Clause-by-clause translation of IEC 60364-7-701: zones 0–3, 30 mA RCD, IPX4/IPX7, socket restrictions, supplementary bonding.
| Document | IEC 60364-7-701 Rooms with baths and showers |
| Edition | 2006 (в ред. 2021) |
| Status | Current (IEC 60364-7-701) |
| Issued by | IEC |
| Applies to | Rooms with baths and showers: zones 0–3 |
| № | Chapter / section |
|---|---|
| 701.30 | Zones |
| 701.40–701.45 | Shock protection |
| 701.512–701.517 | Equipment selection and installation |
Zone 0 — inside the bath/shower tray; zone 1 — above the bath to 2.25 m; zone 2 — 0.6 m around zone 1 (and basins); zone 3 — 2.4 m around zone 2 (where defined).
701.41 All bathroom circuits: 30 mA RCD (or SELV).
701.41.1 Zones 0–1: SELV only, IPX7 (zone 0) / IPX4 (zone 1).
701.415 Supplementary bonding of all exposed and extraneous parts.
701.512.2 IP: zone 0 — IPX7; zone 1 — IPX4; zone 2 — IPX4; zone 3 — IPX1.
701.512.3 Sockets: forbidden in zones 0–1; zone 2 — allowed ≥ 0.6 m from zone 1 on 30 mA RCD/SELV.
701.55 Luminaires class II or SELV in zone 1.