GOST R 50571.7.701 Bathrooms — translation

Russian adoption of IEC 60364-7-701: zones 0–3, 30 mA RCDs, IPX4/IPX7.

🇷🇺 PUE — Rules for Electrical Installations (7th ed.)🕰️ PUE-6 — Rules for Electrical Installations (6th ed., 1985)🇺🇸 NEC — National Electrical Code (NFPA 70)🇪🇺 IEC 60364 / HD 60364 (EU national codes)🌎 NOM-001-SEDE, NBR 5410, AEA 90364, RETIE, NCh 4, CNE🇨🇳 GB 50054, GB 50303, JGJ 16, GB/T 16895 (IEC 60364)🇮🇳 IS 732

Document

DocumentGOST R 50571.7.701 Bathrooms
Editionактуальные редакции
StatusCurrent (GOST R 50571.7.701)
Issued byRosstandart (adoption of IEC 60364-7-701)
Applies toRooms with baths and showers: zones 0–3

Document structure

№Chapter / section
701.30Zones
701.41Shock protection
701.512–701.55Equipment
PUE 7, Section 1PUE 7, Section 7PUE 7, Chapter 2PUE 7, Chapter 3PUE 7, Section 1PUE 7, Section 1PUE 7, Section 1PUE 7, Chapter 1PUE 7, Section 6 LightingSP 256PUE 7, Section 1PUE 7, Section 1PUE 7, Chapter 2PUE 7, Chapter 4PUE 7, Chapter 7PUE 7, Chapter 7GOST R 50571 Building electrical installations (Russian IEC 60364)PUE 7, Chapter 2PUE 7, Chapter 7SP 158PUE 7, Chapters 2SP 76GOST R 50571Japan: electrical rules (JIS, 100 V)

Zones (701.30)

Zone 0 — bath volume; 1 — to 2.25 m; 2 — 0.6 m around; 3 — 2.4 m.

Protection (701.41)

30 mA RCD or SELV for all circuits; supplementary bonding (701.415).

Equipment

IPX7 zone 0; IPX4 zones 1–2; no sockets in zones 0–1.