)

Main bonding in every building; supplementary in bathrooms/pools.

PEN (546)

Copper ≥ 10 mm² / aluminium ≥ 16 mm²; never broken; not through RCDs; PEN split — PE first.