Clause-by-clause review of PUE chapter 1.7 (7th ed.): TN-C/TN-S/TN-C-S/TT/IT earthing, direct and indirect contact protection, 30 mA RCDs, protective conductors, bonding. Clause numbers included.
| Document | PUE 7, Section 1.7 Earthing and safety measures |
| Edition | 2002 (ПУЭ-7, гл. 1.7) |
| Status | Current |
| Issued by | Ministry of Energy of Russia (2002–2003) |
| Applies to | All installations up to and above 1 kV: earthing and electrical safety measures |
| № | Chapter / section |
|---|---|
| 1.7.1–1.7.15 | Scope, terms, earthing systems |
| 1.7.16–1.7.31 | Protection against direct contact |
| 1.7.32–1.7.49 | Protection against indirect contact |
| 1.7.50–1.7.67 | Earthing arrangements |
| 1.7.68–1.7.87 | Protective conductors, RCDs |
| 1.7.88–1.7.105 | Equipotential bonding |
| 1.7.106–1.7.118 | Inspection and maintenance |
| 1.7.119–1.7.176 | Requirements for residential, public buildings and outdoor installations |
1.7.3 TN-C: combined neutral and protective conductor (PEN) throughout.
1.7.4 TN-S: separate N and PE throughout.
1.7.5 TN-C-S: PEN combined up to the intake, then split into PE and N — standard for new Russian buildings.
1.7.6 TT: neutral earthed, exposed parts earthed separately.
1.7.7 IT: neutral isolated (or earthed via high impedance), exposed parts earthed separately.
1.7.31 Additional protection: RCD ≤ 30 mA.
1.7.36 Disconnection times (table 1.7.1): 0.4 s at 380/220 V, 0.2 s at 660/380 V.
1.7.45 TT: RCD-based protection, RA×Ia ≤ 50 V.
1.7.51 Earth resistance ≤ 4 Ω in TN systems (10 Ω below 100 kVA).
1.7.63 Underground earthing conductors: copper ≥ 10 mm², aluminium 16 mm², steel 75 mm².
1.7.76/79 Exposed parts to PE; PE separate from N after the PEN split.
1.7.87 Residential group circuits: RCD ≤ 30 mA.
1.7.91 Main bonding in every building: pipes, steelwork, PE, lightning.
1.7.92 Supplementary bonding in bathrooms, saunas, wet rooms.
1.7.99–1.7.101 Bonding conductor sizes: main — ≥ half of the largest PE (6–25 mm² copper); supplementary per table 1.7.5.
1.7.120 No water/gas pipes, cable sheaths or rebar as PE.
1.7.123 Socket earthing contact must connect to PE.
1.7.132 Bathroom sockets: 30 mA RCD line or isolating transformer.
1.7.135 Combining N and PE in final circuits is prohibited.
Section 1.7 is the most cited part of PUE: TN-C-S choice, 30 mA RCDs, main and supplementary bonding, the N–PE prohibition (1.7.135). Harmonized with IEC 60364-4-41 and 5-54.
Automatic single-line diagrams, PUE/GOST/IEC calculations, specification and PDF — from one model.
Start freeData is for reference. Final design decisions must follow current regulations and a qualified engineer.