SP 158: hospital supply categories, medical IT systems, operating theatre lighting, RCDs.
| Document | SP 158.13330.2014 Medical buildings (Russia) |
| Edition | 2014 (СП 158.13330.2014) |
| Status | Current |
| Issued by | Ministry of Construction of Russia |
| Applies to | Medical buildings: supply, lighting, medical equipment |
| № | Chapter / section |
|---|---|
| 5 | Power supply |
| 7 | Lighting |
| 9 | Medical equipment |
Category 1 (special group) for operating theatres/ICU: two sources + DG/battery, 0.5–5 s interruption.
Operating theatres ≥ 1000 lx; emergency lighting with ≥ 1 h autonomy.
Medical IT systems with insulation monitoring (per GOST R 50571.7.710); ≥ 2 identified socket circuits at beds.