PUE 7, Chapter 2.1 Wiring — clause by clause

Clause-by-clause review of PUE chapter 2.1: open and concealed wiring, conduit and trunking, joints, earthing of metal enclosures, wooden houses.

🇷🇺 PUE — Rules for Electrical Installations (7th ed.)🕰️ PUE-6 — Rules for Electrical Installations (6th ed., 1985)🇺🇸 NEC — National Electrical Code (NFPA 70)🇪🇺 IEC 60364 / HD 60364 (EU national codes)🌎 NOM-001-SEDE, NBR 5410, AEA 90364, RETIE, NCh 4, CNE🇨🇳 GB 50054, GB 50303, JGJ 16, GB/T 16895 (IEC 60364)🇮🇳 IS 732

Document

DocumentPUE 7, Chapter 2.1 Wiring
Edition2002 (ПУЭ-7, гл. 2.1)
StatusCurrent
Issued byMinistry of Energy of Russia
Applies toWiring up to 1 kV: open, concealed, in conduit and trunking

Document structure

№Chapter / section
2.1.1–2.1.15Scope, terms
2.1.16–2.1.20Selection of wiring type
2.1.21–2.1.30Open and concealed wiring
2.1.31–2.1.44Conduit and trunking installation
2.1.45–2.1.64Joints, branches, earthing
PUE 7, Section 1PUE 7, Section 7PUE 7, Chapter 2PUE 7, Chapter 3PUE 7, Section 1PUE 7, Section 1PUE 7, Section 1PUE 7, Chapter 1PUE 7, Section 6 LightingSP 256PUE 7, Section 1PUE 7, Section 1PUE 7, Chapter 2PUE 7, Chapter 4PUE 7, Chapter 7PUE 7, Chapter 7GOST R 50571 Building electrical installations (Russian IEC 60364)PUE 7, Chapter 2PUE 7, Chapter 7SP 158PUE 7, Chapters 2SP 76GOST R 50571Japan: electrical rules (JIS, 100 V)

General (2.1.1–2.1.15)

2.1.1 Applies to power, lighting and secondary circuits up to 1 kV.

2.1.5 Open wiring — on surfaces; concealed — inside structures.

Selection (2.1.16–2.1.20)

2.1.19 Sections by current, strength and heating; copper from 1.5 mm².

Open and concealed (2.1.21–2.1.30)

2.1.21–22 Heights: unprotected 2 m, protected/cables 0.5 m.

2.1.23 Concealed in walls — in conduit/chases with protection.

2.1.28 Wall/floor penetrations — in sealed conduit.

Conduit and trunking (2.1.31–2.1.44)

2.1.37 All conductors of a circuit in one conduit.

2.1.38 Conduit ID ≥ 1.5 × cable diameter.

2.1.44 Joints only in junction boxes; no welding hidden in walls.

Joints and earthing (2.1.45–2.1.64)

2.1.45 Joints: welding, crimping, soldering, screw/spring terminals.

2.1.52 Metallic conduits — continuous earthing path.

2.1.58–59 Wooden houses: metal conduits or flame-retardant cable (NYM, VVGng).

Practical takeaways

Chapter 2.1 is the technical basis of any wiring job: sections, conduit sizing 1.5×, joints in boxes (2.1.44), conduit earthing (2.1.52), wooden-house rules (2.1.58–59).